background image

%

urr

Copper pipe

Spare reamer

Pipe cutter

3-2. FLARING WORK

1) Cut the copper pipe correctly with pipe cutter

 (Fig

 1, 2)

2) Completely remove all 

E

urrs from the cut cross section 

of pipe

 (Fig

 3)

‡

  Put the end of the copper pipe to downward direction 

as you remove 

E

urrs in order to avoid to let 

E

urrs drop 

in the piping

3) Remove 

À

are nuts attached to indoor and outdoor units, 

then put them on pipe having completed 

E

urr removal

 

(Not possi

E

le to put them on after 

À

aring work

4) Flaring work (Fig

 4, 5)

 Firmly hold copper pipe in the 

dimension shown in the ta

E

le

 Select A mm from the ta

E

le 

according to the tool you use

5) Check 

‡

 Compare the 

À

ared work with Fig

 6

‡

 If 

À

are is noted to 

E

e defective, cut off the 

À

ared sec

tion and do 

À

aring work again

3-3. PIPE CONNECTION

‡

 Fasten 

À

are nut with a torque wrench as speci

¿

ed in the ta

E

le

‡

  When fastened too tight, 

À

are nut may 

E

reak after a long period and cause refrigerant 

leakage

‡

 

%

e sure to wrap insulation around the piping

 

'

irect contact with the 

E

are piping may 

result in 

E

urns or frost

E

ite

Indoor unit connection

Connect 

E

oth liquid and gas pipings to indoor unit

‡

  Apply a thin coat of refrigeration oil (J) on the 

À

ared ends of the pipes

 

'

o not apply 

refrigeration oil on screw threads

 Excessive tightening torque will result in damage on 

the screw

‡

 For 

connection, 

¿

rst align the center, then tighten the 

¿

rst 3 to 4 turns of 

À

are nut

‡

  Use tightening torque ta

E

le a

E

ove as a guideline for indoor unit side union joint section, 

and tighten using two wrenches

 Excessive tightening damages the 

À

are section

Pipe diameter 

(mm)

Nut 

(mm)

A (mm)

Tightening torque

Clutch 

type tool 

for R32, 

R410A

Clutch type 

tool for 

R22

Wing nut 

type tool for 

R22

N

‡

m

kgf

‡

cm

ø6

35 (1/4

´

)

17

0 to 0

5

1

0 to 1

5

1

5 to 2

0

13

7 to 

17

7

140 to 180

ø9

52 (3/8

´

)

22

34

3 to 

41

2

350 to 420

ø12

7 (1/2

´

)

26

2

0 to 2

5

49

0 to 

56

4

500 to 575

ø15

88 (5/8

´

)

29

73

5 to 

78

4

750 to 800

Copper 
pipe

Good

Tilted Uneven 

%

urred

No good

Fig

 1

Fig

 2

Clutch type

Flaring tool

Fig

 4

Fig

 3

Smooth all 
around

Even length 
all around

Inside is shin

ing without any 
scratches

Flare nut

'

ie

Fig

 

5

Fig

 6

3.  OUTDOOR UNIT INSTALLATION

Copper pipe

Wing nut type

 WARNING

When installing the unit, securely connect the refrigerant 
pipes before starting the compressor.

3-1. CONNECTING WIRES FOR OUTDOOR UNIT

1) Open the service panel

2) Loosen terminal screw, and connect indoor/outdoor unit connecting wire (A) from the 

indoor unit correctly on the terminal 

E

lock

 

%

e careful not to make mis

wiring

 Fix the wire 

to the terminal 

E

lock securely so that no part of its core is appeared, and no external 

force is conveyed to the connecting section of the terminal 

E

lock

 

3) Firmly tighten the terminal screws to prevent them from loosening

 After tightening, pull 

the wires lightly to con

¿

rm that they do not move

4) Connect power supply cord (K)

5) Fix indoor/outdoor unit connecting wire (A) and power supply cord (K) with the cord clamp

6) Close the service panel securely

‡

  Make earth wire a little longer than others

 (More than 100 mm)

‡

  For future servicing, give extra length to the connecting wires

‡

 

%

e sure to attach each screw to its correspondent terminal when securing the cord 

and/or the wire to the terminal 

E

lock

35 mm

15 mm

Lead wire

Power supply cord (K)

Outdoor unit connection

Connect pipes to stop valve pipe joint of the outdoor unit in the 
same manner applied for indoor unit

