11
2) For wireless remote controller (Fig. 6-10)
Changing the power voltage setting
• Be sure to change the power voltage setting depending on the voltage used.
1
Going to the function select mode
Press
the
CHECK
button
F
twice continuously.
(Start this operation from the status of remote controller display turned off.)
CHECK
is lighted and “00” blinks.
Press
the temp button
C
once to set “50”. Direct the wireless remote control-
ler toward the receiver of the indoor unit and press the
h
button
A
.
2
Setting the unit number
Press
the
temp buttons
C
and
D
to set the unit number “00”. Direct the
wireless remote controller toward the receiver of the indoor unit and press the
min
button
B
.
3
Selecting a mode
Enter 04 to change the power voltage setting using the
temp buttons
C
and
D
. Direct the wireless remote controller toward the receiver of the indoor
unit and press the
h
button
A
.
Current setting number:
1 = 1 beep (1 second)
2 = 2 beeps (1 second each)
3 = 3 beeps (1 second each)
4
Selecting the setting number
Use the
temp buttons
C
and
D
to change the power voltage setting to
01 (240 V). Direct the wireless remote controller toward the sensor of the indoor
unit and press the
h
button
A
.
5
To select multiple functions continuously
Repeat
steps
3
and
4
to change multiple function settings continuously.
6
Complete function selection
Direct the wireless remote controller toward the sensor of the indoor unit and
press the
button
E
.
Note: Whenever changes are made to the function settings after installation
or maintenance, be sure to record the changes with a mark in the “Setting”
column of the Function table.
6.3.2. Function setting on the remote controller
Refer to the indoor unit operation manual.
6. Electrical work
Function table
Select unit number 00
Mode
Settings
Mode no.
Setting no. Initial setting
setting
Power failure automatic recovery
Not available
01
1
Available
w
2
Ο
Indoor temperature detecting
Indoor unit operating average
02
1
Ο
Set by indoor unit’s remote controller
2
Remote controller’s internal sensor
3
LOSSNAY connectivity
Not Supported
03
1
Ο
Supported (indoor unit is not equipped with outdoor-air intake)
2
Supported (indoor unit is equipped with outdoor-air intake)
3
Power voltage
240 V
04
1
220 V, 230 V
2
Ο
CHECK
CHECK
ON/OFF
TEMP
FAN
VANE
TEST RUN
AUTO STOP
AUTO START
h
min
LOUVER
MODE
CHECK
RESET
SET
CLOCK
CHECK
CHECK
CHECK
Fig. 6-10
Select unit numbers 01 to 03 or all units (AL [wired remote controller]/07 [wireless remote controller])
Mode
Settings
Mode no.
Setting no. Initial setting
setting
Filter sign
100Hr
07
1
2500Hr
2
Ο
No
fi
lter sign indicator
3
Fan speed
Silent
08
1
Standard
2
Ο
High ceiling
3
Up/down vane setting
No vanes
11
1
Equipped with vanes (vanes angle setup
1
)
2
Ο
Equipped with vanes (vanes angle setup
2
)
3
w
When the power supply returns, the air conditioner will start 3 minutes later.