background image

11

6-3

PIPE CONNECTION

1. Indoor unit connection

• Connect both liquid and gas piping to the indoor unit.

- Apply a thin coat of refrigerant oil on the seat surface

of pipe.

- For connection first align the center, then hand tighten

the first 3 to 4 turns of flare nut.

- Use tightening torque table below as a guideline for

the indoor unit side union joint section, and tighten us-
ing two wrenches. Excess tightening damages the
flared section.

Pipe diameter

Tightening torque

mm

N·m

kgf·cm

6.35

13.7 to 17.7

140 to 180

9.52

34.3 to 41.2

350 to 420

2. Outdoor unit connection

• Connect pipes to stop valve pipe joint of the outdoor unit in

the same manner applied for the indoor unit.

- For tightening, use a torque wrench or spanner, and

use the same tightening torque applied for the indoor
unit.

3. Refrigerant pipe insulation

• Use pipe cover (foam polyethylene 8 mm thickness) which

is contained in accessories, insulate both liquid and gas
pipes together. Put the refrigerant piping and apply piping
tape 

C

.

a

Indoor unit refrigerant pipe

b

Flare joint

d

Pipe cover

A

Refrigerant pipe

C

Piping tape

4. Knockout cover

• Attach knockout cover 

9

 to close knockout hole to prevent

rat or something strange from getting into the indoor unit.

9

Knockout cover

0

Screw for 

9

 4 

×

 10 mm

A

b

a

c

d

c

9

0

Connecting wire and
refrigerant pipes
must be separated.

6-4

PURGING PROCEDURES · LEAK TEST

• Use the vacuum pump for air purging for the purpose of environmental protection.

PURGING PROCEDURES

Connect the refrigerant pipes (both liquid pipe and the gas pipe) between the indoor and the outdoor unit.

Remove the service port cap of the stop valve on the side of the outdoor unit gas pipe. (The stop valve will
not work in it initial state fresh out of the factory (totally closed with cap on).)

Connect the gauge manifold valve and the vacuum pump to the service port of the stop valve on the gas
pipe side of the outdoor unit.

Run the vacuum pump. (Vacuumize for more than 15 minutes.)

Check the vacuum with the gauge manifold valve, then close the gauge manifold valve, and stop the vacuum
pump.

Leave as it is for one or two minutes. Make sure the pointer gauge manifold valve remains in the same
position. Confirm that the pressure gauge shows–0.101 Mpa [Gauge] (–760 mmHg).

Remove the gauge manifold valve quickly from the service port of the stop valve.

After refrigerant pipes are connected and evacuated, fully open all stop valves on both sides of gas pipe and
liquid pipe.
Operating without fully opening lowers the performance and this causes trouble.

Pipe length up to 7 m

No gas charge is needed.

Pipe length exceeding 7 m

Charge the prescribed amount of

gas. (refer to 4)

Tighten the cap to the service port to obtain the initial status.

Retighten the cap.

Leak test

Tightening torque

N·m

kgf·cm

Cap for service port

13.7 to 17.7

140 to 180

Cap for stop valve

19.6 to 29.4

200 to 300

*Close

*Open

Hexagonal wrench

Stop valve

*4 to 5 turns

Stop valve

(or the vacuum pump with
the function to prevent the
back flow)

Gauge manifold
valve (for R410A)

Pressure gauge
    (for R410A)

Compound pressure
gauge (for R410A)

-0.101MPa
(-760 mmHg)

Handle
Low

Handle High

Window

Charge hose
(for R410A)

Vacuum
pump

Adapter for preventing the
back flow

Charge hose
(for R410A)

Service port

Stop
valve

Summary of Contents for MUZ-A12YV

Page 1: ...TALLATION LOCATION 2 3 INSTALLATION DIAGRAM ACCESSORIES 3 4 INDOOR UNIT INSTALLATION 4 5 OUTDOOR UNIT INSTALLATION 9 6 INDOOR OUTDOOR UNIT CONNECTION FINISHING AND TEST RUN 10 7 FOR MOVEMENT AND MAINTENANCE 13 Floor and CeilingType Air Conditioner MCFZ A12WV MUZ A12YV H FLARE CONNECTION TYPE English HFC utilized R410A ...

Page 2: ...tion of the air conditioner may interfere with radio or TV reception in areas where reception is weak An amplifier may be required for the affected device In a place as far away as possible from fluorescent and incandescent lights so the infrared remote control can operate the air conditioner normally Where the air filter can be removed and replaced easily 2 2 WIRELESS REMOTE CONTROLLER MOUNTING P...

