SP007-26
REFRIGERANT CHARGE (R-22 (oz)) ADJUSTMENT
FOR OPTIMUM PERFORMANCE
7
Note: See Performance Data for Pressure/Temperature Charging.
Note: It is not necessary to remove refrigerant for linesets less than 100 feet; however, doing so will provide
some improvement of system efficiency.
Model
ARI
rating pt.
25 ft
25 ft
-10
-10
-25
-25
-25
50 ft
-7
-7
-17
-17
-17
75 ft
-4
-4
-9
-9
-9
100 ft
111
108
125
130
125
125 ft
3
3
8
8
8
150 ft
7
7
8
8
8
Subtract Charge
Add Charge
Factory
Charge
PUG/H18
PUG/H24
PUG/H30
PUG/H36
PUG/H42
101
98
100
105
100
1) Copeland Scroll “KC” Compressors
Model
ARI
rating pt.
25 ft
25 ft
-10
-10
-25
-25
-25
50 ft
-7
-7
-17
-17
-17
75 ft
-4
-4
-9
-9
-9
100 ft
90
98
121
115
127
125 ft
3
3
8
8
8
150 ft
7
7
8
8
8
Subtract Charge
Add Charge
Factory
Charge
PUG/H18
PUG/H24
PUG/H30
PUG/H36
PUG/H42
80
88
96
90
102
2) Copeland Scroll “K4/K3” Compressors