8. Specifications
Notes: Refer to the product nameplate attached to the unit for the electrical specifications.
Rating conditions (cooling) Indoor: 27 °C DB, 19 °C WB
Outdoor: 35 °C DB
Rating conditions (heating) Indoor: 20 °C DB
Outdoor: 7 °C DB, 6 °C WB
7. Installation and transferring works, and checking
Regarding place for installation
Consult with your dealer for details on installation and transferring the installation.
Caution:
Never install the air conditioner where there is a risk of leakage of flammable
gas.
If gas leaks and accumulates around the unit, fire can result.
Never install the air conditioner at the following place:
•
where there is much machine oil
•
near ocean and beach areas where there is much salt
•
where humidity is high
•
where there are hot springs nearby
•
where there is much sulfureted gas
•
where there is a high-frequency processing machinery (a high-frequency welder,
etc.)
•
where acid solution is frequently used
•
where special sprays are frequently used
•
Install the indoor unit horizontally. Otherwise, water leakage can result.
•
Take sufficient measures against noise when installing the air conditioners at
hospitals or communication-related businesses.
If the air conditioner is used in any of the above-mentioned environments, frequent
operational failure can be expected. It is advisable to avoid these types of installa-
tion sites.
For further details, consult with your dealer.
Regarding electrical work
Caution:
•
The electrical work must be undertaken by a person who is qualified as
an electric engineer according to local regulations and the instruction
given in the installation manual with the absolute use of exclusive cir-
cuits. The use of other products with the power source can result in burnt-
out beakers and fuses.
•
Never connect the grounding wire to a gas pipe, water pipe, arrester, or
telephone grounding wire. For details, consult with your dealer.
•
In some types of installation sites, the installation of an earth leakage
breaker is mandatory. For details, consult with your dealer.
Regarding transfer of installation
•
When removing and reinstalling the air conditioner when you enlarge your
home, remodel, or move, consult with your dealer in advance to ascertain the
cost of the professional engineering work required for transferring the installa-
tion.
Caution:
When moving or reinstalling the air conditioner, consult with your dealer.
Defective installation can result in electric shock, fire, etc.
Regarding noise
•
In installing work, choose a place that can fully bear the weight of the air con-
ditioner, and where noise and vibration can be reduced.
•
Choose a place where cool or warm air and noise from the outdoor air outlet of
the air conditioner do not inconvenience the neighbours.
•
If any alien object is placed near the outdoor air outlet of the air conditioner,
decreased performance and increased noise can result. Avoid placing any
obstacles adjacent to the air outlet.
•
If the air conditioner produces any abnormal sound, consult with your dealer.
Maintenance and inspection
•
If the air conditioner is used throughout several seasons, the insides can get
dirty, reducing the performance.
Depending upon the conditions of usage, foul odors can be generated and
drainage can deteriorate due to dust and dirt, etc.
Ceiling concealed type (Refrigerant R22)
Cooling capacity
Gross
kW
Net
kW
Net
kW
Voltage
V
Frequency
Hz
Height
mm
Width
mm
Depth
mm
12.1
11.2
—
PE-5GAK
3000/2400
46/42 (-SP: 48/45)
15.7
14.8
—
PE-6GAK
3300/2640
21.6
20.6
—
PE-8GAK
3900/3120
1400
26.7
25.6 (-SP: 25.5)
—
PE-10GAK
4800/3840
50/46 (-SP: 52/49)
1600
30.8
29.6
—
PE-12GAK
5400/4320
51/48
400
1600
634
43.2
41.7
—
PE-16GAK
7200
52
53.4
50.6
—
PE-20GAK
9600
53
Indoor
unit
Model name
Power supply
External static pressure
Pa
Airflow rate (Hi/Lo)
m
3
/h
Noise level (Hi/Lo)
dB(A)
Outdoor model
Net weight
kg
56
PU-5YAKD
PU-5YJSA
59
PU-6YAKD
PU-6YJSA
70
PU-8YAKD
77
PU-10YAKD
77
PU-12YAKD
130
PU-8YAKD
×
2
133
PU-10YAKD
×
2
~ 220, 230, 240
3N ~ 380, 400, 415
50
100 (-SP: 150)
150
49/45 (-SP: 51/48)
400
595
1947
764
634
1180
Heating capacity
100
12.1
11.2
15.5
PEH-5GAK
3000/2400
46/42 (-SP: 48/45)
15.7
14.8
18.5
PEH-6GAK
3300/2640
49/45 (-SP: 51/48)
100 (-SP: 150)
400
1180
634
~ 220, 230, 240
56
PUH-5YKSA
59
PUH-6YKSA