J Check of power supply
Is there voltage 208/230 VAC
between the indoor terminal
block S1 and S2?
No
Yes
Replace the indoor
electronic control P.C.
board.
Rectify indoor/outdoor
connecting wire.
Yes
If lights up, OK.
If
fl
ashes, refer to 10-3.
Does the left lamp of the
OPERATION INDICATOR lamp on
the indoor unit light up?
Does LED on the inverter P.C.
board light up or
fl
ash?
(Refer to 10-6.1.)
No
Replace the inverter
P.C. board.
Is there DC voltage 260 - 370 VDC
between DB61 (+) and DB61 (–)
(
MUFZ-KJ09/12
)/294 - 370 VDC
between JP715 (+) and JP30 (–)
(
MUFZ-KJ15/18
) on the inverter P.C.
board? (Refer to 10-6.1.)
No
Check the electric parts in main circuit.
Yes
Yes
No
Disconnect the connector between the
compressor and the power module
(IC700) (
MUFZ-KJ09/12
)/IGBT module
(IC700) (
MUFZ-KJ15/18
).
Turn ON power supply and press
EMERGENCY OPERATION switch.
Inverter P.C. board
(Solder side)
DB61
260 - 370 VDC
MUFZ-KJ09/12
294 -370 VDC
JP30
JP715
MUFZ-KJ15/18
OBH753A