331
APPENDICES
A
Appendix
3 Det
a
ils of
Rem
o
te
Buf
fer Me
mory
A
reas
(20)CH
Adjustment sensitivity (dead band) setting (address: 111H, 141H, 171H,
1A1H)
To prevent a chattering in the two-position control, set the adjustment sensitivity (dead band) for the set value
(SV).
For details on the two-position control, refer to the following.
(a) Setting range
Set the value within the range 1 to 100 (0.1% to 10.0%) of the full scale of the set input range.
For details on the input range, refer to the following.
Ex.
When the value of the remote buffer memory is set as follows; CH
Input range (address: 100H, 130H,
160H, 190H): 38 (temperature measurement range: -200.0 to 400.0
), CH
Adjustment sensitivity
(dead band) setting (address: 111H, 141H, 171H, 1A1H): 10 (1.0%)
The following calculation shows that the dead band is the range of 6.0
with the set value (SV) being set
as the center of the range.
• (Full scale)
(Adjustment sensitivity (dead band) setting) = (400.0
- (-200.0
))
0.01 = 6.0
(b) Enabling the setting
Enable the setting contents by either of the following.
• Turning off and on Initial data setting request flag (RY9) while the operations of all channels are stopped
• Turning off and on During operation setting change instruction (RY10)
(c) Default value
The default values are set to 5 (0.5%) in all channels.
Standard
Heating-cooling
ON
OFF
Temperature
process value (PV)
Set value (SV)
Transistor output
Time
Adjustment
sensitivity
(dead band)
Summary of Contents for NZ2GF2B-60TCRT4
Page 2: ......
Page 86: ...84 Memo ...
Page 268: ...266 Memo ...
Page 377: ...375 APPENDICES A Appendix 6 External Dimensions Memo ...
Page 383: ...I 4 4 7 8 381 Memo ...
Page 387: ......