27
(3) Auto vane control
Auto vane position is set to 35degrees(SW5-3:OFF) or 20 degrees(SW5-3:ON) airflow at the start-up of COOL operation. It
can then be changed by the remote controller.
Auto vane operation can be changed between STOP mode (fixed operation) and SWINGmode by AIR DISCHARGE
SWING/STOP button on the remote controller.
(a) Stop mode (fixed operation)
( i ) At start-up of COOL operation, the auto vane is set to 10 degrees airflow direction.
( ii ) Airflow direction can be changed with
button.
(b) SWING mode.
( i ) The vane motor turns ON when the SWING mode is selected.
The vane motor is continuously ON during SWING mode.
( ii ) The operation in SWING mode can be changed to the fluctuant operation by turning ON the dipswitch SW1-2.
(iii) When SWING mode is changed to STOP mode, the airflow direction returns to the position of the last STOP mode.
When 55°/45 degrees or 65°/65 degrees airflow is selected with the LOW fan speed in COOL operation, “AUTO RETURN”
will appear below the temperature display. One hour later, the airflow direction returns to 35/25 degrees automatically and
“AUTO RETURN” will disappear. If the airflow direction is set to 35/20 degrees during “AUTO RETURN” indication, the
time counting for AUTO RETURN is cancelled.
1
Fan speed : LOW
2
Fan speed : HIGH
35°/20°
55°/45°
65°/65°
35°/20°
55°/45°
65°/65°
SWING
SWING
(SW5-3:OFF/ON)
(SW5-3:OFF/ON)
45°/35°
35 /20
35 /20
55 /45
45 /35
65 /65
AUTO RETURN
AUTO RETURN
55 /45
65 /65
<AUTO RETURN>
1
Fan speed : LOW
2
Fan speed : HIGH