background image

Test Run

6

Measure an impedance between the power supply terminal block on the outdoor unit

and the ground with a 500V Megger and check that it is equal to or greater than 1.0 M

"

.

    

     

1

 Turn on the main power to the unit.

     

2

 Press the         button twice continuously.

         (Start this operation from the status of remote controller display turned off.)

         

A

 

 

TEST RUN

 and current operation mode are displayed.

     

3

 Press the         (               ) button to activate COOL    mode, then check whether

         cool air is blown out from the unit.

     

4

 Press the         (               ) button to activate HEAT    mode, then check whether

         warm air is blown out from the unit. (only H/P model)
     

5

 Press the         button and check whether strong air is blown out from the unit.

     

6

 Press the         button and check whether the auto vane operates properly.

     

7

 Press the ON/OFF button to stop the test run.

TEST RUN

MODE

MODE

FAN

VANE

NOTE : • Point the remote controller towards the indoor unit receiver 

               while following steps 

2

 to 

7

.

             • It is not possible to run in FAN, DRY or AUTO mode. 

Function Selection

7

This setting is available only for Mr. Slim model. CITY MULTI model can be set by dip switch of indoor/outdoor

control circuit board. Refer to technical data of CITY MULTI model to set dip switch.

Each function can be set according to necessity using the remote controller.

The setting of function for each unit can only be done by the remote controller.

Select function available from the Table3. Function selection using wireless remote controller 

is available only for refrigerant system with wireless function. Refrigerant address cannot 

be specified by the wireless remote controller.

The article below describes how to set “LOSSNAY connectivity” into “supported

(indoor unit is not equipped with outdoor-air intake)” in Table 3 as an example.

           

1

 Go to the function select mode

               Press the          button 

F

 twice continuously. 

               (Start this operation from the status of remote controller display turned off.)

               

CHECK  

is lighted and “00” blinks.

               Press the temp      button 

C

 once to set “50”. Direct the wireless remote 

               controller toward the receiver of the indoor unit and press the         button 

A

.  

           

2

 Setting the unit number            

               Press the temp          button 

C

 and 

D

 to set the unit number “00”. Direct 

               the wireless remote controller toward the receiver of the indoor unit and 

               press the         button 

B

           

3

 Selecting a mode

               Enter “03” to change the LOSSNAY connectivity setting using the      

C

 and

                    

D

 buttons. Direct the wireless remote controller toward the receiver 

               of the indoor unit and press the          button 

A

.

               Current setting number:                         1=1 beep (1 second)

                                                                              2=2 beeps (1 second each)

                                                                              3=3 beeps (1 second each)

          

W

 If a mode number that can not be recognized by the unit is entered, 

             3 beeps (3 beeps of 0.4 seconds duration) will be heard. 

             Reenter the mode number selecting.

          

W

 If the signal was not received by the sensor or an error occurred during 

             transmission, you will not hear a beep or a “double beep” may be heard.

             Press the          button again.

           

4

 Selecting the setting number

               Use the      

C

 and      

D

 buttons to change the LOSSNAY connectivity setting

               to “02”. Direct the wireless remote controller toward the sensor of the indoor

               unit and press the          button 

A

.

              → At this time, current setting number for selected mode number will be output

                  by the interrupted buzzer sounds and the blinks of operation indicator.

               Output : setting number = 1 → beep beep (0.4 0.4 second) ×1

                                                         2 → beep beep (0.4 0.4 second) ×2

                                                         3 → beep beep (0.4 0.4 second) ×3

          

W

 If a setting number that can not be recognized by the unit is entered, 3 beeps

             (3 beeps of 0.4 seconds duration) will be heard (unit will beep only).

             Reenter the setting number selecting.

          

W

 If the signal was not received by the sensor or an error occurred during

             transmission, you will not hear a beep or a “double beep” may be heard.

             Press the          button again.

          

W

 If the number that can not be set is input, the former setting number will be set.

            

5

 To select multiple functions continuously

                Repeat steps 

3

 and 

4

 to change multiple function settings continuously.

            

6

 Complete function selection

                Direct the wireless remote controller toward the sensor of the indoor unit

                and press the 

   

 button 

E

.

 

CHECK

h

min

h

h

h

h

NOTE : Whenever changes are made to the function settings after construction or maintenance, be sure to record the 

              added functions with an “

”, in the “Check” column provided on the chart.

CHECK

CHECK

CHECK

CHECK

1

2

3

4

Other function selections

Now that you know how to change LOSSANY connectivity setting, there are several other settings that can be changed as well.

The following table lists the various settings that can be changed through the remote controller and the default settings.

