28
Outline of the function
This air conditioner can memorize the abnormal condition which has occurred once.
Even though LED indication listed on the troubleshooting check table (11-3.) disappears, the memorized failure details can be recalled.
11-2. FAILURE MODE RECALL FUNCTION
1. Flow chart of failure mode recall function for the indoor/outdoor unit
2. Blinking pattern when the indoor unit is abnormal:
3.Blinking pattern when the outdoor unit is abnormal:
ON
OFF
Beeps
Repeated cycle
Repeated cycle
ON
OFF
No beep
Beeps
Repeated cycle
2.5-second OFF
Blinking at 0.5-
second interval
2.5-second OFF
3-second ON
Blinking at 0.5-
second interval
Beeps
Repeated cycle
2.5-second OFF
Blinking at 0.5-
second interval
No beep
Beeps
Repeated cycle
2.5-second OFF
3-second ON
Blinking at 0.5-
second interval
Repeated cycle
Beeps
NOTE:
1. Make sure to release the failure mode recall function after it is set up, otherwise the unit cannot operate properly.
2. If the abnormal condition is not deleted from the memory, the last abnormal condition is kept memorized.
Does the left lamp of the OPERATION INDICATOR lamp on
the indoor unit blink at the interval of 0.5 seconds?
Blinks: Either indoor or outdoor unit is abnormal. Beep is emit-
ted at the same timing as the blinking of the left lamp of
the OPERATION INDICATOR lamp. 2
Indoor unit is normal.
But the outdoor unit might be abnormal because there are some abnor-
malities that cannot be recalled with this way.
Check if the outdoor unit is abnormal according to the detailed outdoor
unit failure mode recall function. (Refer to 11-2.2)
No
Yes
The cause of abnormality cannot be found because the abnormality does not recur.
Setting up the failure mode recall function
Turn ON the power supply.
<Preparation of the remote controller>
While pressing OPERATION SELECT (MODE) button and TEMP
button on the
remote controller at the same time, press RESET button.
First, release RESET button.
Hold down the other 2 buttons for another 3 seconds. Make sure that the indicators on
the LCD screen shown in the right fi gure are all displayed. Then release the buttons.
Press OPERATE/STOP (ON/OFF)(
MFZ-KJ25/35/50VE
)/ STOP/OPERATE (OFF/ON)
(
MFZ-KJ25/35/50VE2
) button of the remote controller (the set temperature is displayed)
with the remote controller headed towards the indoor unit. 1
Judgment of indoor/outdoor abnormality
Before blinking, does the left lamp of the OPERATION INDI-
CATOR lamp stay ON for 3 seconds?
When it stays ON for 3 seconds (without beep):
The outdoor unit is abnormal.
The indoor unit is abnormal.
Check the blinking pattern, and identify the abnormal point by referring to the
indoor unit failure mode table. (Refer to indoor unit service manual.)
Make sure to check at least 2 consecutive blinking cycles. 2
Releasing the failure mode recall function
Release the failure mode recall function by the following procedures.
Turn OFF the power supply and turn it ON again.
Press RESET button of the remote controller.
Repair the failure parts.
Deleting the memorized abnormal condition
After repairing the unit, recall the failure mode again according to "Setting up the failure mode recall
function" mentioned above.
Press OPERATE/STOP (ON/OFF)(
MFZ-KJ25/35/50VE
)/ STOP/OPERATE (OFF/ON)(
MFZ-
KJ25/35/50VE2
) button of the remote controller (the set temperature is displayed) with the remote
controller headed towards the indoor unit.
Press EMERGENCY OPERATION switch so that the memorized abnormal condition is deleted. 4
Release the failure mode recall function according to "Releasing the failure mode recall function"
mentioned above.
Operational procedure
Yes
(Blinks)
No
(OFF)
1. Regardless of normal or abnormal condition,
a short beep is emitted once the signal is
received.
NOTE:
It takes up to 1 minute to indicate the outdoor unit abnormality.
Even if the OPERATION INDICATOR lamp is not lighting, keep checking
at least 1 minute or longer.
4 The information regarding whether the connected
outdoor unit is a low-standby-power model or a non-low-
standby-power model will also be initialized.
(Default= compatible with a low-standby-power model)
The outdoor unit is abnormal.
Check the blinking pattern, and identify the abnormal point by referring to
the outdoor unit failure mode table. (Refer to 11-2.3)
Make sure to check at least 2 consecutive blinking cycles. 3
AM PM
AM PM
AM PM
AM PM
MFZ-KJ25VE2
MFZ-KJ35VE2
MFZ-KJ50VE2
MFZ-KJ25VE
MFZ-KJ35VE
MFZ-KJ50VE
OBH668E