7-2. FUNCTION OF DIP-SWITCH
ON
OFF
1 2 3 4 5 6
1
2
3
4
5
6
7
8
9
10
1~6
1
2
3
4
5
6
7
8
1~4
Thermistor<Intake temperature
detection>position
ON
OFF
Filter clogging detection
Provided
Not provided
Filter life
2,500hr
100hr
Air intake
Effective
Not effective
Remote indication switching
Thermostat ON signal indication Fan output indication
Humidifier control
Operational while the heat is ON
Operational, depending on the condition
Air flow st
Low
Extra low
Heat thermostat OFF
Setting air flow
Reset to SW1-7
Auto reset function
Effective
Not effective
Power ON/OFF
Effective
Not effective
Heat pump/Cool only
Cooling only
Heat pump
Louver
Available
Not available
Vane
Available
Not available
Vane swing function
Available
Not available
Vane horizontal angle
Second setting
First setting
Vane cooling limit angle setting
Horizontal angle
Down blow
9
10
Heating 4deg up
Not effective
Effective
ON
OFF
1 2 3 4
ON
OFF
1 2 3 4 5 6
ON
OFF
1 2 3 4 5 6
MODELS
SW2
MODELS
SW2
MODELS
SW2
PEFY-
P20VMM-E
PEFY-
P25VMM-E
PEFY-
P40VMM-E
PEFY-
P50VMM-E
PEFY-
P80VMM-E
Address board
Indoor controller board
Indoor controller board
Indoor controller board
<At delivery>
SW4
Unit
Selection
SW3
Function
Selection
SW2
Capacity
code
setting
SW1
Mode
Selection
Switch Pole
Function
Built-in remote controller
Indoor unit
Set while the unit is off.
<At delivery>
Set for each capacity.
Set while the unit is off.
Set while the unit is off.
Operation by switch
Remarks
ON
OFF
1 2 3 4 5 6
PEFY-
P100VMM-E
PEFY-
P32VMM-E
PEFY-
P63VMM-E
ON
OFF
1 2 3 4 5 6
PEFY-
P125VMM-E
ON
OFF
1 2 3 4 5 6
ON
OFF
1 2 3 4 5 6
ON
OFF
1 2 3 4 5 6
ON
OFF
1 2 3 4 5 6
Note
:The DipSW setting is effective during unit stopping ( remote controller OFF ) for SW1,2,3 and 4 commonly and the
power source is not required to reset.
1 2 3 4
ON
OFF
P20~P80
P100~P140
PEFY-
P71VMM-E
ON
OFF
1 2 3 4 5 6
PEFY-
P140VMM-E
ON
OFF
1 2 3 4 5 6
:When both SW1-7 and SW1-8 are being set to ON, the fan stops at the heating thermostat OFF.
16