 

Function

Settings

Not available

Available

Indoor unit operating average

Set by indoor unit’s remote controller

Remote controller’s internal sensor

Not supported

Supported (indoor unit is not equipped with outdoor-air intake)

Not supported (indoor unit is not equipped with outdoor-air intake)

100Hr

2500Hr

No filter sign indicator

Quiet

Standard

High ceiling

No vanes

Equipped with vanes (No.1 set)

Equipped with vanes (No.2 set)

○○

*1



PCA-RP·KA


PC-KAK

Power failure 

automatic recovery

Indoor temperature 

detecting

LOSSNAY connectivity

Filter sign

Fan speed (only for PCA)

Up/down vane setting

*1 It is possible to set it only while connecting wired remote control.

 Things to remember when entering function selections:

 The basic procedure for entering function selections is the same as described for switching between LOSSNAY connectivity.

 However, there are some differences at step 

2

 for selecting the unit number, step 

3

 for selecting the mode number and 

 step 

4

 for selecting the setting number.

 The following Tables 4 and 5 list the various function settings, mode numbers and setting numbers.

 Table 4 details the function of the entire refrigerant system while Table 5 shows the function that can be set for the indoor unit. 

Table 4. Itemized functions of the entire refrigerant system (select unit number 00)

Mode

Settings

Not available

Available (Approximately 4-minutes wait-period after power

is restored.)

Indoor unit operating average

Set by indoor unit’s remote controller

Remote controller’s internal sensor

Not supported

Supported (indoor unit is not equipped with outdoor-air intake)

Not supported (indoor unit is not equipped with outdoor-air intake)

01

02

03

Mode No.

Power failure 

automatic recovery

Indoor temperature 

detecting

LOSSNAY 

connectivity

Setting No. Check

Remarks

1
2
1

2

3

1

2

3

Approximately 4-minutes wait-

period after power is restored.

Table 5. Itemized functions of the indoor unit (select unit numbers 01 to 04 or 07)

Mode

Settings

100Hr

2500Hr

No filter sign indicator

Quiet

standard

High ceiling

No vanes

Equipped with vanes (No.1 set)

Equipped with vanes (No.2 set)

07

08

11

Mode No.

Filter sign

Fan speed

(only for PCA)

Up/down vane 

setting

Setting No. Check

Remarks

1

2

3

1

2

3

1

2

3

2

 Setting the unit numbers

Set “00” as the unit number when setting function from Table 4.

When setting function from Table 5.

- When setting function for an indoor unit in an independent system, set the unit number to 01.

- When setting function for a simultaneous-Twin Triple quadruple indoor unit system, assign unit numbers from 01 to 04 to

  each indoor unit.

- When setting the same functions for an entire simultaneous Twin Triple quadruple-indoor unit system, assign “07” as 

  the unit number.

3

 Selecting the mode number

    Select from Table 4 and Table 5.

4

 Selecting the setting number.

Self-Check

8

1

 Turn on the main power to the unit.

2

 Press the          button twice continuously.

    (Start this operation from the status of remote controller display turned off.)
    

A

 

 

CHECK   

begins to light. 

    

B

 “00” begins to blink.

3

 While pointing the remote controller toward the unit’s receiver, press

    the         button. The check code will be indicated by the number of 
    

times that the buzzer sounds from the receiver section and the number

    of blinks of the operation lamp.

4

 Press the ON/OFF button to stop the self-check.

CHECK

h

[Output pattern A]  Errors detected by indoor unit

[Output pattern B]  Errors detected by unit other than indoor unit (outdoor unit, etc.)

E9

*1 

If the beeper does not sound again after the initial 

2 beeps to confirm the self-check start signal was received and 

the OPERATION INDICATOR lamp does not come on, 

there are no error records.

*2

If the beeper sounds 3 times continuously “beep, beep, beep (0.4 + 0.4 + 0.4 sec.)” after the initial 2 beeps to confirm 

the self-check start signal was received, the specified refrigerant address is incorrect.

OPERATION

INDICA

TOR

lamp blink

pattern

Beep

Beep Beep Beep

Beep

Beep

Beep

Off

Approx. 2.5 sec.

On

Approx. 3 sec.

On

0.5 sec.

On

0.5 sec.

On

0.5 sec.

On

0.5 sec.

Off

Approx. 2.5 sec.

On

Approx. 3 sec.

On

0.5 sec.

On

0.5 sec.

· · ·

 Repeated

Number of blinks/beeps in pattern indicates the check

code in the following table (i.e., n=5 for “U2”)

Number of blinks/beeps in pattern indicates

the check code in the following table

n

th

1

st

2

nd

3

rd

1

st

2

nd

Self-check

starts

(Start signal

received)

Beeper sounds

[Output pattern B]

OPERATION

INDICA

TOR

lamp blink

pattern

Beep

Beep Beep Beep

Beep

Beep Beep

Off

Approx. 2.5 sec.

On

0.5 sec.

On

0.5 sec.

On

0.5 sec.

On

0.5 sec.

Off

Approx. 2.5 sec.

On

0.5 sec.

