En-6

4-3. LOCKING THE OPERATION MODE OF THE AIR CONDITIONER (COOL, DRY, HEAT)

4-4. LOWERING THE OPERATION NOISE OF THE OUTDOOR UNIT

4-2. GAS CHARGE

Perform gas charge to unit.
) Connect gas cylinder to the service port of stop valve.
2) Perform air purge of the pipe (or hose) coming from refrigerant gas cylinder.

3) Replenish specified amount of the refrigerant, while operating the air condi

-

tioner for cooling.

Note:

In case of adding refrigerant, comply with the quantity specified for the refrigerat

-

ing cycle.

CAUTION:

When charging the refrigerant system with additional refrigerant, be sure to use 
liquid  refrigerant. Adding  gas  refrigerant  may  change  the  composition  of  the 
refrigerant in the system and affect normal operation of the air conditioner. Also, 
charge the liquid refrigerant slowly, otherwise the compressor will be locked.
To  maintain  the  high  pressure  of  the  gas  cylinder,  warm  the  gas  cylinder  with 

warm water (under 40°C) during cold season. But never use naked fire or steam.

HEAT

COOL/DRY

•  Description of the function:
 

With  this  function,  once  the  operation  mode  is  locked  to  either  COOL/DRY 
mode or HEAT mode, the air conditioner operates in that mode only.

*  Changing the setting is required to activate this function. Please explain about 

this function to your customers and ask them whether they want to use it.

[How to lock the operation mode]

) Be  sure  to  turn  off  the  main  power  for  the  air  conditioner  before  making  the 

setting.

2) Set the “” of SW on the outdoor controller board to ON to enable this func-

tion.

3) To lock  the operation  mode  in  COOL/DRY mode,  set the “2” of SW on  the 

outdoor controller board to OFF. To lock the operation in HEAT mode, set the 
same switch to ON.

4) Turn on the main power for the air conditioner.

•  Description of the function:
 

With this function, the operating noise of the outdoor unit can be lowered by reducing the operation load, for example, during nighttime in COOL mode. 
However, please note that the cooling and heating capacity may lower if this function is activated.

*  Changing the setting is required to activate this function. Please explain about this function to your customers and ask them whether they want to use it.

Union

Stop valve

Liquid 
pipe

Indoor 

unit

Stop valve with 

service port

Gas 
pipe

Refrigerant gas 
cylinder  
operating valve
(for R40A)

Gauge manifold 
valve (for R40A)

Charge hose 
(for R40A)

Refrigerant gas cylinder for R40A with siphon

Electronic scale for refrigerant charging

Refrigerant (liquid)

Outdoor 

unit

Union

Union

Union

4-5. CHANGING THE AMPERE LIMIT

•  Description of the function:

  With this function, the amount of current that flows in the outdoor unit can be 

changed.

Note:

Use this function only when the amount of current exceeds the allowed value.

[How to change the ampere limit]

) Be  sure  to  turn  off  the  main  power  for  the  air  conditioner  before  making  the 

setting.

2) Make the setting referring to the table below.
3) Turn on the main power for the air conditioner.

SW2

20A

25A

Factory setting

Full

Lower the operating noise

[How to lower the operating noise]

) Be  sure  to  turn  off  the  main  power  for  the  air  conditioner  before  making  the 

setting.

2) Set the “3” of SW on the outdoor controller board to ON to enable this func-

tion.

3) Turn on the main power for the air conditioner.

JG79A665H01_en.indd   6

2012/09/24   19:20:05

Summary of Contents for MXZ-6C122VA

Page 1: ...nuale di instal lazione Εγχειρίδιο εγκατάστασης Για τον ΤΕΧΝΙΚΟ Στο παρόν εγχειρίδιο περιγράφεται μόνο η εγκατάσταση της μονάδας εξωτερικού χώρου Για την εγκατάσταση της μονάδας εσωτερικού χώρου ανατρέξτε στο εγχειρίδιο εγκατάστασης της μονάδας εσωτερικού χώρου Manual de Instalação Para o INSTALADOR Este manual descreve apenas a instalação da unidade exterior Quando proceder à instalação da unidad...

Page 2: ...d ance with EN378 1 n Check that the refrigerant gas does not leak after installation has been completed If refrigerant gas leaks indoors and comes into contact with the flame of a fan heater space heater stove etc harmful substances will be generated n Use appropriate tools and piping materials for installation The pressure of R410A is 1 6 times more than R22 Not using appropri ate tools or mater...

Page 3: ...ar outdoor unit so as to reduce vibration transmitted from there 500 or more 200 or more 350 or more 100 or more 100 or more 500 or more 100 or more Service space 350 or more 350 or more When installing the unit in an area that is enclosed with walls such as a verandah be sure to have enough space as shown below In this case the air conditioning capacity and power consumption might deteriorate Whe...

Page 4: ...t 1 1 Note Place indoor outdoor unit connecting wire B and power supply cord A at least 1 m away from the TV antenna wire The Q ty for B to K in the above table is quan tity to be used per indoor unit More than 100 mm Open as a rule More than 500 mm if the front and both sides are open More than 100 mm More than 200 mm if there are obstacles to both sides Open as a rule More than 500 mm if the bac...

Page 5: ...utdoor unit connecting wire B from the indoor unit correctly on the terminal block Be careful not to make mis wiring Fix the wire to the terminal block securely so that no part of its core is appeared and no external force is conveyed to the connecting section of the terminal block 3 Firmly tighten the terminal screws to prevent them from loosening Af ter tightening pull the wires lightly to confi...

Page 6: ...3 Remove flare nuts attached to indoor and outdoor units then put them on pipe having completed burr removal Not possible to put them on after flaring work 4 Flaring work Fig 4 5 Firmly hold copper pipe in the dimension shown in the table Select A mm from the table according to the tool selected 5 Check Compare the flared work with Fig 6 If flare is noted to be defective cut off the flared section...

Page 7: ...o lock the operation mode in COOL DRY mode set the 2 of SW1 on the outdoor controller board to OFF To lock the operation in HEAT mode set the same switch to ON 4 Turn on the main power for the air conditioner Description of the function With this function the operating noise of the outdoor unit can be lowered by reducing the operation load for example during nighttime in COOL mode However please n...

Page 8: ...ED indication during detection LED1 Red LED2 Yellow LED3 Green Lighted Lighted Once Result of piping wiring correction function LED1 Red LED2 Yellow LED3 Green Result Lighted Not lighted Lighted Completed Problem corrected or normal Once Once Once Not completed Detection failed Other indications Refer to SAFETY PRE CAUTIONS WHEN LED FLASHES located behind the service panel 5 RELOCATION AND MAINTEN...

Page 9: ... numéro de série de l appareil se trouve sur la plaque du produit Opmerking het serienummer staat op het naamplaatje van het product Nota El número de serie se encuentra en la placa que contiene el nombre del producto Nota il numero di serie si trova sulla targhetta del prodotto Σημείωση Ο σειριακός του αριθμός βρίσκεται στην πινακίδα ονόματος του προϊόντος Nota o número de série encontra se na pl...

Reviews: