5
3
SPECIFICATION
Outdoor unit model
MUZ-HM09NA
-
U1
MUZ-HM09NA2
-
U1
MUZ-HM09NA
-
U8
MUZ-HM09NA2
-
U8
Capacity
Rated (Minimum~Maximum)
Cooling 1
Btu/h
9,000 ( 3,800 ~ 10,000 )
Heating 47 1
Btu/h
10,900 ( 4,500 ~ 11,800 )
Capacity
Rated (Maximum)
Heating 17 2
Btu/h
6,700 (7,200)
Power consumption
Rated (Minimum~Maximum)
Cooling 1
W
750 (240 - 850)
750 (205 - 850)
Heating 47 1
W
900 (240 - 1,000)
900 (255 - 1,000)
Power consumption
Rated (Maximum)
Heating 17 2
W
700 (780)
EER
1
[SEER]
3
Cooling
12.0 [ 18.0 ]
HSPF IV
4
Heating 10.0
[
NA
] / 8.5 [
NA2
]
COP Heating
1
3.55
Power factor
Cooling (208/230) %
87/87
84/84
Heating (208/230) %
90/90
90/89
Power supply
V , phase , Hz
208/230 , 1 , 60
Max. fuse size (time delay)
A
15
Min. circuit ampacity
A
9
12
Fan motor
F.L.A
A
0.50
Compressor
Model KNB073FRVMC
KNB073FQDHC
R.L.A A
6.2
6.6
L.R.A A
7.7
8.2
Refrigeration oil
fl oz. (L) (Model)
9.1 (0.27) (FV50S)
10.8 (0.32) (NEO22)
Refrigerant control
Linear expansion valve
Sound level
1
Cooling dB(A)
46
Heating
dB(A)
50
Airfl ow
High - Med. - Low
Cooling CFM
1,063
Heating
CFM
1,282 - 1,105
1,240 - 1,105
Fan speed
High - Med. - Low
Cooling
rpm
740
Heating
rpm
890 - 770
860 - 770
Defrost method
Reverse cycle
Dimensions
W
in.
31-1/2
D
in.
11-1/4
H
in.
21-5/8
Weight Ib.
73
External fi nish
Munsell 3Y 7.8/1.1
Refrigerant piping
Not supplied
Refrigerant pipe size
(Min. wall thickness)
Liquid in.
1/4
(0.0315)
Gas in.
3/8
(0.0315)
Connection method
Indoor Flared
Outdoor Flared
Between the indoor &
outdoor units
Height difference
ft.
40
Piping length
ft.
65
Refrigerant charge (R410A)
1 lb. 12 oz.
NOTE
: Test conditions are based on AHRI 210/240.
1: Rating conditions (Cooling) — Indoor: 80˚FDB, 67˚FWB, Outdoor: 95˚FDB, (75˚FWB)
(Heating) — Indoor: 70˚FDB, 60˚FWB, Outdoor: 47˚FDB, 43˚FWB
2: (Heating)
—
Indoor: 70˚FDB, 60˚FWB, Outdoor: 17˚FDB, 15˚FWB
3: Test condition (Refer to page 9.)
4: Test condition (Refer to page 9.)
OBH747C