232
CHAPTER 9
PROGRAMMING
This chapter describes the programming of a temperature control module.
9.1
Precautions for Programming
This section describes precautions to create CC-Link IE Field Network programs.
(1) Cyclic transmission program
For a cyclic transmission program, interlock with the following link special relay (SB) and link special register
(SW).
• Own station data link status (master station) (SB0049)
• Data link status (each station) (SW00B0 to SW00B7)
For the link special relay (SB) and link special register (SW), refer to the following.
User's manual for the master/local module used
Ex.
Interlock example
(2) Transient transmission program
For a transient transmission program, interlock with the following link special relay (SB) and link special register
(SW).
• Own station baton pass status (master station) (SB0047)
• Baton pass status (each station) (SW00A0 to SW00A7)
For the link special relay (SB) and link special register (SW), refer to the following.
User's manual for the master/local module used
Ex.
Interlock example
Communication program with station No.1
Communication program with station No.2
Dedicated instruction to station No.1
Start-up contact
Summary of Contents for NZ2GF2B-60TCRT4
Page 2: ......
Page 86: ...84 Memo ...
Page 268: ...266 Memo ...
Page 377: ...375 APPENDICES A Appendix 6 External Dimensions Memo ...
Page 383: ...I 4 4 7 8 381 Memo ...
Page 387: ......