Mitsubishi Electric PAC-YG63MCA Instruction Manual Download Page 5

4

6-2. Installation Procedure

The AI controller PAC-YG63MCA does not have a waterproof structure.

Be sure to install the AI controller inside a control panel that is located indoors. 
Prepare a control panel capable of storing this device such as the one shown in the figure. (Install the device in a control 
panel strong enough to withstand a weight of 0.6 kg [1

3

/

8

 lb].)

This device can be installed flat or vertically. Clear the space shown below when installing.

(1) Fix the top of this unit to the control panel at two points by loosely tightening the screws (M4) that were procured locally. 

Fix the bottom in place with two screws and then tighten all four of the screws.

(2) To remove the cover, as shown in the figure, remove the two screws for fixing the cover in place and then remove the cover by 

unhooking the upper hook section from the lower case. To attach the cover, hook the upper hook section on the lower case and then 
fix the cover in place with the two screws that were removed.

Note:  The space shown above does not include space for peripherals. Additionally, the amount of space necessary varies according to 

the functions that are used and the wiring method. Secure enough space appropriate for the type of installation. 

Note:  Two hooks are located on the upper section of the cover.

 

100

(

3

15

/

16

)

100

(

3

15

/

16

)

100

(

3

15

/

16

)

100

(

3

15

/

16

)

Size of the device: 200 (W) × 120 (H) × 45 (D) mm/

7

7

/

8

 (W) × 4

3

/

4

 (H) × 1

25

/

32

 (D) in

Unit: mm (in)

 

110 

(

4

11

/

32

)

150 

(

5

29

/

32

)

 

Screw pitch

Unit: mm (in)

Hooks

Screws for fixing 

the cover

Summary of Contents for PAC-YG63MCA

Page 1: ...2 4 Specifications 2 4 1 Product Specifications 2 4 2 External View 2 5 Example of System Configuration 3 6 Installation Method 3 6 1 Parts to be Procured Locally 3 6 2 Installation Procedure 4 7 Wiring Method 5 7 1 Names of Parts 5 7 2 Connecting the Power Line and M NET Transmission Line 6 7 3 Connecting the Sensors 6 1 Channel 1 Pt100 Input 6 2 Channel 1 Channel 2 Analog Input 7 7 4 Connecting ...

Page 2: ... in an unusual environment If the device is installed where a large amount of oil including machine oil steam or sulfidizing gas is present this environment may lead the device to a remarkable drop in performance or damage its parts Do not install the device where a large amount of steam rises such as in the bathroom or kitchen Avoid installing this device where dew condensation occurs If the devi...

Page 3: ... 4 to 20 mADC Temperature humidity Set by system controller 0 5 FS 0 1 C 0 18 F 3 0 5 FS 0 1 RH at 25 C 77 F Screwless terminal block 2 poles 1 to 5 VDC 2 0 to 10 VDC Output Upper lower limit alarm output non voltage contact Applied load MAX 24 VDC 5 W MIN 5 VDC 2 mW AC loads cannot be connected Screw terminal block M3 5 Interlock Function Interlock M NET devices according to measurement data valu...

Page 4: ...or etc AI controller 24 VDC Power Supply 24 VDC Power Supply 6 Installation Method Required Part Specification Unit fixing screws M4 screw 4 Power supply for this unit Power source 24 VDC 10 0 2 A Minimum loading SELV circuit power line with grounding terminal Ripple noise Lower than 200 mVp p Compatible specification Authorized or CE marked products Subject to regulations IEC60950 or EN60950 CISP...

Page 5: ... all four of the screws 2 To remove the cover as shown in the figure remove the two screws for fixing the cover in place and then remove the cover by unhooking the upper hook section from the lower case To attach the cover hook the upper hook section on the lower case and then fix the cover in place with the two screws that were removed Note The space shown above does not include space for periphe...

Page 6: ...erform wiring so that the terminal block is not strained If strained use a wire guide or junction terminal to alleviate the stress on the terminal block Do not connect the wires directly from the top of the control panel to the terminal block Moisture may enter this device along the wiring and cause electric shock or fire 24 VDC Power source Relay Junction terminal block 7 Wiring Method CN01 CN03 ...

Page 7: ... 24 VDC power supply 1 Varistor 2 Arrester 3 Noise filter 4 Fuse It is important to pay attention to the polarity when connecting to the 24 VDC power supply terminal block Connecting the positive and negative in the reverse order will cause a failure Fix the power line and M NET transmission line in place on the outside to ensure that the terminal block is not affected by any external force Not se...

Page 8: ... circuiting the plates cover lower case or neighboring wires Perform wiring so that the terminal block is not strained If strained use a wire guide or junction terminal to alleviate the stress on the terminal block CN03 Ch1 Ch2 X1 Caution To use X1 relay obtain one that satisfies the following specifications Operating coil Applied load MAX 24 VDC 5 W Built in diode MIN 5 VDC 2 mW Built in diode 1 ...

Page 9: ... Procedure Ch Setting Setting Switch Pt100 To not use Ch1 Pt100 used 1 SW01 1 2 SW01 3 ON ON OFF OFF Ch Setting Setting Switch 4 to 20 mADC 1 to 5 VDC 0 to 10 VDC To not use Ch1 Setting of sensor to use 1 SW11 1 2 SW11 2 3 SW01 1 4 SW01 2 5 SW01 3 ON ON ON OFF OFF OFF ON ON OFF OFF OFF OFF ON ON OFF OFF OFF OFF OFF OFF Ch2 Setting of sensor to use 1 SW12 1 2 SW12 2 3 SW02 1 4 SW02 2 ON ON ON OFF O...

Page 10: ...emperature Measurement range setting Set the upper limit and lower limit values Set a range from 30 C 22 F to 60 C 140 F Measurement correction Input the measurement temperature correction value offset value Ch Setting Setting with G B 50A or TG 2000A Ch1 Measurement category setting Select the temperature humidity Measurement range setting Set the upper limit and lower limit values Measurement co...

Page 11: ... of upper lower limit alarm interlock output use No Yes Specify whether to use channel 2 upper lower limit alarm interlock output 6 Selection of the system to judge upper lower limit alarm interlock output Self judgment System controller Select whether this device itself or the system controller performs the output judgment of the upper lower limit alarm interlock 7 Unused Set to OFF 8 Unused Set ...

Page 12: ...2 Output LEDs Error status 1 1 4 digit error code LED12 13 14 15 Status display LEDs Refer to 10 2 Error Status Display Output Method Ch1 Ch2 LED 03 LED 02 Level Output Alarm output Alarm stop Alarm output Alarm stop LED11 LED12 LED13 LED14 LED15 Function Remark Common Error code display Binary number indication 23 8 22 4 21 2 20 1 STEP1 ErrorStatusDisplay Starting Point Indication LEDs 12 to 15 f...

Page 13: ...surement accuracy of the sensor used results in extreme differences in the measurement values use the measurement correction value offset value input function of the system controller to correct the measurement values 3 When upper lower limit alarm interlock is to be used input a value that exceeds the set alarm level and confirm whether the alarm is displayed on the controller Furthermore confirm...

Page 14: ......

Page 15: ......

Page 16: ... if not installed and used in accordance with the instructions may cause harmful interference to radio communications However there is no guarantee that interference will not occur in a particular installation If this equipment does cause harmful interference to radio or television reception which can be determined by turning the equipment off and on the use is encouraged to try to correct the int...

Reviews: