Mitsubishi Electric PAR-W21MAA Installation Manual Download Page 5

5

 6

Initial Setting

 * The available settings differ depending on the model of the unit to connect.

F

I
J
K

D

E

1. Water temperature initial setting

Water Temp Heating

1

Water temperature display

2. Water temperature initial setting

Water Temp Heating ECO No.1

2

Water 
temperature
display

3

Outside air 
temperature 
display

3. Water temperature initial setting

Water Temp Heating ECO No.2

4

Water 
temperature
display

5

Outside air 
temperature 
display

4. Water temperature initial setting

Water Temp Hot Water

6

Water temperature display

5. Water temperature initial setting

Water Temp Anti-freeze

7

Water temperature display

7. Water temperature initial setting

Temp Offset Heating

9

Offset amount display

6. Water temperature initial setting

Water Temp Cooling

8

Water temperature display

8. Water temperature initial setting

Temp Offset Cooling

0

Offset amount display

Outside air 
temperature 
setting of Heating 
ECO No.2 must be 
higher than that of 
Heating ECO No.1.

Outside air 
temperature 
setting of Heating 
ECO No.2 must be 
higher than that of 
Heating ECO No.1.

(

)

(

)

(1) Water temperature initial setting mode

1

Stop the unit by pressing the [

ON/OFF] 

I

 button. 

2

To enter the water temperature initial setting, press and hold down the [INITIAL 
SETTING (

)] 

J

 button for three seconds or longer. (Any of 1. to 8. will be displayed.)

*

Wait a while because the water temperature initial setting takes approximately 30 
seconds to display after the [INITIAL SETTING (

)] 

J

 button is pressed. 

*

Depending on the model of the unit to connect, the water temperature initial setting may 
not be possible. In such case, the screen transitions to the unit stop screen after the 
display of the error. 

3

To select a water temperature initial setting from 1. to 8., press the [Mode (Back)] 

E

 

button.

The initial operation mode can be set. Change the setting when needed.

(3) Timer function setting

To switch the setting, press the [

ON/OFF] button (Choose one of 

the followings.).

1

WEEKLY TIMER (Initial setting value):

The weekly timer can be used.

2

AUTO OFF TIMER

: The auto off timer can be used.

3

SIMPLE TIMER

: The simple timer can be used.

4

TIMER MODE OFF

: The timer mode cannot be used.

* When the use of clock setting is OFF, the “WEEKLY TIMER” cannot be 

used.

(4) Contact number setting for error situation

To switch the setting, press the [

ON/OFF] button.

1

CALL OFF

: The set contact numbers are not displayed in 

case of error.

2

CALL **** *** ****

: The set contact numbers are displayed in case 

of error.

 

CALL_

: The contact number can be set when the 

display is as shown on the left.

Setting the contact numbers

To set the contact numbers, follow the following procedures.
Move the flashing cursor to set numbers. Press the [

TEMP. (

) or 

(

)] button to move the cursor to the right (left). Press the [

CLOCK 

(

) or (

)] button to set the numbers.

(5) Temp off set setting

To switch the following settings, press the [

ON/OFF] button.

1

 ON

: The setback amount setting is displayed under the water 

temperature initial setting mode.

2

 OFF : The setback amount setting is not displayed under the water 

temperature initial setting mode.

 

[4] -4. Display change setting

(1) Temperature display °C/°F setting

To switch the setting, press the [

ON/OFF] button.

1

 °C:

The temperature unit °C is used.

2

 °F:

The temperature unit °F is used.

(2) Water temperature display setting

To switch the setting, press the [

ON/OFF] button.

1

 ON

: The water temperature is displayed.

2

 OFF : The water temperature is not displayed.

Summary of Contents for PAR-W21MAA

Page 1: ...ed by installation may result in an electric shock or fire All electrical work must be performed by a licensed technician according to local regulations and the instructions given in this manual Any lack of electric circuit or any deficiency caused by installation may result in an electric shock or fire Do not move and re install the PAR W21MAA yourself Any deficiency caused by installation may re...

Page 2: ...hing Wiring pipe Lock nut Switch box Seal around here with putty Remote control cord When installing directly on the wall When opening a hole using a drill for the remote controller cord or when taking the cord out of the back of the remote controller seal the hole with putty When routing the cord via the portion cut off from the upper cover similarly seal that portion with putty When taking the r...

Page 3: ...operation section Peel off this protection sheet before use Item 1 Item 2 Item 3 Setting content 1 Change Language CHANGE LANGUAGE Language setting to display Display in multiple languages is possible 2 Function limit FUNCTION SELECTION 1 Operation function limit setting operation lock LOCKING FUNCTION Setting the range of operation limit operation lock 2 Operation mode skip setting SELECT MODE Se...

Page 4: ...splay Press the D button Press the D button Press the D button Press the G button Mode selection MODE SELECTION Press the E button Press the E button Press the G button Press the G button See 4 2 1 See 4 2 2 See 4 2 3 See 4 3 1 See 4 3 2 See 4 3 3 See 4 3 4 See 4 3 5 See 4 4 1 See 4 4 2 Operation function limit setting LOCKING FUNCTION Temperature range limit setting LIMIT TEMP FUNCTION Operation ...

Page 5: ...e the screen transitions to the unit stop screen after the display of the error 3 To select a water temperature initial setting from 1 to 8 press the Mode Back E button The initial operation mode can be set Change the setting when needed 3 Timer function setting To switch the setting press the ON OFF button Choose one of the followings 1 WEEKLY TIMER Initial setting value The weekly timer can be u...

Page 6: ...F 87 F 1 Outside air temperature 20 C 40 C 4 F 104 F Temp Offset Heating Cooling 15 C 15 C 5 F 59 F A Heating system Lower limit value setting Defines the 4 mA 0 V input as the water temperature 1 C of the Heating Hot Water and Anti freeze modes Upper limit value setting Defines the 20 mA 10 V input as the water temperature 2 C of the Heating Hot Water and Anti freeze modes B Cooling system Lower ...

Page 7: ...he self check mode When the CHECK H button is pressed twice successively within three seconds the display shown below appears 2 Set the address or refrigerant address No you want to self check When the TEMP or F buttons are pressed the address decreases and increases between 001 and 127 or 00 and 15 Set it to the address No or refrigerant address No you want to self check Approximately three secon...

Page 8: ...ntroller ERROR CODE Error code 2 E3 6833 6832 flash o Cannot send Error display 3 ERC and data error count are displayed o Data error generation 3 Remote controller check result There is noise on the transmission line or the unit or another remote controller is faulty Check the transmission line and the other remote controllers Data error count is the difference between the number of bits of remot...

Reviews: