EN-8
en
4. Connecting the Plasma Quad Connect
(For details on each system, see the relevant instruction manual.)
A space of 100 mm or more is necessary between the indoor unit and the ceiling to install the product.
Turn off the breaker of the air conditioner before installation.
Refer to the installation manual of the indoor unit for work performed on the indoor unit.
Be sure to follow the instructions in this manual when installing the product. Installation error may cause fire, electrical
shock, malfunction or reduction in capacity.
Install the Plasma Quad Connect above the indoor unit at a height of 2 m or higher from the floor.
Preparation for the spacer to attach the Plasma Quad Connect
1) Divide the spacer into 2 pieces at the connected part. (Fig. 2)
Fig. 2
* 32 mm if the depth of the indoor unit is 200 mm or less.
Use a spacer to ensure the dimensions described above.
Ceiling
Indoor unit
15.5 mm
100 mm
or more
10 mm*
Installation plate
2
2) Fix the spacer A and B with tape and use them when the depth of the indoor unit is less than 200 mm.
Use only the spacer A when it is 200 mm or more. (Fig. 3)
Note: Spacer is used to ensure space to open/close the FRONT PANEL.
Fig. 3
Installing the Plasma Quad Connect
1) Remove the panel.
2) Put the spacer on the top surface of the BOX and fix it with tape temporarily. (Fig. 4)
Fig. 4
The marks
should point in the same direction.
Fix both edges.
The BOX side should butt up to the protruding part
of the spacer.
The end should butt up to the wall.
A5_JG79Y920H01_01En.indd 8
2021/02/22 9:05:58