Page 3: ...o 5 F Fixing screw for E The quantity depends on the pipe length 2 to 5 G Drain joint pipe PVC pipe OD ø26 L 50 mm 1 H Power supply cord 3 core 1 0 mm2 1 I Piping hole repair parts Putty and Wall hole cover 1 J Installation plate fixing bolt M10 4 K Nut Spring washer for J M10 4 set REFRIGERANT AND DRAIN PIPE SIZES Refrigerant pipe Liquid OD ø6 35 Gas OD ø9 52 Drain pipe Hard PVC pipe OD ø26 OPTIO...

Page 4: ...may cause dew drippage 4 1 A CASE OF SUSPENDING INDOOR UNIT FROM THE CEILING 4 1 1 MOUNTING INSTALLATION PLATE FIXING BOLTS 4 INDOOR UNIT INSTALLATION 1 Determine the locations of installation plate fixing bolts Use installation pattern to determine the locations of instal lation plate fixing bolts J a Installation pattern Details are printed on pattern Attention Surrounding temperature and humidi...

Page 5: ...wn in Fig 2 Be sure to confirm letters FRONT in installation plates 1 set FRONT side to air outlet side of indoor unit a FRONT 1 Installation plate 2 In case of fixing installation plates 1 above the ceiling put installation plates fixing bolt through a nut a spring washer the installation plate a spring washer and double nut Fig 3 In case of fixing installation plates 1 forward the ceiling direct...

Page 6: ...irm the dimensions as below 4 2 4 FRONT GRILLE REMOVAL See to 4 1 4 Page 5 4 2 5 OPENING KNOCKOUT HOLE See to 4 1 5 Page 5 Installation pattern Remove installation pattern after installing Horizontal base line Hole for refrigerant and drain pipe in the case of downward piping Hole for refrigerant and drain pipe in the case of rear piping Installation plate 1 FRONT 4 2 6 FIXING UNIT TO INSTALLATION...

Page 7: ...e to fix the cable by cable clamp 3 Replace the terminal cover securely Cable clamp Screw Terminal cover Warning Attach the electrical part cover securely If it is attached incorrectly it could result in a fire an elec tric shock due to dust water etc Use the specified indoor outdoor unit connecting wire to connect the indoor and outdoor units and fix the wire to the terminal block securely so tha...

Page 8: ...rain pipe cover D Drain pipe VP 20 c 8 D b a d b a 30 2 In case of connecting drain pipe D to drain joint bush through drain hose Drain hose 7 which is contained in accessories is flexible so use it when drain pipe D should be alternated direction Be sure to wind pipe cover which is provided in accessories around drain hose with vinyl tape Cut VP 20 in dimension as shown at the right and connect d...

Page 9: ...en the terminal screws to prevent them from loosening After tightening pull the wires lightly to confirm that they do not move Warning Be sure to attach the service panel of the outdoor unit securely If it is not attached correctly it could result in a fire or an electric shock due to dust water etc Indoor terminal block Outdoor terminal block N 3 2 3 N 2 Indoor outdoor unit connecting wire B 4 co...

Page 10: ...e for R410A Yes Substitutable for R410A Electronic scale for re frigerant charging 6 2 FLARING WORK Main cause of gas leakage is defect in flaring work Carry out correct flaring work in the following procedure 2 Burrs removal Completely remove all burrs from the cut cross section of pipe Put the end of the copper pipe to downward direction as you remove burrs in order to avoid to let burrs drop in...

Page 11: ...nd the gas pipe between the indoor and the outdoor unit Remove the service port cap of the stop valve on the side of the outdoor unit gas pipe The stop valve will not work in it initial state fresh out of the factory totally closed with cap on Connect the gauge manifold valve and the vacuum pump to the service port of the stop valve on the gas pipe side of the outdoor unit Run the vacuum pump Vacu...

Page 12: ...in the following to the customer how to control temperature how to re move the air filters how to remove or put the remote controller in the remote controller holder how to clean precautions etc Recommend the customer to carefully read the Operating Instruction Book EMERGENCY OPERATION switch 6 5 TEST RUN Before performing the test run recheck for any wrong wiring Wrong wiring prevents normal oper...

Page 13: ...arge refrigerant into the atmosphere during installation reinstallation or re pairs to the refrigerant circuit For additional charging charge the refrigerant from liquid phase of the gas cylinder If the refrigerant is charged from the gas phase composition change may occur in the refrigerant inside the cylinder and the outdoor unit In this case ability of the refrigerating cycle decreases or norma...

Page 14: ... TOKYO 100 8310 JAPAN This product is designed and intended for use in the residential commercial and light industrial environment The product at hand is based on the following EU regulations Low Voltage Directive 73 23 EEC Electromagnetic Compatibility Directive 89 336 EEC ...

Reviews: