1-2. DRY mode of “I FEEL CONTROL”

The system for dry operation uses the same refrigerant circuit as the cooling circuit.
The compressor and the indoor fan are controlled by the room temperature.
NOTE :  By such controls, indoor flow amounts will be reduced in order to lower humidity without much room

temperature decrease.

2. Indoor fan speed control

Indoor fan operates at the set speed by FAN SPEED CONTROL button .
In Auto fan speed becomes Low.

3. The operation of the compressor and indoor / outdoor fan

Compressor operates by room temperature control and time control.
Set temperature is controlled to fall 2°C from initial room temperature.
Indoor fan and outdoor fan operate in the same cycle as the compressor.

When the room temperature is 23°C or over:

When the thermostat is ON, the compressor repeats 8 minutes ON and 3 minutes OFF.
When the thermostat is OFF, the compressor repeats 4 minutes OFF and 1 minute ON.

When the room temperature is under 23°C.
When the thermostat is ON, the compressor repeats 2 minutes ON and 3 minutes OFF.
When the thermostat is OFF, the compressor repeats 4 minutes OFF and 1 minute ON.

Compressor
Outdoor fan

OFF

ON

(Continuously at set speed)

Indoor fan 

ON

ON

OFF

Operation chart

Example

Operation time chart

Example

Thermostat

Indoor fan

Outdoor fan 
Compressor

ON

8 min.

1 min.

3 min.

4 min.

ON

OFF

OFF

OFF

OFF

OFF

OFF

OFF

OFF

ON

ON

ON

ON

ON

ON

4. Coil frost prevention

• The operation is the same as coil frost prevention during COOL mode of “I FEEL CONTROL”.
• Indoor fan operates at the set speed and the compressor stops for 5 minutes because coil frost prevention has priority.

When coil frost prevention works while indoor fan’s stop and compressor’s stop, indoor fan operates at set speed.

② 

Time control
When the three conditions as follows have been satisfied for 1 hour and 45 minutes, compressor stops for 3 minutes.
a. Compressor has been continuously operating.
b. Indoor fan speed is Low or Med..
c. Room temperature is below 26°C.
When compressor stops, the value of its duration measure is reset. When it restarts, its duration measure starts all over
again.
Duration measure temporarily stops when the indoor fan speed becomes High or when room temperature exceeds 26

:

.

However, it begins to function again when both conditions above, b. and c. are satisfied.

-0.3

:

0.3

:

1. Thermostat control

Thermostat is ON or OFF by difference between room temperature and set temperature

Initial temperature difference                   Thermostat

Room temperature minus set temperature : 0.3 

:

or more················································ON

Room temperature minus set temperature : less than -0.3 

:

············································OFF

Set temperature

Difference between room
temperature and set tem-
perature during operation

OBT10.qxp  05.5.11 11:26 AM  Page 4

Summary of Contents for MS-A08ND

Page 1: ... A12ND MS A15ND WH MU A15ND C1 C1 C1 C1 C1 C1 C1 C1 No OBT10 SPLIT TYPE AIR CONDITIONERS CONTENTS MICROPROCESSOR CONTROL 1 I FEEL CONTROL OPERATION 2 2 COOL OPERATION 5 3 DRY OPERATION 5 4 FAN OPERATION 5 5 FAN MOTOR CONTROL 5 6 AUTO VANE OPERATION 5 7 TIMER OPERATION 7 8 EMERGENCY TEST OPERATION 7 TM ...

Page 2: ...peration state INDOOR UNIT DISPLAY SECTION The following indication applies regardless of shape of the indicator Once the mode is fixed the mode does not change by room temperature afterwards Under ON TIMER operation the mode is deter mined according to the room temperature at set time the operation starts When the system is stopped by the remote controller and restarted within 2 hours in I FEEL C...

Page 3: ...room temperature the frequency of pressing TOO COOL or TOO WARM button and the user s preference to heat or cold So this is called Fuzzy control and works only in I FEEL CONTROL mode In DRY mode of I FEEL CONTROL the set temperature doesn t change To raise the set temperature 1 2 degrees To lower the set temperature 1 2 degrees TOO COOL TOO WARM 1 deg 1 7 deg 3 deg Difference between room temperat...

Page 4: ...Operation time chart Example Thermostat Indoor fan Outdoor fan Compressor ON 8 min 1 min 3 min 4 min ON OFF OFF OFF OFF OFF OFF OFF OFF ON ON ON ON ON ON 4 Coil frost prevention The operation is the same as coil frost prevention during COOL mode of I FEEL CONTROL Indoor fan operates at the set speed and the compressor stops for 5 minutes because coil frost prevention has priority When coil frost p...

Page 5: ... work The other operations are same as DRY mode of I FEEL CONTROL 4 DRY operation will not work when the room temperature is 13 C or below 4 FAN OPERATION 1 Press OPERATE STOP ON OFF button OPERATION INDICATOR lamp of the indoor unit turns on with a beep tone 2 Select FAN mode with OPERATION SELECT button 3 Select the desired fan speed When AUTO it becomes Low Only indoor fan operates Outdoor unit...

Page 6: ... is pressed in COOL mode set temperature is automatically set 2 higher than that in COOL mode Also the horizontal vane swings in a cycle which fits the temperature of indoor heat exchanger RT12 SWING operation makes you feel cooler than set temperature So even though the set temperature is higher than that in COOL mode the air conditioner can keep comfort As a result energy can be saved ECONO COOL...

Page 7: ... can not be set at the same time TIME SELECT Example 1 Setting to stop the air conditioner 3 hours later 1 Press button to select OFF TIMER 2 Press button to set the 3h TIME SELECT 3 h 7 h Example 2 Setting to operate the air conditioner 7 hours later 1 Press button to select ON TIMER 2 Press button to set the 7h TIME SELECT 2 Cancel Press button until OFF TIMER and ON TIMER are not displayed SELE...

Page 8: ...2 3 MARUNOUCHI CHIYODA KU TOKYO100 8310 JAPAN C C Copyright 2005 MITSUBISHI ELECTRIC ENGINEERING CO LTD Distributed in May 2005 No OBT10 7 Made in Japan New publication effective May 2005 Specifications subject to change without notice TM ...

Reviews: