
6
Caution:
• Before you start cleaning, stop operation and turn OFF the power supply.
• Indoor units are equipped with filters to remove the dust of sucked-in air.
Clean the filters using the methods shown in the following sketches.
■
PLFY-NAMU-A
1
Pull the knob on the intake grille in the direction indicated by the arrow and it
should open.
2
Open the intake grille.
3
Release the knob on the center edge of the intake grille and pull the filter forward
to remove the filter.
A
Knob
B
Grille
C
Intake grille
D
Filter
4. Care and cleaning
B
A
D
C
■
PLFY-NAMU-A
5. Troubleshooting
State of Machine
It does not run.
Air flows out but it does not cool enough or heat
enough.
Cool air or warm air does not come out.
The sound of the exhaust and rotation of the motor
can still be heard after stop of running.
Troubleshooting
Press the [ON/OFF] button after power restoration.
Check the set temperature.
Clean up the filter.
Wait for a while.
The restart-preventing circuit is in operation for 3 minutes.
Wait for a while.
Indoor unit operation was started anew during the heating and defrosting operation.
Wait for 3 minutes.
The machine stops after running a drain-up mechanism for 3 minutes when air-cooling operation is stopped.
Before you ask for repair service, check the following points:
The following symptoms are not air conditioner failures:
• The air blown out from the air conditioner can sometimes give off odors. This is due to cigarette smoke contained in the air of the room, the smell of cosmetics, the walls,
furniture, etc., absorbed in the air conditioner.
• A hissing noise can be heard immediately after the air conditioner is started or stopped. This is the sound of the refrigerant flowing inside the air conditioner. The problem is
insignificant.
• The air conditioner sometimes snaps or clicks at the beginning or end of cooling/heating operation. This is the sound of friction on the front panel and other sections due to
inflation and contraction caused by temperature change. The problem is insignificant.
Range of application
The range of working temperatures for both the indoor and outdoor units of the series Y, R2, Multi-S is as below.
Caution:
The use of your air conditioner outside the range of working temperature and humidity can result in serious failure.
Note: As an applicable humidity standard for both indoors and outdoors, we recommend use within a range of 30 - 80% relative humidity.
PUHY
23
°
F - 110
°
FDB
5
°
F - 60
°
FWB
Mode
Cooling
Heating
Indoor unit
59
°
F - 75
°
FWB
59
°
F - 81
°
FDB
Outdoor unit
PURY
23
°
F - 110
°
FDB
5
°
F - 60
°
FWB
PUMY
23
°
F - 115
°
FDB
5
°
F - 60
°
FWB