The standard specifications apply only to the operation of the air conditioner under normal conditions.
Since operating conditions vary according to the areas where these units are installed, the following information has been pro-
vided to clarify the operating characteristics of the air conditioner under the conditions indicated by the performance curve.
(1) GUARANTEED VOLTAGE
198 ~ 253 V 60 Hz
(2) AIR FLOW
Air flow should be set at MAX.
(3) MAIN READINGS
(1) Indoor intake air wet-bulb temperature :
°FWB
}
Cooling
(2) Indoor outlet air wet-bulb temperature :
°FWB
(3) Outdoor intake air dry-bulb temperature :
°FDB
(4) Total input:
W
(5) Indoor intake air dry-bulb temperature :
°FDB
}
Heating
(6) Outdoor intake air wet-bulb temperature :
°FWB
(7) Total input :
W
Indoor air wet and dry bulb temperature difference on the left side of the following chart shows the difference between the
indoor intake air wet and dry bulb temperature and the indoor outlet air wet and dry bulb temperature for your reference at
service.
How to measure the indoor air wet and dry bulb temperature difference
1.
Attach at least 2 sets of wet and dry bulb thermometers to the indoor air intake as shown in the figure, and at least 2 sets of
wet and dry bulb thermometers to the indoor air outlet. The thermometers must be attached to the position where air speed
is high.
2.
Attach at least 2 sets of wet and dry bulb thermometers to the outdoor air intake.
Cover the thermometers to prevent direct rays of the sun.
3.
Check that the air filter is cleaned.
4.
Open windows and doors of room.
5.
Press the EMERGENCY OPERATION switch once (twice) to start the EMERGENCY COOL (HEAT) MODE.
6.
Compressor starts running at 33 Hz (COOL) or 45 Hz (HEAT). The frequency at each operation mode is fixed.
7.
When system stabilizes after more than 15 minutes, measure temperature and take an average temperature.
8.
10 minutes later, measure temperature again and check that the temperature does not change.
INDOOR UNIT
OUTDOOR UNIT
Wet and dry bulb
thermometers
Wet and dry bulb
thermometers
OBH702N