85
CHAPTER 6 INSTALLATION AND WIRING
6
6.
1 St
at
ion Numb
er
S
e
tting
CHAPTER 6
INSTALLATION AND WIRING
This chapter describes the installation and wiring of a temperature control module.
6.1
Station Number Setting
(1) Setting method
Set the station number with the rotary switch on the front of the module. Since the setting value of the station
number becomes valid at power-on, set the station number under power-off condition.
• The hundreds and tens place of a station number is set with
10.
• The ones place of a station number is set with
1.
Ex.
To set the station number to 115, set the switch as shown below.
(2) Setting range
Set the station number from 1 to 120. Setting the value other than 1 to 120 causes a communication error and the
D LINK LED flashes.
Remark
●
Changing the station number setting switch while the module is powered on causes a minor error and the ERR. LED
flashes. Undoing the change allows recovery from the error after five seconds and the ERR. LED turns off.
●
Do not set the same station number with the other station numbers. Doing so causes a communication error and the D
LINK LED does not turn on.