background image

1

.  Test run

Water supply pump

Water (about 1000cc, 1/4 gal)

Drain plug

Pour water through outlet

.Be carefule not to spray water

  into the drain pump mechanism.

.4.  Check of drainage (Fig. -5)

•  Ensure that the water is being properly drained out and that no water is leaking 

from joints.

When electric work is completed.

Pour water during cooling operation and check.

When electric work is not completed.

Pour water during emergency operation and check.

* Drain pan and fan are activated simultaneously when single phase 220-240V is 

turned on to S1 and S2 on terminal block after the connecter (SWE) on controller 

board in the electrical branch box is set to ON.

Be sure to turn it back to the former state after work.

•  If the unit cannot be operated properly after the test run has been performed, refer to the following table to remove the cause.

Symptom

Cause

Wired remote controller

LED 1, 2 (PCB in outdoor unit

PLEASE WAIT

For about 2 minutes 
after power-on

After LED 1, 2 are lighted, LED 2 is turned 
off, then only LED 1 is lighted. (Correct 
operation)

•For about 2 minutes after power-on, operation of the remote 

controller is not possible due to system start-up. (Correct 
operation)

PLEASE WAIT 

Error code

Subsequent to about 
2 minutes after power-
on

Only LED 1 is lighted. 

 LED 1, 2 blink.

•Connector for the outdoor unit’s protection device is not 

connected.

•Reverse or open phase wiring for the outdoor unit’s power 

terminal block (L1, L2, GR)

Display messages do not appear 
even when operation switch is 
turned ON 
(operation lamp does not light up).

Only LED 1 is lighted. 

 LED 1 blinks 

twice, LED 2 blinks once.

•Incorrect wiring between indoor and outdoor units (incorrect 

polarity of S1, S2, S3)

•Remote controller wire short

On the IR wireless remote controller with condition above, following phenomena take place.

•  No signals from the remote controller are accepted.

•  Operation lamp is blinking.

•  The buzzer makes a short ping sound.

Note:

Operation is not possible for about 30 seconds after cancellation of function selection. (Correct operation)

For description of each LED (LED1, 2, 3) provided on the indoor controller, refer to the following table.

LED 1 (power for microcomputer)

Indicates whether control power is supplied. Make sure that this LED is always lit.

LED 2 (power for remote controller)

Indicates whether power is supplied to the remote controller. This LED lights only in the case of 
the indoor unit which is connected to the outdoor unit refrigerant address “0”.

LED 3 (communication between indoor and outdoor units)

Indicates state of communication between the indoor and outdoor units. Make sure that this LED 
is always blinking.

01_RG79D307K02_EN.indd   12

2010/09/01   11:03:29

Summary of Contents for PLA-A-BA4 Series

Page 1: ...A4 English INSTALLATION MANUAL For safe and correct use read this manual and the outdoor unit installation manual thoroughly before installing the air conditioner unit FOR INSTALLER 01_RG79D307K02_EN indd 1 2010 09 01 11 03 22 ...

Page 2: ...e gases may leak be produced flow or accumulate If combustible gas accumulates around the unit fire or explosion may result Do not keep food plants caged pets artwork or precision instruments in the direct airflow of the indoor unit or too close to the unit as these items can be damaged by temperature changes or dripping water When the room humidity exceeds 80 or when the drainpipe is clogged wate...

Page 3: ... The method for using the template and the gauge is shown Before using check the dimensions of template and gauge because they change due to fluctuations of temperature and humidity The dimensions of ceiling opening can be regulated within the range shown in Fig 3 2 so center the main unit against the opening of ceiling ensuring that the respective opposite sides on all sides of the clearance betw...

Page 4: ...prior to installation of the decorative cover or when applying ceiling materials 3 7 Confirming the position of main unit and tightening the suspension bolts Fig 3 8 Using the gauge attached to the grille ensure that the bottom of the main unit is properly aligned with the opening of the ceiling Be sure to confirm this otherwise condensation may form and drip due to air leakage etc Confirm that th...

Page 5: ...n pipe should be wrapped with polyethylene foam insulation materials specific gravity of 0 03 thickness of 9 mm 23 64 inch or more Apply thin layer of refrigerant oil to pipe and joint seating surface before tightening flare nut Use two wrenches to tighten piping connections Use refrigerant piping insulation provided to insulate indoor unit connections Insulate carefully B Flare nut tightening tor...

