background image

En-6

4-3. LOCKING THE OPERATION MODE OF THE AIR CONDITIONER (COOL, DRY, HEAT)

4-4. LOWERING THE OPERATION NOISE OF THE OUTDOOR UNIT

4-2. GAS CHARGE

Perform gas charge to unit.
) Connect gas cylinder to the service port of stop valve.
2) Perform air purge of the pipe (or hose) coming from refrigerant gas cylinder.

3) Replenish specified amount of the refrigerant, while operating the air condi

-

tioner for cooling.

Note:

In case of adding refrigerant, comply with the quantity specified for the refrigerat

-

ing cycle.

CAUTION:

When charging the refrigerant system with additional refrigerant, be sure to use 
liquid  refrigerant. Adding  gas  refrigerant  may  change  the  composition  of  the 
refrigerant in the system and affect normal operation of the air conditioner. Also, 
charge the liquid refrigerant slowly, otherwise the compressor will be locked.
To  maintain  the  high  pressure  of  the  gas  cylinder,  warm  the  gas  cylinder  with 

warm water (under 40°C) during cold season. But never use naked fire or steam.

•  Description of the function:
 

With  this  function,  once  the  operation  mode  is  locked  to  either  COOL/DRY 
mode or HEAT mode, the air conditioner operates in that mode only.

*  Changing the setting is required to activate this function. Please explain about 

this function to your customers and ask them whether they want to use it.

[How to lock the operation mode]

) Be  sure  to  turn  off  the  main  power  for  the  air  conditioner  before  making  the 

setting.

2) Set the “” of SW on the outdoor controller board to ON to enable this func-

tion.

3) To lock  the operation  mode  in  COOL/DRY mode,  set the “2” of SW on  the 

outdoor controller board to OFF. To lock the operation in HEAT mode, set the 
same switch to ON.

4) Turn on the main power for the air conditioner.

•  Description of the function:
 

With this function, the operating noise of the outdoor unit can be lowered by reducing the operation load, for example, during nighttime in COOL mode. 
However, please note that the cooling and heating capacity may lower if this function is activated.

*  Changing the setting is required to activate this function. Please explain about this function to your customers and ask them whether they want to use it.

4-5. CHANGING THE AMPERE LIMIT

•  Description of the function:

  With this function, the amount of current that flows in the outdoor unit can be 

changed.

Note:

Use this function only when the amount of current exceeds the allowed value.

[How to change the ampere limit]

) Be  sure  to  turn  off  the  main  power  for  the  air  conditioner  before  making  the 

setting.

2) Make the setting referring to the table below.
3) Turn on the main power for the air conditioner.

Lower the operating noise

[How to lower the operating noise]

) Be  sure  to  turn  off  the  main  power  for  the  air  conditioner  before  making  the 

setting.

2) Set the “3” of SW on the outdoor controller board to ON to enable this func-

tion.

3) Turn on the main power for the air conditioner.

Union

Stop valve

Liquid 
pipe

Indoor 

unit

Stop valve with 

service port

Gas 
pipe

Refrigerant gas            
cylinder  
operating valve
(for R40A)

Gauge manifold 
valve (for R40A)

Charge hose 
(for R40A)

Refrigerant gas cylinder for R40A with siphon

Electronic scale for refrigerant charging

Refrigerant (liquid)

Outdoor 

unit

* E unit is for 
5D02VA only.

Union

Union

Union

HEAT

COOL/DRY

SW2

MXZ-5D00VA

MXZ-4D80VA

0.5 A

0.5 A

5.5 A

5.5 A

Factory setting

Full

Factory setting

Full

BH79A024H01_en.indd   6

2014/01/21   13:46:51

Summary of Contents for MXZ-4D80VA

Page 1: ...nual For INSTALLER This manual only describes the installation of outdoor unit When installing the indoor unit refer to the installation manual of indoor unit Split type Air Conditioner MXZ 4D80VA MXZ 5D100VA English ...

Page 2: ...nerated n Check that the refrigerant gas does not leak after installation has been completed If refrigerant gas leaks indoors and comes into contact with the flame of a fan heater space heater stove etc harmful substances will be generated n Use appropriate tools and piping materials for installation The pressure of R410A is 1 6 times more than R22 Not using appropri ate tools or materials and inc...

Page 3: ...ow or there is a possibility of becoming short cycle install an outlet guide and make sure there is enough space behind of the unit When installing two or more units do not install the units in front or behind each other 100 or more 200 or more 350 or more 500 or more 500 or more Unit mm 5 Obstacles in front behind and on side s 4 Obstacles in front and behind The unit can be used by at taching an...

Page 4: ...7 mm After the leak test apply insulat ing material tightly so that there is no gap When the piping is to be at tached to a wall containing metals tin plated or metal netting use a chemically treated wooden piece 20 mm or thicker between the wall and the piping or wrap 7 to 8 turns of insulation vinyl tape around the piping To use existing piping perform COOL operation for 30 minutes and pump down...

Page 5: ...s conveyed to the connecting section of the terminal block 3 Firmly tighten the terminal screws to prevent them from loosening Af ter tightening pull the wires lightly to confirm that they do not move 4 Perform 2 and 3 for each indoor unit 5 Connect power supply cord A 6 Fix indoor outdoor unit connecting wire B and power supply cord A with the cable clamps 7 Close the service panel securely Make ...

Page 6: ...ring work Fig 4 5 Firmly hold copper pipe in the dimension shown in the table Select A mm from the table according to the tool selected 5 Check Compare the flared work with Fig 6 If flare is noted to be defective cut off the flared section and do flar ing work again 1 Remove service port cap of stop valve on the side of the outdoor unit gas pipe The stop valves are fully closed and covered in caps...

Page 7: ... on the outdoor controller board to OFF To lock the operation in HEAT mode set the same switch to ON 4 Turn on the main power for the air conditioner Description of the function With this function the operating noise of the outdoor unit can be lowered by reducing the operation load for example during nighttime in COOL mode However please note that the cooling and heating capacity may lower if this...

Page 8: ...vent electronic control P C board damage make sure to perform static elimi nation before operating this function This function does not operate when the outside temperature is 0 C or below LED indication during detection LED1 Red LED2 Yellow LED3 Green Lighted Lighted Once Result of piping wiring correction function LED1 Red LED2 Yellow LED3 Green Result Lighted Not lighted Lighted Completed Probl...

Reviews: