When using the external input and output functions, use the external input and output cables provided with the remote controller.
(5 wire cable for input and 4 wire cable for output are provided.)
1. External signal input function
(1) External Input
Emergency stop/Normal, ON/OFF and Prohibit/Permit local remote controller operation control can be applied to all units
being controlled by inputting the no-voltage contact signal from an external source.
(2) Level signal and pulse signal
(3) External input specification
(4) Example of a recommended circuit
•
The relays and extension cables, etc. must be prepared separately at the site.
•
Use a no-voltage contact and minute load relay (minimum application load 5VDC-1mA).
•
The length of the connection cable extension should not exceed 10m. (Use a cable of 0.3mm
2
or thicker.)
•
Cut of the cable not being used close the connector and properly insulate the cut off ends with tape or the like.
4 Using the External Input and Output
No.
1
2
3
4
Do not use external input
Change between Emergency stop/Normal.
Set ON/OFF
Set ON/OFF and Prohibit/Permit.
Input state
—
ON/OFF remote
controller
SW4
2
Schedule timer
SW3
2
3
3
OFF
OFF
OFF
OFF
Level input
Level input
Pulse input
(0.5sec or more)
OFF
ON
ON
ON
OFF
ON
System remote
controller
SW3
2
3
OFF
OFF
OFF
ON
ON
ON
OFF
ON
OFF
ON
ON
ON
OFF
ON
External input signal functions
All units will stop with the external input,and all operations of this unit,other system controllers and
local remote controller will be prohibited.
All units will turn ON/OFF according to the input state. ON/OFF operations using this unit and the
local remote controller will be prohibited when using this function.
All units are started or stopped, or all local remote controller operations are prohibited according to
the input state. When prohibit is input, the local remote controller’s ON/OFF, operation mode, set
temperature and filter reset operations will be prohibited. Operation with this system will be enabled.
NOTE :
For System remote controller and Schedule timer
* If the SW3-4 "operation prohibit setting changeover" is set to "OFF (disable)", use is possible only for emergency stop.
* If the SW3-5 "operation prohibit range setting changeover" is set to "ON (including system controller), operations of the local remote
controller and other system controllers will be prohibited by the prohibit input. If set to "OFF (only local remote controller)", operation
of only the local remote controller will be prohibited. (When the level "emergency stop" or "ON/OFF" is input, operation of the other
system controllers will also be prohibited regardless of the switch setting.)
For ON/OFF remote controller
* All units are stopped when emergency stop is input, and ON/OFF operations of this unit, other system controllers and local remote
controller will be prohibited.
* Only ON/OFF of the local remote controller will be prohibited with the prohibit input.
Contact ON
Contact OFF
Contact ON
Contact OFF
Contact ON
Contact OFF
Contact ON
Contact OFF
OFF
OFF
ON
Normal
Normal
Emergency
STOP
OFF
OFF
ON
(A) Level signal
(B) Pulse signal
0.5sec or more
0.5sec or more
(Example) Case of ON/OFF signal
Signal 1 (ON)
Signal 2 (OFF)
* The same applies to Prohibit/Permit.
!!
"# $
#
%
&'
&'
('
(
!!
)
CN2
No. 1
No. 2
No. 3
No. 4
No. 5
Lead wires (5 wires)
Green
Yellow
Orange
Red
Brown
Level signal for Emergency stop/Normal
Emergency stop/Normal input
Not used
Not used
Not used
Common 0V
Level signal for ON/OFF
ON/OFF input
Not used
Not used
Not used
Pulse signal for ON/OFF, Prohibit/Permit
On input
Off input
Prohibit local remote controller operation input
Permit local remote controller operation input
For level signal
Contact operation
OFF ON
Operation state
Emergency stop/Normal
Normal Emergency stop
Emergency stop Normal
ON OFF
External input
For pulse signal
* Operation will continue even if a ON signal is input during operation. (This also applies to OFF, prohibit and enable).
* If the local remote controller is prohibited, ON/OFF, operation mode, temperature and filter reset operations using the local
remote controller will be prohibited. (Only ON/OFF are prohibited for the ON/OFF remote controller.)
* Set the pulse duration (contact ON time) to 0.5sec or more.
ON/OFF
OFF ON
ON OFF
NOTE :