2-2-2. Space required for Installation and servicing for branch box for PAC-MK53/33BCB
(1) Front View (Fig. 2-6)
A
Branch box
B
On the side of piping
(2) Side View (Fig. 2-7, Fig. 2-8, Fig. 2-9)
C
For indoor installations
D
Ceiling board
E
Maintenance hole
*1:
A minimum 350 mm is required for 90° bends in refrigerant piping.
*2
:
A
is “Min. 200 mm” <recommendation>.
In the case of less than 200 mm (for example
A
is 100 mm), the exchange work of branch box from a maintenance hole
becomes difficult (Only exchange work of a PCB, linear expansion valve coils and sensors is possible).
To install the optional reactor box, set
A
to Min. 270 mm <recommendation> (Fig. 2-9)
*3
:
B
is “600 mm”
.
In the case of “450 mm”, prepare a maintenance hole at a PCB side (as it is shown in Fig. 2-8, Fig. 2-9), and “Min. 300
mm” is needed as distance
A
.
In the case of less than 300 mm (for example
A
is 100 mm), the exchange work of Branch box, linear expansion
valve coils and sensors from a maintenance hole becomes difficult. Only exchange work of a PCB is possible.
(3) Top View (Fig. 2-10)
NOTE 1: The branch box is only for indoor use.
NOTE 2: Please attach the special optional cover (PAC-AK350CVR-E) to install branch box outdoors.