(1) Error code list (0000
H
to 07FF
H
)
The following describes the error messages, error conditions, causes and actions of the error codes (0000
H
to
07FF
H
).
If an error occurred, after taking action, clear the error.
For the Ethernet adapter module, use an SLMP command, Clear Error (command: 1617).
End code or
error code
Error and cause
Action
0100
H
System error
Please consult your local Mitsubishi representative.
0101
H
to 0103
H
Network module failure
• Malfunction may have occurred due to noise. Check the wire and cable
distances and grounding condition of each device, and take measures
against noise.
• Perform a unit test. If the same error is displayed again, the hardware of
the Ethernet adapter module may be faulty. Please consult your local
Mitsubishi representative.
0104
H
Receive queue full
• Reduce the frequency of transient transmission and then retry the
operation.
• Check if the cables and switching hub are connected properly.
0105
H
Network module failure
• Malfunction may have occurred due to noise. Check the wire and cable
distances and grounding condition of each device, and take measures
against noise.
• Perform a unit test. If the same error is displayed again, the hardware of
the Ethernet adapter module may be faulty. Please consult your local
Mitsubishi representative.
0106
H
to 0109
H
Parameter error
Write the parameters again. If the same error is displayed again, please
consult your local Mitsubishi representative.
010AH
Parameter check result error
010BH
to 010C
H
System error
• Malfunction may have occurred due to noise. Check the wire and cable
distances and grounding condition of each device, and take measures
against noise.
• Perform a unit test. If the same error is displayed again, the hardware of
the Ethernet adapter module may be faulty. Please consult your local
Mitsubishi representative.
010D
H
Ethernet adapter module failure
Restart the Ethernet adapter module. If the same error is displayed again,
please consult your local Mitsubishi representative.
010E
H
Ethernet adapter module stop error
• Check the description in "CC-Link IE Field Network Error" in the "Ethernet
Adapter Diagnostics" window of the configuration tool, and take action.
• Perform the CC-Link IE Field Network diagnostics from the master
station, identify the error and take action.
• Write the parameters again. If the same error is displayed again, please
consult your local Mitsubishi representative.
0180
H
Sum check code error
Write the parameters again. If the same error is displayed again, please
consult your local Mitsubishi representative.
0181
H
Start block code error
0182
H
End block code error
0183
H
Operation setting parameter error
0184
H
Initial setting parameter error
0185
H
Connection setting parameter error
0186
H
Account setting parameter error
0187
H
CC-Link IE Field Network gateway setting error
Summary of Contents for NZ2GF-ETB
Page 1: ...CC Link IE Field Network Ethernet Adapter Module User s Manual NZ2GF ETB ...
Page 2: ......
Page 49: ...47 CHAPTER 4 PROCEDURE BEFORE THE OPERATION 4 4 1 Start Up Procedure Memo ...
Page 198: ...196 a Detail Setting ...
Page 246: ...244 Memo ...
Page 253: ......