‡

  For tightening, use a torque wrench or spanner and use the 

same tightening torque applied for indoor unit

3-4. INSULATION AND TAPING

1) Cover piping joints with pipe cover

2) For outdoor unit side, surely insulate every piping including valves

3) Using piping tape (G), apply taping starting from the entry of outdoor unit

‡

  Stop the end of piping tape (G) with tape (with adhesive agent attached)

‡

  When piping have to 

E

e arranged through a

E

ove ceiling, closet or where the tempera

ture and humidity are high, wind additional commercially sold insulation to prevent 
condensation

Terminal 

E

lock

Terminal 

E

lock

Cord clamp

Cord clamp

Power supply 
cord (K)

Power supply cord (K)

Terminal 

E

lock

Indoor/outdoor 
unit connect

ing wire (A)

Indoor/outdoor 
unit connecting 
wire (A)

Always 

¿

x the power 

supply cord on this side

Insert the end of the ca

E

le 

tie in the rectangle hole

<LN25, 35>

<LN50>

<LN50

+

Z, 60>

 WARNING

To avoid risk of 

¿

re, 

À

are connection should be installed outdoors.

Reusable mechanical connectors and 

À

ared 

M

oints are not allowed indoors.

When connecting the refrigerant piping by brazing, rather than using 

À

are con-

nections, complete all brazing prior to connecting indoor unit to outdoor unit.

Summary of Contents for MSZ-LN25VG

Page 1: ...ply plug replace it Attach the electrical cover to the indoor unit and the service panel to the outdoor unit securely If the electrical cover of the indoor unit and or the service panel of the outdoor unit are not attached securely it could result in a re or an electric shock due to dust water etc When installing relocating or servicing the unit make sure that no substance other than the speci ed ...

Page 2: ...nd If the outdoor unit is exposed to a wind during defrosting the defrosting time will Ee longer Where airÀow is good and dustless Where rain or direct sunlight can Ee avoided as much as possiEle Where neighEours are not annoyed Ey operation sound or hot or cool air Where rigid wall or support is availaEle to prevent the increase of operation sound or viEration Where there is no risk of comEustiEl...

Page 3: ...r purifying device 1 Outdoor unit 12 rain socket VG type only 1 Air inlet LN25 35 50 50 Z 60 LN25 35 50 50 Z 60 3 When any 2 sides of left right and rear of unit are clear 4 The manufacturing year and month is indicated on the spec name plate 60 mm or more 150 mm or more for left and left Eack piping using spacer 101 mm or more 111 mm or more 350 mm or more Note Install the unit horizontally o not...

Page 4: ... pipe Fig 3 o not make drain piping as shown Eelow o not raise Accumulated drain water Air Waving Water leakage Water leakage Water leakage Tip of drain hose dipped in water itch At least 50 mm gap ownward slope rain hose Soft hose I 15 mm rain hose ard vinyl chloride pipe I 30 mm Insert securely ifferent diameter joint 70 cm or more Fig 1 Fig 2 Fig 3 For future servicing give extra length to the ...

Page 5: ...e 1 part aEout 90 degrees around the hinge point you have just created to put the parts together 3 Press the Ease of portion with the mark to snap into place When changing the part disassemEle Ey moving the part in a reverse direction The parts that were not used may Ee necessary in the future if the air conditioner is relocated so ask customers to keep those parts 4 Attach the assemEled corner Eo...

Page 6: ...he unit securely connect the refrigerant pipes before starting the compressor 3 1 CONNECTING WIRES FOR OUTDOOR UNIT 1 Open the service panel 2 Loosen terminal screw and connect indoor outdoor unit connecting wire A from the indoor unit correctly on the terminal Elock e careful not to make mis wiring Fix the wire to the terminal Elock securely so that no part of its core is appeared and no external...

Page 7: ...he unit with the E O SW or the remote controller Eefore turning off the power supply Not doing so will cause the unit to start operation automatically when power supply is resumed To the user After installing the unit make sure to explain the user aEout auto restart function If auto restart function is unnecessary it can Ee deactivated Consult the service representative to deactivate the function ...

Page 8: ... the pressure gauge shows 0 05 to 0 MPa Gauge approx 0 5 to 0 kgf cmð 6 Stop the emergency COOL operation Press the E O SW several times until all LE lamps turn off Refer to operating instruc tions for details 6 RELOCATION AND MAINTENANCE When pumping down the refrigerant stop the compressor before disconnecting the refrigerant pipes The compressor may burst if air etc get into it WARNING 6 2 REMO...

Reviews: