35
10-7. TEST POINT DIAGRAM
Indoor controller board
PCA-RP35KAQ PCA-RP50KAQ
PCA-RP60KAQ PCA-RP71KAQ
PCA-RP100KAQ PCA-RP125KAQ
PCA-RP140KAQ
PCA-RP50KAQR1 PCA-RP60KAQR1
PCA-RP71KAQR1
CN3C
Transmission
(Indoor/outdoor)
(0~24V DC)
SW2
Capacity setting
SW1
Model selection
CN2L
Connector (LOSSNAY)
CN41
Connector (HA terminal-A)
CN90
CN105
Connect to the wireless remote
controller board (CNB)
CN20
Room temperature
thermistor (TH1)
CN22
Connect to the terminal
block (TB5)
(Remote controller con-
necting wire)
(10.4~14.6V DC)
LED2
Power supply (R.B)
LED1
Power supply (I.B)
LED3
Transmission
(Indoor/outdoor)
CNP
Drain-pump output (DP)
(220-240V AC) (option)
CN01
Connect to the Terminal Block
(TB4)
(Indoor/outdoor connecting line)
Between
and
220-240V AC
CNV
Vane motor output (MV)
12V pulse output
SWE
Emergency operation
Jumper wire J41,J42
Pair No. setting for wireless
remote controller
FUSE
6.3A /250V
CNMF
Fan motor
-
: DC 310~340V
-
: DC15V
-
: DC0~6.5V
-
: Stop Dc0 or 15V
Operation DC7.5V
(0~15V pulse)
V
SP
: Voltage between pins of
C626
DC0V (FAN stop)
DC1~6.5V (FAN operation)
(Same as
(+)–
(-) of CNMF)
V
FG
: Voltage between
PC6722 and C955(-)
(Same as
(+)–
(-) of CNMF)
V
CC
: Voltage between pins of
C955 15VDC
(Same as
(+)–
(-) of CNMF)
CN44
Pipe temperature
thermistor
-
: Liquid (TH2)
-
: Cond./Eva. (TH5)
CN4F
Drain float switch (FS)
(option)
CN51
Centrally control
-
: Control signal
13VDC pulse input (
: +)
-
: Operation indicator
13VDC (
: +)
-
: Malfunction indicator
13VDC (
: +)
OCH491B