5   Drain piping work

1. Ensure that the drain piping is downward (pitch of more than

1/100) to the outdoor (discharge) side. Do not provide any trap
or irregularity on the way. (Fig. 5-1) 

2. Ensure that any cross-wise drain piping is less than 20 m

(excluding the difference of elevation). If the drain piping is long,
provide metal braces to prevent it from waving. Never provide
any air vent pipe. Otherwise drain may be ejected.

3. Use a hard vinyl chloride pipe VP-25 (with an external diameter

of 32 mm) for drain piping.

4. Ensure that collected pipes are 10 cm lower than the unit

body’s drain port.(Fig. 5-2)

5. Do not provide any odor trap at the drain discharge port.

6. Put the end of the drain piping in a position where no odor is

generated.

7. Do not put the end of the drain piping in any drain where ionic

gases are generated.

8. The intake of the drain piping can be made 41 cm higher than

the drain discharge port. If there are some obstacles under the
ceiling, use elbows to make it at least height according to the
site. (Fig. 5-3)

Downward pitch of 
more than 1/100

Metal brace

Insulating material

25 cm

1.5 – 2 m

Fig. 5-1

Indoor unit

Indoor unit

Indoor unit

Collecvtive piping

Take as large as possible. 
About 10 cm

Fig. 5-2

within 41cm

Less than 300 mm

Drain hose
 (Accessory)

Tie band (small)
 (Accessory)

Hard vinyl chloride 90˚
elbow (field supply)

Hard vinyl
chloride (VP-25)
(field supply)

Hard vinyl chloride 90˚
elbow (field supply)

Be sure to use the supplied drain hose (Accessory).


Connect each connection with vinyl chloride adhesive. But never 
use any adhesive over the indoor unit

 

discharge port. Otherwise 

the drain-up mechanism cannot be serviced later. Also, the end 
connection may be eroded by resin and so cracked.

Fig. 5-3

Note:

If the rise portion is long, there will be a lot of returned water
in an operation stop, generating slime or odor during off-sea-
son. Ensure that the rise portion is at a minimum.

Pipe the drain piping to ensure that it discharges drain, and
insulate it to prevent dew condensation. A failure to the pip-
ing work may cause water leakage and so wet your property.

6   Confirming drain discharge

1. Insert the enclosed connector

into the red connector (2P) on the side of the

control box.

2. Remove the polyethylene plug

B

on the same side as the indoor unit piping.

3. Fill water into the feed water pump

A

using a feed water tank. In filling, be

sure to put the end of the pump in drain pan. (If the insertion is incomplete,
water may flow over the machine.)

4. Turn on the main power. The drain pump is forced to operate without any

remote controller operation. Make sure using a transparent drain hose(acces-
sory) that drain is discharged.

5. After confirmation, turn off the main power, remove the connector, and insert

the polyethylene plug into its original position, insulate drain hose.

A

Insert the pump’s end 2 to 4 cm.

B

Remove the polyethylene plug.

C

About 1000 ml

D

Water

E

Filling port

Caution:

Make sure that the drain-up mechanism operates normally for discharge
and that there is no water leakage from the connections.
•Be sure to confirm the above in a period of heating operation.
•Be sure to confirm the above before ceiling work is done in the case of a new

construction.

Summary of Contents for PAC-KD02DM-FA

Page 1: ... use for special applications such as storing food plants precision equipment or art The quality of these items may deteriorate Always provide adequate signal noise protection when installing in facilities such as hospitals and communication stations Equipment at these facilities such as inverters in house generators high frequency medical equipment two way communication equip ment may cause the a...

Page 2: ...5NMU E PDFY P18NMU E PDFY P24NMU E PDFY P27NMU E PDFY P30NMU E PDFY P36NMU E PDFY P48NMU E 2 Provided parts Check that the packet includes the following parts in addition to this installation manual 1DRAIN PUMP ASSY 2PUMP COVER ASSY 3RUBBER PLUG 4BAND 1 1 1 1 SHAPE Q TY PARTS 5PTT SCREW 4X10 6SCREW 4X10 7CONNECTOR SHAPE Q TY PARTS 8WIRING ASSY A1 8 C Use for PDFY 10 16 24 32 40 48NMU A 9WIRING ASS...

Page 3: ...ump cover and then bind the two leads with a band 4 Temporarily turn in the light brown screws in the socket section of the drain assembly 3 to 5 times Screw Light brown Screw Light brown B Rubber plug C Drainage outlet of the socket 5 From the inside of the unit insert the slightly tightened screws through the screw holes shown by B and then slowly lower the assembly so that the screws slide into...

Page 4: ...connector 4P White connector 3P Red connector 2P For trial operation of the drain pump 2 Remove the screws and then remove the control box cover 3 Remove the short circuit connector at CN31 on the circuit board and insert the white connector 3P small of the drain pump assembly 4 Insert the white connector Large on one of the leads of the drain pump assembly into the white relay connector at the si...

Page 5: ...cover Screw Screw Drain pump connector Drain sensor connector 2 Remove the screws and then remove the control box cover 3 Run the drain pump and drain sensor wires through the holes shown below Rubber bushing B White Connector Large White Connector small Rubber bushing A In the case of PDFY 10 16 24 32 40 48NMU A and PDFY P06 P08 P12 P15 P18 P24 P27 P30 P36 P48NMU E ...

Page 6: ...ii From drain sensor Procedures Warning Perform the following procedures with the power being turned off iii Fix the fuse holder item A with the PTT screw item C to the control box and attach the fuse item B iv Connect wire assembly items 8 or 9 Note Item 9 wire is intended for PDFY 40 48 NMU A and PDFY P36 P48NMU E Do not use it for other types i Remove the short circuit connector on CN31 In the ...

Page 7: ... with vinyl chloride adhesive But never use any adhesive over the indoor unit discharge port Otherwise the drain up mechanism cannot be serviced later Also the end connection may be eroded by resin and so cracked Fig 5 3 Note If the rise portion is long there will be a lot of returned water in an operation stop generating slime or odor during off sea son Ensure that the rise portion is at a minimu...

Page 8: ......

Reviews: