J Check of power supply
Is there voltage 230 VAC
between the indoor terminal
block S1 and S2?
No
Yes
Replace the indoor
electronic control P.C.
board.
Rectify indoor/outdoor
connecting wire.
Yes
If light up, OK.
If
fl
ash, refer to 11-3.
Does The upper lamp of
OPERATION INDICATOR lamp on
the indoor unit light up?
Dose LED on the inverter P.C.
board light up or
fl
ash? (Refer
to 11-6.1.)
No
Replace the inverter
P.C. board.
Is there voltage 280 - 370 VDC
between DB61 (+) and DB61 (–)
on the inverter P.C. board?
(Refer to 11-6.1.)
No
Check the electric parts in main circuit.
Yes
Yes
No
Disconnect the connector between
compressor and intelligent power
module.
Turn ON power supply and press
EMERGENCY OPERATION switch.
Inverter P.C. board
(Solder side)
DB61
280 - 370 VDC
MUZ-GE25VA MUZ-GE25VAH MUZ-GE35VA MUZ-GE35VAH MUZ-GE42VA MUZ-GE42VAH
MUZ-GE50VA MUZ-GE50VAH
MUZ-GE60VA MUZ-GE71VA
Is there voltage 230 VAC
between the indoor terminal
block S1 and S2?
No
Yes
Replace the indoor
electronic control P.C.
board.
Rectify indoor/outdoor
connecting wire.
Yes
If light up, OK.
If
fl
ash, refer to 11-3.
Does the upper lamp of
OPERATION INDICATOR on the
indoor unit light up?
Dose LED on the inverter P.C.
board light up or
fl
ash? (Refer
to 11-6.1.)
No
Replace the inverter
P.C. board.
Is there bus-bar voltage 325 - 370
VDC between JP715 (+) and JP30
(–) on the inverter P.C. board?
(Refer to 11-6.1.)
No
Check the electric parts in main circuit.
Yes
Yes
No
Disconnect the connector between
compressor and intelligent power
module.
Turn ON power supply and press
EMERGENCY OPERATION switch.
325 -370 VDC
JP30 JP715
MUZ-GE25/35/42/50
MUZ-GE60/71