PMFY-3
2012 PMFY-P-NBMU-ER5 (October 2012)
© 2012 Mitsubishi Electric US, Inc.
Model
PMFY-P06NBMU-ER5
PMFY-P08NBMU-ER5
PMFY-P12NBMU-ER5
PMFY-P15NBMU-ER5
Power source
1-phase 208-230 v 60Hz
Cooling capacity *1
(Nominal)
Btu/h
6,000
8,000
12,000
15,000
kW
1.8
2.3
3.5
4.4
Power input
kW
0.04
0.04
0.04
0.05
Current input
A
0.20
0.20
0.21
0.26
Heating capacity *2
(Nominal)
Btu/h
6,700
9,000
13,500
17,000
kW
2.0
2.6
4.0
5.0
Power input
kW
0.04
0.04
0.04
0.05
Current input
A
0.20
0.20
0.21
0.26
External finish
-
External dimension H x W x D
in.
9-1/16 x 31-31/32 x 15-9/16 9-1/16 x 31-31/32 x 15-9/16 9-1/16 x 31-31/32 x 15-9/16 9-1/16 x 31-31/32 x 15-9/16
mm
230 x 812 x 395
230 x 812 x 395
230 x 812 x 395
230 x 812 x 395
Net weight
lbs (kg)
31 (14)
31 (14)
31 (14)
31 (14)
Decoration
panel
Model
PMP-16BMUW
PMP-16BMUW
PMP-16BMUW
PMP-16BMUW
External finish
6.4Y 8.9/0.4
Dimension
in.
1-3/16 x 39-3/8 x 18-17/32
1-3/16 x 39-3/8 x 18-17/32
1-3/16 x 39-3/8 x 18-17/32
1-3/16 x 39-3/8 x 18-17/32
H x W x D
mm
30 x 1,000 x 470
30 x 1,000 x 470
30 x 1,000 x 470
30 x 1,000 x 470
Net Weight
lbs (kg)
7(3)
7(3)
7(3)
7(3)
Heat exchanger
Cross fin
FAN
Type x Quantity
Line flow fan x 1
Line flow fan x 1
Line flow fan x 1
Line flow fan x 1
External
static pressure
in.WG
0.000 (208v)
0.000 (208v)
0.000 (208v)
0.000 (208v)
Pa
0
0
0
0
in.WG
0.000 (230v)
0.000 (230v)
0.000 (230v)
0.000 (230v)
Pa
0
0
0
0
Motor type
DC Brushless
Driving
mechanism
Direct-driven
Airflow rate
(Low-Mid1-
Mid2-High)
CFM
230-254-283-307
258-283-304-328
258-283-304-328
272-307-343-378
m3 / min
6.5-7.2-8.0-8.7
7.3-8.0-8.6-9.3
7.3-8.0-8.6-9.3
7.7-8.7-9.7-10.7
L / s
108-120-133-145
122-133-143-155
122-133-143-155
128-145-162-178
Sound pressure level
(Low-Mid1-Mid2-High)
(measured in anechoic room)
dB <A>
27-30-33-35 (208-230v)
32-34-36-37 (208-230v)
32-34-36-37 (208-230v)
33-35-37-39 (208-230v)
Insulation material
PS foam, Polyethylene foam
Air filter
PP honeycomb
Protection device
Fuse
Refrigerant control device
LEv
Connectable outdoor unit
R410A CITY MULTI
R410A CITY MULTI
R410A,R22 CITY MULTI
R410A,R22 CITY MULTI
Diameter of
refrigerant
pipe (O.D.)
Liquid (R410A)
(R22)
in. (mm)
1/4 (6.35) Flare
-
1/4 (6.35) Flare
-
1/4 (6.35) Flare
1/4 (6.35) Flare
1/4 (6.35) Flare
1/4 (6.35) Flare
Gas (R410A)
(R22)
in. (mm)
1/2 (12.7) Flare
-
1/2 (12.7) Flare
-
1/2 (12.7) Flare
1/2 (12.7) Flare
1/2 (12.7) Flare
1/2 (12.7) Flare
Field drain pipe size
in. (mm)
O.D. 1 (26)
O.D. 1 (26)
O.D. 1 (26)
O.D. 1 (26)
Drain lift mechanism
in. (mm)
23-5/8 (600)
23-5/8 (600)
23-5/8 (600)
23-5/8 (600)
Drawing
External
BH01C848
Wiring
BH79C630
Standard
attachment
Document
Accessory
Installation Manual,Installation Book
Optional
parts
External heater adapter
CN24RELAY-KIT-CM3
CN24RELAY-KIT-CM3
CN24RELAY-KIT-CM3
CN24RELAY-KIT-CM3
Remark
Installation
Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be referred to
the Installation Manual.
Ventilation Air: Providing sufficient ventilation air is an important part of every building design.
ASHRAE standard 62 provides the minimum ventilation air requirements. Also check local codes.
1. sPECiFiCatiONs
Note:
*1 Nominal cooling conditions
*2 Nominal heating conditions
Unit converter
Indoor:
80degF D.B. / 67degF W.B.
(26.7degC D.B. / 19.4degC W.B.)
70degF D.B. (21.1degC D.B.)
kcal/h = kW x 860
BTU/h = kW x 3,412
Outdoor:
95degF D.B. (35degC D.B.)
47degF D.B. / 43degF W.B.
(8.3degC D.B. / 6.1degC W.B.)
cfm = m3/min x 35.31
lbs = kg / 0.4536
Pipe length:
25 ft. (7.6 m)
25 ft. (7.6 m)
*Above specification data is
subject to rounding variation.
Level difference:
0 ft. (0 m)
0 ft. (0 m)
*Due to continuing improvement, above specification may be subject to change without notice.