31
Refrigerant piping length (one way)
5m
10m
15m
20m
25m
30m
35m
40m
45m
50m
55m
60m
65m
70m
75m
80m
Service Ref.
PEAD-RP3EA
1
PEAD-RP4EA
1
PEAD-RP5EA
1
PEAD-RP6EA
1
PEAD-RP2EA
PEAD-RP1.6EA
PEAD-RP2.5EA
1.00
1.00
1.00
0.997
0.997
0.997
0.994
0.994
0.994
0.991
0.991
0.991
0.988
0.988
0.988
0.985
0.985
0.985
0.982
0.982
0.982
0.979
0.979
0.979
0.976
0.976
0.976
0.973
0.973
0.973
0.970 0.967 0.964 0.961 0.958
1.00 0.997 0.994 0.991 0.988 0.985 0.982 0.979 0.976 0.973 0.970 0.967 0.964 0.961 0.958
1.00 0.997 0.994 0.991 0.988 0.985 0.982 0.979 0.976 0.973 0.970 0.967 0.964 0.961 0.958
1.00 0.997 0.994 0.991 0.988 0.985 0.982 0.979 0.976 0.973
1.00 0.997 0.994 0.991 0.988 0.985 0.982 0.979 0.976 0.973
Heating capacity correction factor
PEAD-RP
·
EA/PUHZ-RP
·
VHA
5m
10m
15m
20m
25m
30m
35m
40m
45m
50m
Refrigerant piping length (one way)
Service Ref.
PEAD-RP3EA
1
PEAD-RP4EA
1
PEAD-RP5EA
1
PEAD-RP6EA
1
PEAD-RP2EA
PEAD-RP1.6EA
PEAD-RP2.5EA
1.00
1.00
1.00
0.998
0.998
0.998
0.995
0.995
0.995
0.993
0.993
0.993
0.990
0.990
0.990
0.988
0.988
0.988
0.985
0.985
0.985
0.983
0.983
0.983
0.980
0.980
0.980
0.978
0.978
1.00
0.998
0.995
0.993
0.990
0.988
0.985
0.983
0.980
0.978
1.00
0.998
0.995
0.993
0.990
0.988
0.985
0.983
0.980
0.978
0.978
1.00
0.998
0.995
0.993
0.990
0.988
0.985
0.983
1.00
0.998
0.995
0.993
0.990
0.988
0.985
0.983
PEAD-RP
·
EA / PUH-P
·
VGAA.UK
PU-P
·
VGAA.UK
PUH-P
·
VGAA
1
.UK
PU-P
·
VGAA
1
.UK
PUH-P
·
YGAA.UK
PU-P
·
YGAA.UK
PUH-P
·
YGAA
1
.UK
PU-P
·
YGAA
1
.UK
OUTDOOR W.B.(
°
C)
TOTAL INPUT (RATIO)
CAPACITY (RATIO)
INDOOR D.B.(
°
C)
INDOOR D.B.(
°
C)
15
15
25
25
20
20
0.4
1.4
1.4
Correcting the capacity line influenced by frosting
Not correcting the capacity line influenced by frosting
1.2
1.0
0.8
0.6
0.4
1.2
1.0
0.8
0.6
15
10
5
0
-5
-10
-12
OUTDOOR W.B.(
°
C)
TOTAL INPUT (RATIO)
C
APACITY (RATIO)
INDOOR D.B.(
°
C)
INDOOR D.B.(
°
C)
15
15
25
25
20
20
0.4
1.4
1.4
Correcting the capacity line influenced by frosting
In some cases, heating operation
cannot be conducted with the maximum
frequency in the area below the slanting line.
In some cases, heating operation
cannot be conducted with the maximum
frequency in the area below the slanting line.
Not correcting the capacity line influenced by frosting
1.2
1.0
0.8
0.6
0.4
1.2
1.0
0.8
0.6
15
10
5
0
-5
-10
-12