2 )  Before constructing the installation or transfer. 

Do not leave the mounting base being damaged.

        

The damaged base may cause the falling down of the unit which
may give injury.

Install drain piping (hose) according to
this Installation Manual to ensure proper
drainage.

    

Improper drain piping (hose) may cause water
leakage and damage to furniture or other possessions.

Do not touch the metal edges inside the unit without
wearing glove on your hands.

    

Touching directly it may injure your hands.

Do not place objects under the units to avoid damage
of condensation.

       

When the room is high humidity or when the drain pipe is clogged,
water may drip from the unit.

Never install on the place where a combustible gas
might leak.

     

The gas may ignite or explode when the gas leaks and collects
in surroundings of the unit.

For special use as for foods, animals/plants, precision
equipment  or art objects, the applicability should be
confirmed earlier.

     

As the use for the applications other than that
designed originally may result in the deterioration
of the quality.
Consult your dealer in this regard.

When the unit is installed at telecommunication centers
or hospitals, take a proper provision against noise.

    
The erroneous operation of air conditioner may be induced by inverter
equipment, independent power device, medical equipment or
communication equipment.

Do not operate the air conditioner without the air filter
set place.

    

Dust may accumulate, and cause a failure.

Do not touch the compressor or refrigerant
piping without wearing glove on your hands.

     

Touching directly such the parts can cause a burn
or frostbite as it becomes high or low temperature
according to the refrigerant state.

Do not handle the switch with wet hands.

     

Otherwise electric shock can be resulted.

The unit should be securely installed level surface.

      
When the unit inclines, it causes the water leak and the breakdown.
Please confirm the horizontal with the spirit level.

Do not use the unit under a special atmosphere.

     
Installing the unit at the following places may cause a trouble, 
a place where is much machine oil, salt , humidity or dust, 
spa district, a place full of sulfur gas, volatile gas, or corrosive gas,
a place near high frequency processing machine.

Do not wash the unit with water.

        
If washed with water, electric shock may be caused.

At emergency (if you smell something burning), stop
operation and turn the power source switch off.

      

Continuing the operation without eliminating the emergency state may
cause a machine trouble, fire, or electric shock.

Do not remove the panel or the fan guard from the unit
when it is running.

    

You could be injured if you touch rotating, hot or high-voltage parts .

Process the packing material surely.

       

Be sure to safety dispose the packing materials.
Packing materials, such as catches and other metal or wooden parts,
may cause stabs or other injuries.
Tear off and discard plastic packing bags so that children will not play
any of them.
If children play with a plastic bags which was not torn off, it may cause
a risk of suffocation.

2

The base and attachments of the unit should be periodically
checked for looseness, cracks or other damage.

       

If such defects are left uncorrected, the unit may fall and cause personal
injury or property damage.

3 )  Before starting. 

2. Selection of installed place.

Select space for installing unit, which will meet the following
conditions.

Please pay attention to the refrigerant   (Freon gas).

A non flammable, non-toxic, odourless refrigerant is used for this air
conditioner.
The refrigerant is collected on the floor side in the room because the
specific gravity are larger than air. And, it causes the hypoxia accident.

When the refrigerant gas leaks by any chance, the user must ventilates
air enough by stopping the drive of the unit and opening the door.

Place where no direct thermal radiation from other heat sources.
Place where no possibility of short cycle operations caused by exhaust
heat from unit.
Place where no possibility of annoying neighbors by noise from unit.
Place where no exposition to strong wind.
Place where no possibility of snow wind.
Place where with strength which bears weight unit.
Because of the possibility of fire, do not install unit to the space where
generation, inflow, stagnation, and leak of combustible gas is expected.
Avoid unit installation in a place where acidic spray (sulfur) are often used.
Place without dispersion of oil and steam.

Remote controller is not allowed to install for the place
where direct sunshine strikes.

Remote controller should be pushed with finger.

     

It occasionally causes the electric shock and the breakdown.

Please do not use the unit in the following places.

Place where a lot of oil (The machine oil is contained), moistures,
and dust exist.
Place where a lot of salinity such as beach districts exists.
Place where sulfur gas, volatile gas, and corroded gas are filled.
Place where acid solution is frequently used.
Place where special spray is frequently used.
Hot spring zone.
Near machine (high cycle welding machine etc.) generating high cycle.
Place where ventilation entrance of unit is closed by snowfall.
The main body might corrode when the unit is used in such a place,
the refrigerant leak, the performance of the unit decrease remarkably,
and it cause the damage of parts of the unit.

Be very careful about unit transportation.

