28
Photo. 3-2
3. Power Supply
Interface controller is applicable to both methods of interface unit power supplied from outdoor unit, and of separate interface
unit/outdoor unit power supplies. Choose one according to the site.
(Photo. 3-1)
A
Inlet for control cable
B
Inlet for power
C
Clamp
D
Interface / Outdoor unit connecting terminals
E
Earth terminal
Photo. 3-1
A
B
C
E
C
D
3.1. Interface unit power supplied from outdoor unit (Photo 3-2)
The following connection patterns are available.
The outdoor unit power supply patterns vary on models.
S1
S2
L
N
S1
S2
S3
S3
A
B
C
D
E
F
A Outdoor unit power supply
B Earth leakage breaker
C Wiring circuit breaker or isolating switch
D Outdoor unit
E Interface unit/outdoor unit connecting cables
F Interface unit
Interface unit model
PAC-IF011B-E
Wiring
Wire No.×
size (mm
2
)
Interface unit-Outdoor unit
*1
3× 1.5 (polar)
Interface unit-Outdoor unit earth
*1
1 × Min.1.5
Circuit
rating
Interface unit-Outdoor unit S1-S2
*2
AC 230 V
Interface unit-Outdoor unit S2-S3
*2
DC24 V
*1. Max. 80 m
*2. The
fi
gures are NOT always against the ground.
S3 terminal has DC 24 V against S2 terminal. However between S3 and S1, these terminals are not electrically insulated by the transformer or other device.
Notes: 1. Wiring size must comply with the applicable local and national code.
2. Power supply cables and interface unit/outdoor unit connecting cables shall not be lighter than polychloro-
prene sheathed
fl
exible cable. (Design 60245 IEC 57)
3. Install an earth longer than other cables.
Summary of Contents for PAC-IF012B