On

0.5 sec.

· · ·

 Repeated

Number of blinks/beeps in pattern indicates the check

code in the following table (i.e., n=5 for “P5”)

Number of blinks/beeps in pattern indicates

the check code in the following table

n

th

1

st

2

nd

3

rd

1

st

2

nd

Self-check

starts

(Start signal

received)

Beeper sounds

 Refer to the following tables for details on the check codes.

[Output pattern A]

Beeper sounds/OPERATION

INDICATOR lamp blinks

 Check code

Symptom

Remarks

(Number of times)

Wireless remote controller Wired remote 

controller

Beeper sounds/OPERATION

INDICATOR lamp blinks

 Check code

(Number of times)

Wireless remote controller

1

2

3

4

5

6

7

8

9

10

11

12

No sound

No sound

No sound

P1

Intake sensor error

P2, P9

Pipe (Liquid or 2-phase pipe) sensor error

E6,E7

Indoor/outdoor unit communication error

P4

Drain sensor error/Float switch connector open

P5

Drain pump error

P6

Freezing/Overheating safeguard operation

EE

Communication error between indoor and outdoor units

P8

Pipe temperature error

E4

Remote controller signal receiving error

Symptom

Remarks

1
2

3

4
5

6

7

8

9

10
11
12

13

14

Indoor/outdoor unit communication error 

(Transmitting error) (Outdoor unit)

Open/short of outdoor unit thermistors

Compressor overcurrent interruption (When compressor locked)

Abnormal high discharging temperature/

insufficient refrigerant

Abnormal high pressure (63H worked)/Overheating 

protection operation

Abnormal temperature of heat sink

– (Outdoor unit error)

Compressor overcurrent interruption/Abnormal of power module

Abnormality of super heat due to low discharge temperature

Abnormality such as overvoltage or voltage shortage and 

abnormal synchronous signal to main circuit/Current sensor error

U2

U5

UP

U3,U4

UF

U1,Ud

U8

U6

U7

U9,UH

Others

Other errors (Refer to the technical manual for the outdoor unit.)

For details, check

the LED display 

of the outdoor 

controller board.

Fb

E0, E3

E1, E2

– – – –

Indoor unit control system error (memory error, etc.)

Compressor overcurrent interruption

• On wireless remote controller

  The continuous buzzer sounds from receiving section of indoor unit.

  Blink of operation lamp

• On wired remote controller

  Check code display in the LCD.

Wired remote 

controller

ON/OFF

  TEMP

FAN

VANE

TEST RUN

AUTO STOP

AUTO START

h

min

LOUVER

MODE

CHECK

RESET

SET

CLOCK

NOT AVAILABLE

SWING

TEST

RUN

3

 

4

6

5

7

2

A

ON/OFF

  TEMP

FAN

VANE

TEST RUN

AUTO STOP

AUTO START

h

min

LOUVER

MODE

CHECK

RESET

SET

CLOCK

CHECK

F

E

B

A

CD

ON/OFF

  TEMP

FAN

VANE

TEST RUN

AUTO STOP

AUTO START

h

min

LOUVER

MODE

CHECK

RESET

SET

CLOCK

CHECK

2

 

4

3

 

A

 

B

Table 3.

Remote controller transmission error

Remote controller control board error

No corresponding

RG79V995H03

1

 Output pattern (Mr.Slim model / CITY MULTI model)

2

 Check code (Mr.Slim model)

3

 Check code (CITY MULTI model)

Beeper sounds/OPERATION

INDICATOR lamp blinks

 Check code

Remarks

(Number of times)

Wireless remote controller

Wired remote 

controller

1

2

3

4

5

6

7

8

9

1000 ~ 1999

2000 ~ 2999

3000 ~ 3999

4000 ~ 4999

5000 ~ 5999

6000 ~ 6999

7000 ~ 7999

0000 ~ 0999

8000 over

[Output pattern A]  Errors detected by indoor unit or LOSSNAY unit

[Output pattern B]  Errors detected by unit other than indoor unit (outdoor unit, etc.)

*2 

If the beeper does not sound again after the initial 

2 beeps to confirm the self-check start signal was received and 

the OPERATION INDICATOR lamp does not come on, 

there are no error records.

*3

If the beeper sounds 3 times continuously “beep, beep, beep (0.4 + 0.4 + 0.4 sec.)” after the initial 2 beeps to confirm 

the self-check start signal was received, the specified address is incorrect.

• On wireless remote controller

  The continuous buzzer sounds from receiving section of indoor unit.

  Blink of operation lamp

• On wired remote controller

  Check code display in the LCD.

*1 Refer to service handbook of outdoor unit for the detail. 

HEAD OFFICE:

 

TOKYO BUILDING, 2-7-3, MARUNOUCHI, CHIYODA-KU,

 T

OKYO 100-8310, JA

PAN

Reviews: