background image

Job Name:

Location:

Date:

Purchaser:

Engineer:

Submitted to:

For        Reference      Approval     Construction

System Designation:

Schedule No.:

© 2011 MITSUBISHI ELECTRIC & ELECTRONICS, INC.

Cooling Capacity*

. . . . . . . . . . . . . . . . . . . . . . . . . . . .12,000 Btu/h

Heating Capacity*

. . . . . . . . . . . . . . . . . . . . . . . . . . . .14,400 Btu/h

Rating Conditions (Cooling) - Indoor: 80ºF (27ºC) DB, 67ºF (19ºC) WB; Outdoor: 95ºF 

(35ºC) DB, 75ºF (24ºC) WB.

(Heating at 47ºF) - Indoor: 70ºF (21ºC) DB, 60ºF (16ºC) WB; Outdoor: 47ºF (8ºC) DB, 43ºF (6ºC) WB.

(For data on specific indoor units [all ducted, all non-ducted, and both ducted 

and non-ducted] combinations, see the MXZ-B Technical and Service Manual.)

Electrical Requirements

Power Supply . . . . . . . . . . . . . . . . . . . . 208 / 230V, 1-Phase, 60 Hz

MCA  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 A

.

SUBMITTAL DATA: MSZ-GE12NA-8

. . . . . . . 12,000 BTU/H WALL-MOUNTED INDOOR UNIT FOR MXZ-B MULTI-ZONE HEAT-PUMP SYSTEMS

Indoor Unit: MSZ-GE12NA-8

MXZ-B SERIES HEAT-PUMP OUTDOOR UNITS

SEZ and PEAD-A24AA4

MSZ-GE

MXZ-B MULTI-ZONE SYSTEMS CAN INCLUDE:

• Ducted Indoor Units: 

 

  

SEZ-KD09,12,15,18NA4, PEAD-A24AA4

• Nonducted Indoor Units: 

 

  

MSZ-GE06,09,12,15NA,18NA-8,24NA,  

  MSZ-FE09,12NA-8,18NA, MFZ-KA09,12,18NA,  

  PCA-A24KA4, SLZ-KA09,12,15NA, and  

  PLA-A12,18,24BA4

• A combination of both Ducted and Nonducted

 

  Indoor Units

Refer to the separate submittal forms for the  

MSZ-GE, MSZ-FE, MFZ-KA, SEZ-KD, SLZ-KA, 

PEAD, PCA, PLA Indoor Units, and MXZ Outdoor 

Units.

MULTI-ZONE OUTDOOR UNIT

MSZ-FE

MFZ-KA

PCA-A24KA4

SLZ and PLA-A12,18,24BA4

OPTIONAL ACCESSORIES

Indoor Unit

 

Condensate Pump (230V; SI3100-230)

Controller Options

 

Wireless Remote Controller Kit (MHK1) with Remote Controller 

(MRCH1), Wireless Receiver (MIFH1), and cable (MRC1)*

 

Setback down to 50°F when used with MRCH1 Remote 

 

Portable Central Controller (MCCH1; for use with Wireless Remote 

Controller Kit MHK1)*

 

Outdoor Air Sensor (MOS1; for use with Remote Controller (MRCH1),  

Wireless Remote Controller Kit (MHK1) and Portable Central 

Controller (MCCH1)*Controller (MCCH1)*

*See Submittal for information on each option.

 

Wall-mounted Wired Remote Controller  

(PAR-21MAA requires MAC-397IF) 

 

MA Contact Terminal Interface (MAC-397IF)

 

M-NET Control Adapter (MAC-399IF)

 

Remote Temperature Sensor (M21-JKO-307)

 

Lockdown Bracket for Hand-held Controller (RCMKP1CB)

GENERAL FEATURES

• 

Wall-mounted indoor unit

•  Standard Hybrid Catechin Prefilter is included with indoor unit

• 

Quiet operation

• 

Choice of fan speeds: Quiet, Low, Medium, High, and Super High  

Auto fan speed control also included

• 

Hand-held Wireless Remote Controller

• 

Indoor unit powered from outdoor unit using A-Control

• 

Auto restart following a power outage

• 

Base heater is available as an option

• 

Anti-allergy Enzyme Filter

•  Limited warranty: five years on parts and defects and seven years

 

on the compressor

Voltage

Indoor - Outdoor S1-S2  . . . . . . . . . . . . . . . . . . . . . . . . AC 208 / 230V

Indoor - Outdoor S2-S3  . . . . . . . . . . . . . . . . . . . . . . . . . . . DC 12-24V

Fan Motor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0.76 F.L.A

Airflow (Quiet -

 Lo - Med - Hi - Super Hi)

   Cooling . . . . . . . . . . . . . . . . . . . . . . . 145 - 170 - 237 - 321 - 399 Dry CFM

109 - 134 - 201 - 286 - 364 Wet CFM

   Heating  . . . . . . . . . . . . . . . . . . . . . 145 - 170 - 237 - 321 - 406 CFM

Sound Pressure Level (Quiet -

 Lo - Med - Hi - Super Hi)

   Cooling  . . . . . . . . . . . . . . . . . . . . . . . . . 19 - 22 - 30 - 37 - 45 dB(A)

   Heating  . . . . . . . . . . . . . . . . . . . . . . . . . 19 - 22 - 30 - 37 - 43 dB(A)

DIMENSIONS

UNIT INCHES / MM

31-7/16 / 799

D

9-1/8 / 232

H

11-5/8 / 295

Weight. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .22 lbs. / 10 kg

External Finish  . . . . . . . . . . . . . . . . . . . . . . Munsell No. 1.0Y 9.2 / 0.2

Field Drainpipe Size O.D.. . . . . . . . . . . . . . . . . . . . . . 5/8" / 15.88 mm

Refrigerant Type. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .R410A

Refrigerant Pipe Size O.D.

   Gas Side  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3/8" / 9.52 mm

   Liquid Side. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1/4" / 6.35 mm

Connection Method  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Flared