Page 6: ...ised B Downward slope 1 100 or more M Odor trap Grouped piping D O D ø32 mm 1 1 4 inch PVC TUBE H Downward slope 1 100 or more E Make it as large as possible I O D ø38 mm 1 1 2 inch PVC TUBE for grouped piping 9 mm 23 64 inch or more insulation F Indoor unit G Make the piping size large for grouped piping J Up to 850 mm 33 7 16 inch 1 Connect the drain socket supplied with the unit to the drain po...

Page 7: ...d 6 1 1 Indoor unit power supplied from outdoor unit The following connection patterns are available The outdoor unit power supply patterns vary on models 1 System S1 S2 L N 1 2 S1 S2 S3 S3 A B C D E F G I H CN105 RED S1 S2 L N 1 2 S1 S2 S3 1 2 S1 S2 S3 S3 A B C D E F G G E Affix label A that is included with the manuals near each wiring diagram for the indoor and outdoor units A Outdoor unit powe...

Page 8: ...ir of an indoor unit PC board and a IR wireless remote controller is assigned to the same pair No 4 IR wireless remote controller pair number setting operation Fig 6 5 Press the SET button with something sharp at the end Start this operation from the status of IR wireless remote controller display turned off MODELSELECT blinks and Model No is lighted Press the min button twice continuously Pair No...

Page 9: ...n from the status of IR wireless remote controller display turned off CHECK is lighted and 00 blinks Press the temp button once to set 50 Direct the IR wireless remote control ler toward the receiver of the indoor unit and press the h button Setting the unit number Press the temp buttons and to set the unit number 00 Direct the IR wireless remote controller toward the receiver of the indoor unit a...

Page 10: ...t equipped with outdoor air intake 2 Supported indoor unit is equipped with outdoor air intake 3 Power voltage 230 V 04 104 1 208 V 2 Select unit numbers 01 to 03 or all units AL wired remote controller 07 wireless remote controller Mode Settings Mode No Setting no Initial setting setting Wired remote controller RF thermostat Filter sign 100Hr 07 107 1 2500Hr 2 No filter sign indicator 3 Fan speed...

Page 11: ...ontrol system error memory error etc No sound E0 E3 Remote controller transmission error No sound E1 E2 Remote controller control board error No sound No corresponding Output pattern B Errors detected by unit other than indoor unit outdoor unit etc IR wireless remote controller Wired remote controller RF thermostat Symptom Remark Beeper sounds OPERATION INDICATOR lamp blinks Number of times Check ...

Page 12: ...er power on Only LED 1 is lighted LED 1 2 blink Connector for the outdoor unit s protection device is not connected Reverse or open phase wiring for the outdoor unit s power terminal block L1 L2 GR Display messages do not appear even when operation switch is turned ON operation lamp does not light up Only LED 1 is lighted LED 1 blinks twice LED 2 blinks once Incorrect wiring between indoor and out...

Page 13: ...er panel Slide the corner panel as indicated by the arrow to remove the corner panel Fig 9 3 Fig 9 4 Intake grille Grille Intake grille levers Grille hook Hole for the grille s hook Corner panel Screw Detail 9 3 Selection of the air outlets For this grille the discharge direction is available in 11 patterns Also by setting the wired remote controller to the appropriate settings you can adjust the ...

Page 14: ...PLP 42BALM the connector of wireless sensor cable is also connected to connecor CN90 on indoor controller board The lead wire of grille is passed through the catch of bell mouth of the unit perfectly The remaining lead wire is tied with clamp of the unit and put the cover of the unit again with 2 screws Note Do not put the remaining lead wire in electrical branch box of the unit 9 5 Locking the up...

Page 15: ...on procedures 10 Easy maintenance function For PUZ A PUY A application only Only for wired remote cpontroller By using the maintenance mode you can display many types of maintenance data on the wired remote controller such as the heat exchanger temperature and com pressor current consumption for the indoor and outdoor units This function can be used whether the air conditioner is operating or not ...

Page 16: ...handing it to the customer This product is designed and intended for use in the residential commercial and light industrial environment HEAD OFFICE TOKYO BLDG 2 7 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN Printed in Japan RG79D307K02 01_RG79D307K02_EN indd 16 2010 09 01 11 03 34 ...

Reviews: