2   Confirming the Supplied Parts

1. Model names and applicable models

PAC-KE05DM-F

PEFY-P200VMHS-E,  PEFY-P250VMHS-E
PEFY-P72NMHSU-E,  PEFY-P96NMHSU-E

Model name

Applicable types

2. Provided parts

Check that the packet includes the following parts in addition to this installation manual.

Float switch

Drain socket

4

BAND (Large)

6

PTT SCREW 4×10

3

BAND (Small)

1

1

1

4

4 + 1 (spare)

1

2

RUBBER PLUG

1

DRAIN PUMP ASSY.

SHAPE

Q'TY

PARTS

SHAPE

Q'TY

PARTS

SHAPE

PARTS

Q'TY

5

INSULATION PIPE

Summary of Contents for PAC-KE05DM-F

Page 1: ... for special applications such as storing food plants precision equipment or art The quality of these items may deteriorate Always provide adequate signal noise protection when installing in facilities such as hospitals and communication stations Equipment at these facilities such as inverters in house generators high frequency medical equipment two way communication equipment may cause the air co...

Page 2: ...FY P96NMHSU E Model name Applicable types 2 Provided parts Check that the packet includes the following parts in addition to this installation manual Float switch Drain socket 4BAND Large 6PTT SCREW 4 10 3BAND Small 1 1 1 4 4 1 spare 1 2RUBBER PLUG 1DRAIN PUMP ASSY SHAPE Q TY PARTS SHAPE Q TY PARTS SHAPE PARTS Q TY 5INSULATION PIPE ...

Page 3: ...ons shown Photo 3 1 and remove the control box cover and the wire cover Fixing screw Fixing screws Control box cover Wire cover Heat exchanger cover Fixing screws Knockout hole Photo 3 1 2 Remove the fixing screws 3 locations shown in Photo 3 2 and remove the heat exchanger cover 3 Open the knockout hole shown in Photo 3 3 using a screwdriver etc Photo 3 2 Photo 3 3 ...

Page 4: ...ose the port To prevent water leakage make sure that the rubber plug is pushed in firmly as far as it will go Drain socket Rubber plug 2 Drain pump assy 1 Inside unit Outside unit Drain socket Frame 6PTT screw 3 3 Attaching the drain socket As shown in the drawing below insert the drain socket into the knockout hole and fix it with the PTT screw 6 Photo 3 4 Fig 3 1 Insert the rubber plug straight ...

Page 5: ...e 2 wire cord with a white connector through the pipe sensor and LEV lead wire hole When fastening lead wires Power wires and low voltage wires are separately bundled inside the control box to reduce noise interference Lead wires from the Drain Water Lift Up Kit also need to be bundled separately Follow the steps below to hold them and the lead wires inside the control box together 1 Power wires F...

Page 6: ...e Accessory Connect each connection with vinyl chloride adhesive Otherwise the Drain Water Lift Up Kit cannot be serviced later Also the end connection may be eroded by resin and so cracked Downward pitch of more than 1 100 Support bracket Insulation 25 cm 1 5 2 m Fig 5 1 Indoor unit Indoor unit Indoor unit Take as large as possible About 10 cm Collective piping Fig 5 2 Less than 700 mm Less than ...

Page 7: ...ach the drain pipe O D ø32 PVC TUBE field supply Attach the pipe with glue for the hard vinyl chloride pipe and fix it with the band small 3 3 Perform insulation work on the drain pipe O D ø32 PVC TUBE and on the socket including elbow 4 Follow the steps in the next section to confirm the drain discharge 5 Wrap the insulation pipe 5 around the connection part between the drain socket and the drain...

Page 8: ...t the water amount with a valve so that the water amount will not exceed 0 4 ℓ min Pouring too much water may result in water leakage from the indoor unit and malfunctions of the drain pump 4 Turn on the main power of the indoor unit The drain pump will be forced to operate even if no remote controller operation is performed Check the transparent drain hose to make sure that drain is discharged 5 ...