[Measurement setting
selection screen]
(3) Demand time limit setting
[Default value: 2 min.]
•
Select DEMAND on the measurement setting selection screen. (Screen [1])
• Press ENTER to switch to the demand time limit display screen. (Screen [2])
Setting value switches through 0
⇔
1
⇔
2
⇔
...
⇔
14
⇔
15
⇔
0.... (in 1 min. steps). Press ENTER to decide the setting.
• Select YES on the allow changes screen and press ENTER to decide the setting. (Screen [3])
Screen [1]
MENU
SETTING
MEASURE
DEMAND
[Demand time limit
display screen]
Screen [2]
Demand time limit
setting value
Select with UP/DOWN
[Allow changes screen]
Screen [3]
To [Measurement
setting selection
screen]
MENU
SETTING
MEASURE
DEMAND
OK?
NO
YES
[ m i n ]
3
ENTER
MENU
ENTER
MENU
ENTER
MENU
SETTING
MEASURE
PHASE
LINE_S
PULSE
DEMAND
[Measurement setting
selection screen]
(4) Pulse unit setting
[Default value: 1 kWh]
• Select PULSE on the measurement setting selection screen. (Screen [1])
• Press ENTER to switch to the pulse unit display screen. (Screen [2])
Setting value switches through 1
⇔
10
⇔
100
⇔
1000
⇔
10000
⇔
1.... Press ENTER to decide the setting.
• Select YES on the allow changes screen and press ENTER to decide the setting. (Screen [3])
Screen [1]
[Pulse unit display screen]
Screen [2]
Pulse unit setting value
Select with UP/DOWN
[Allow changes screen]
Screen [3]
To [Measurement
setting selection
screen]
MENU
SETTING
MEASURE
PULSE
OK?
NO
YES
ENTER
MENU
ENTER
MENU
Select with
UP/DOWN
Select NO
⇔
YES
with UP/DOWN
Select NO
⇔
YES
with UP/DOWN
Select with
UP/DOWN
MENU
SETTING
MEASURE
PHASE
LINE_S
DEMAND
PULSE
[Measurement setting
selection screen]
MENU
SETTING
MEASURE
LINE_S
[Line system display screen]
[Allow changes screen]
(2) Line system setting
[Default value: 3P3W] (3P4W for four-pole products)
• Select LINE_S on the measurement setting selection screen. (Screen [1])
• Press ENTER to switch to the line system display screen. This allows the line system setting value to be changed. (Screen [2])
1P2W (single-phase two-wire)
1P3W (single-phase three-wire)
3P3W (three-phase three-wire)
3P4W (three-phase four-wire) *Only for four-pole products
Select an option and then press ENTER to decide the setting value.
• Select YES on the allow changes screen and press ENTER to decide the setting. (Screen [3])
Screen [1]
Screen [2]
Screen [3]
1P 2 W
1P 3 W
3 P 3 W
3 P 4 W
Line system
setting value
Select with UP/DOWN
MENU
SETTING
MEASURE
LINE_S
OK?
NO
YES
ENTER
MENU
ENTER
MENU
ENTER
To [Measurement
setting selection
screen]
Select NO
⇔
YES
with UP/DOWN
Select with
UP/DOWN
Summary of Contents for NF250-HEV
Page 62: ...MEMO ...
Page 63: ......
Page 64: ...Nov 2019 LN107A330H02 IB63E30 A 1911 MEE MDU Breakers ...