11
Max. Length
A
Max. Height
difference
B
Indoor
unit
Outdoor unit
MAX. REFRIGERANT PIPING LENGTH and MAX. HEIGHT DIFFERENCE
Model
Refrigerant piping: m
Piping size O.D: mm
Max. Length A
Max. Height difference B
Gas
Liquid
MUFZ-KJ25/35
20
12
9.52
6.35
MUFZ-KJ50
30
15
12.7
6.35
ADDITIONAL REFRIGERANT CHARGE (R410A: g)
Model
Outdoor unit
precharged
Refrigerant piping length (one way)
7 m
8 m
9 m
10 m
11 m
12 m
13 m
14 m
15 m
20 m
MUFZ-KJ25/35
1,100
0
30
60
90
120
150
180
210
240
390
Calculation: X g = 30 g/m × (Refrigerant piping length (m) - 7)
Model
Outdoor unit
precharged
Refrigerant piping length (one way)
7 m
10 m
15 m
20 m
25 m
30 m
MUFZ-KJ50
1,500
0
60
160
260
360
460
Calculation: X g = 20 g/m × (Refrigerant piping length (m) – 7)
OBH667B