   
When carrying in unit, be sure to support it at four points.
Carrying in and lifting with 3-point support may make unit unstable,
resulting in a fall of it.
The unit should not be carried by only one person if it is more than 20 kg.
It occasionally causes the damage of the unit and health to be impaired.
Some units use PP bands for packing. Do not use any PP band for
delivery purpose. It may cause the injury.
Do not touch the heat exchanger fins with your bare hands.
Doing so may cut your hands.

Do not operate the air conditioner without the eliminator
set place.

   

Drain may drop into down flow supply duct.

Summary of Contents for PRC- 8MYA

Page 1: ...s manual to have the correct safe use before installation 2 Please keep this manual in the place where it is always seen to use this manual with Operation manual after reading 3 The customer must not install and not transfer the unit by themselves Safety and the function cannot be secured INSTALLATION MANUAL Service ref PRC 8MYA 03 PRC 10MYA 03 PRC 12MYA 03 PRC 15MYA 03 PRC 20MYA 03 PRC 24MYA 03 P...

Page 2: ...tallation may cause a fire electric shock or water leakage Use only the specified refrigerant R 22 to charge the refrigerant circuit Do not mix it with any other refrigerant and do not allow air to remain in the circuit Air enclosed in the circuit can cause high pressure resulting in a rupture and other hazards Arrange the configuration of wiring not to bring up the panel and terminal cover and fa...

Page 3: ...and discard plastic packing bags so that children will not play any of them If children play with a plastic bags which was not torn off it may cause a risk of suffocation 2 The base and attachments of the unit should be periodically checked for looseness cracks or other damage If such defects are left uncorrected the unit may fall and cause personal injury or property damage 3 Before starting 2 Se...

Page 4: ... 8 PRC 10 360 Weight of unit kg 390 PRC 12 395 4 Preparation before installation unit mm Except Drain size unit inch Condenser inlet Electrical control circuit compressor service Electrical control circuit compressor service Evaporator coil fan assy service 300 300 700 1200 Condenser inlet 300 Condenser inlet 300 Evaporator coil service 1000 300 700 300 Evaporator coil fan assy service A 1500 Cond...

Page 5: ...00 200 200 200 200 72 B DETAIL A DETAIL 2032 25 2032 25 15 25 15 25 PRC 15 PRC 20 655 Weight of unit kg 755 PRC 24 765 AIR RETURN AIR SUPPLY A B BOX CONTROL CONDENSER AIR INLET 3 SIDES CONDENSER AIR INLET 3 SIDES AIR WIRING HOLE 6 15X25MTGHOLES BOTH SIDE DRAIN R1 RETURN AIR SUPPLY 3 SIDES AIR INLET CONDENSER 140 1820 140 25 2142 BOLT PITCH 25 46 2100 46 51 51 2100 250 800 BOLT PITCH 800 BOLT PITCH...

Page 6: ... Duct Roof curb Duct Duct work length 850mm or more Duct connection with a vertical air plenum 5 2 Lifting method When the unit is to be lifted and moved attach ropes to the suspension plates 4 p c s provided on the top of the unit When the unit is lifted it is center of gravity tends to shift the unit one side and so balance such as that in the figure below should be attained The angles at which ...

Page 7: ...ain switch fuse field supply Power supply wiring for unit unit f g Connection wiring for unit remote controller Earth b c g PE e f In case of PRC 15 20 24 32Y d Band for wires Screw for earth connection Terminal block for power supply wires Terminal block for connection wires to switch box Field supply or LCD remote controller Option PAC 204RC Control module of unit PRC 15 20 24 Band for wires Scr...

Page 8: ...ally FUNCTION Not change Not change Not change Note Seal the wire lead in hole completely with putty TB1 DIP SW TB2 1 ON 2 3 4 Controller board Outline Key cover open COMP2 COMP1 4WV ERROR 24VAC N 24VAC L FAN HI FAN LO EXT SENSOR JH INT EXT Refer to 2 4 Refer to 2 3 Refer to 2 5 1 This function can not use at above models because the fan speed of these models is constant 2 If need this function pl...

Page 9: ...75A 100A PRC 20 PRC 24 PRC 32 100A 100A 175A NV100 CP 100mA 0 1s or less NV100 CP 100mA 0 1s or less NV225 CP 100mA 0 1s or less 100A 100A 175A 8 Before starting the trial run After having installed the unit check that Phase protector is installed in PRC 8 10 15 20 due to scroll compressor But not installed in PRC 12 24 32 because reciprocating compressor are installed Breaker capacity 1 The unit ...

Page 10: ... the contact address telephone number on the operation manual before handing it to the customer HEAD OFFICE MITSUBISHI DENKI BLDG MARUNOUCHI TOKYO 100 0005 TELEX J24532 CABLE MELCO TOKYO Specifications subject to change without notice ...