1. SPECIFICATIONS
Model
PKFY-P06NBMU-E
PKFY-P08NBMU-E
PKFY-P12NHMU-E
PKFY-P15NHMU-E
Power source
1-phase 208/230V 60Hz
Cooling capacity (Nominal) *1
BTU / h
6,000
8,000
12,000
15,000
kW
1.8
2.3
3.5
4.4
Power input
kW
0.03
0.03
0.03
0.03
Current input
A
0.15
0.15
0.30
0.30
Heating capacity (Nominal) *2
BTU / h
6,700
9,000
13,500
17,000
kW
2.0
2.6
4.0
5.0
Power input
kW
0.03
0.03
0.03
0.03
Current input
A
0.15
0.15
0.30
0.30
MCA
A
0.19
0.19
0.38
0.38
External finish
Plastic, MUNSELL (1.0Y 9.2/0.2)
External dimension HxWxD
in.
11-5/8 x 32-1/8 x 8-7/8
11-5/8 x 32-1/8 x 8-7/8
11-5/8 x 35-3/8 x 9-13/16
11-5/8 x 35-3/8 x 9-13/16
mm
295x815x225
295x815x225
295x898x249
295x898x249
Net weight
lbs (kg)
22 (10)
22 (10)
29(13)
29(13)
Heat exchanger
Cross fin (Aluminum fin and copper tube)
FAN
Type x Quantity
Line flow fan x 1
Line flow fan x 1
Line flow fan x 1
Line flow fan x 1
External static
pressure
in.WG
0.000(208V)
0.000(208V)
0.000(208V)
0.000(208V)
Pa
0
0
0
0
in.WG
0.000(230V)
0.000(230V)
0.000(230V)
0.000(230V)
Pa
0
0
0
0
Motor Type
1-phase induction
motor
1-phase induction motor
DC motor
DC motor
Motor output
kW
0.008
0.008
0.030
0.030
Driving mechanism
Direct-driven by motor
Air flow rate
(Low-Mid1-Mid2-
High)
cfm
170-180-200-210
170-180-200-210
320-355-390
320-370-405
m
3
/ min
4.9-5.2-5.6-5.9
4.9-5.2-5.6-5.9
9-10-11
9-10.5-11.5
L/s
82-87-93-98
82-87-93-98
150-167-183
150-175-192
Sound pressure level
(Low-Mid1-Mid2-High)
(measured in an anechoic room)
dB <A>
32-33-35-36
32-33-35-36
34-38-42
34-38-42
Insulation material
Polyethylene sheet
Air filter
Polypropylene Honeycomb
Protection device
Fuse
Refrigerant control device
LEV
Connectable outdoor unit
R410A , R22 CITY MULTI
Diameter of
refrigerant pipe
Liquid (R410A)
in.(mm)
1/4(6.35) Flare
1/4(6.35) Flare
1/4(6.35) Flare
1/4(6.35) Flare
(R22)
1/4(6.35) Flare
1/4(6.35) Flare
1/4(6.35) Flare
1/4(6.35) Flare
Gas (R410A)
in.(mm)
1/2(12.7) Flare
1/2(12.7) Flare
1/2(12.7) Flare
1/2(12.7) Flare
(R22)
1/2(12.7) Flare
1/2(12.7) Flare
1/2(12.7) Flare
1/2(12.7) Flare
Field drain pipe size
in.(mm)
I.D. 5/8(16)
I.D. 5/8(16)
I.D. 5/8(16)
I.D. 5/8(16)
Drawing
External
-
-
-
-
Wiring
-
-
-
-
Refrigerant cycle
-
-
-
-
Standard
attachment
Document
Installation Manual, Instruction Book
Accessory
-
-
-
-
Optional parts
External heater adapter
PAC-725AD
PAC-725AD
CN24RELAY-KIT-CM3
CN24RELAY-KIT-CM3
Remarks
* Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and
other items shall be referred to the Installation Manual.
Ventilation Air: Providing sufficient ventilation air is an important part of every building design.
ASHRAE standard 62 provides the minimum ventilation air requirements. Also check local codes.
Note:
*1 Nominal cooling conditions
*2 Nominal heating conditions
Unit converter
Indoor:
80degF D.B./ 67degF W.B.
70degF D.B.
kcal =kW x 860
(26.7degC D.B./ 19.4degC W.B.)
(21.1degC D.B.)
BTU/h =kW x 3,412
Outdoor:
95degF D.B. (35degC D.B.)
47degF D.B./43degF W.B.
(8.3degC D.B./6.1degC W.B.)
cfm =m
3
/min x 35.31
lb =kg / 0.4536
Pipe length:
25ft.(7.6m)
25ft.(7.6m)
* Above specification data is subject to rounding
variation.
Level difference:
0ft.(0m)
0ft.(0m)
* Due to continuing improvement, above specifications may be subject to change without notice.