(3) SW3 (Emergency operation switch)
1 2
Normal operation
ON
OFF
1 2
For emergency cooling
ON
OFF
1 2
For emergency heating
ON
OFF
(4) SW5 (Model selector)
1 2 3 4
ON
OFF
1 2 3 4
ON
OFF
SW5-1) Not for use.
SW5-2) OFF: For models with heat pump
ON : For models with cooling only
SW5-3) Not for use.
SW5-4) Keep this switch at OFF.
(5) SW6 (Address selector)
Single control
Twin control
1 2 3
ON
OFF
SW6-1
1 2 3 4
ON
OFF
5 6
OFF
ON(Twin NO.1)
SW6-2
OFF
ON(Twin NO.2)
SW6-3
OFF
OFF
SW6-4
OFF
OFF
(6) SW7 (Model selector)
Switch to set the output of phase-controlled indoor fan motor.
Address setting is available at any time.
The initial factory setting by is based on each capacity.
Service Ref.
SW7
PKH-2GKLA
(7) SW8
SW8-1~5) Not for use.
SW8-6) OFF: For 240, 230V power supply
ON : For 220V power supply
Triple control
ON(Triple NO.1)
ON(Triple NO.2)
ON(Triple NO.3)
ON
(2) SW2 (Address selector)
1 2 3 4 5 6
ON
OFF
Used in setting the unit-address for group control.
For further information, refer to page 56.
(8) SW9
1 2 3 4
ON
OFF
5
SW9-1~5) Keep this switch.
The black square ( ) indicates a switch position.
OC231A