background image

16

8. Electrical work

8.1. Power supply

Electrical specification

Input capacity Main Switch/Fuse (A)

Power supply

(1 phase ~/N, 230V, 50Hz) 

SEZ-M25 SEZ-M35 SEZ-M50 SEZ-M60 SEZ-M71

10

10

20

20

20

 Warning:

• 

The compressor will not operate unless the power supply phase 

connection is correct.

• 

Grounding protection with a no-fuse breaker (earth leakage breaker [ELB]) 

is usually installed for 

.

• 

The connection wiring between the outdoor and indoor units can be 

extended up to a maximum of 50 meters, and the total extension including 

the crossover wiring between rooms is a maximum of 80 m.

A switch with at least 3 mm contact separation in each pole shall be provided 

by the air conditioner installation.

* Label each breaker according to purpose (heater, unit etc.).

[Fig. 8-1] (P.5)

Indoor unit

Outdoor unit

Signal receiving unit

Wireless remote controller

Main switch/fuse

Grounding

8.2. Indoor wire connection

Work procedure

1. Remove 2 screws to detach the electric component cover.

2.  Route each cable through the wiring intake into the electric component box. 

(Procure power cable and in-out connecting cable locally and use remote control 

cable supplied with the unit.)

3.  Securely connect the power cable and the in-out connecting cable and the 

remote control cable to the terminal blocks.

4.  Secure the cables with clamps inside the electric component box.

5.  Attach the electric component cover as it was.

• 

Fix power supply cable and indoor/outdoor cable to control box by using buffer 

bushing for tensile force. (PG connection or the like.)

 Warning:

• 

Attach the electrical part cover securely. If it is attached incorrectly, it could 

result in a fire, electric shock due to dust, water, etc.

•  Use the specified indoor/outdoor unit connecting wire to connect the 

indoor and outdoor units and fix the wire to the terminal bed securely so 

that no stress is applied to the connecting section of the terminal bed.  

Incomplete connection or fixing of the wire could result in a fire.

[Fig. 8-2-1] (P.5)

Screw holding cover (2 pcs)

Cover

[Fig. 8-2-2] (P.5)

Terminal bed box

Knockout hole

Remove

[Fig. 8-2-3] (P.5)

Use PG bushing to keep the weight of the cable and external force from being applied to 

the power supply terminal connector. Use a cable tie to secure the cable.

Indoor/outdoor unit connecting wire

Tensile force

Use ordinary bushing

Signal receiving unit wiring

[Fig. 8-2-4] (P.5)

Terminal bed for power source and indoor transmission

Indoor/outdoor unit connecting wire

Connecting the signal receiving unit 

Connect the signal receiving unit to the CN90 (Connect to the wireless remote controller 

board) on the indoor unit using the supplied remote controller wire. Connect the signal 

receiving units to all the indoor units.

[Fig. 8-3] (P.6)

Indoor terminal block

Earth wire (green/yellow)

Indoor/outdoor unit connecting wire 3-core 1.5 mm

2

 or more

Outdoor terminal block

Power supply cord

Indoor controller board

Connecting cable

Cable 3-core 1.5 mm

2

, in conformity with Design 245 IEC 57.

Indoor terminal block

Outdoor terminal block

Always install an earth wire (1-core 1.5 mm

2

) longer than other cables

Signal receiving unit cable (accessory) (wire length : 5 m)

Signal receiving unit

Power supply cord

• 

Perform wiring as shown in [Fig. 8-3] (P.6). (Procure the cable locally.)  

Make sure to use cables of the correct polarity only.

• 

Connect the terminal blocks as shown in [Fig. 8-3] (P.6).

 Caution:

• 

Use care not to make mis-wiring. 

• 

Firmly tighten the terminal screws to prevent them from loosening.

•  After tightening, pull the wires lightly to confirm that they do not move.

8.3. Remote controller

8.3.1. For wireless remote controller

1) Installation area

• 

Area in which the remote controller is not exposed to direct sunshine.

• 

Area in which there is no nearby heating source.

• 

Area in which the remote controller is not exposed to cold (or hot) winds.

• 

Area in which the remote controller can be operated easily.

• 

Area in which the remote controller is beyond the reach of children.

2) Installation method [Fig. 8-4] (P.6)

  Attach the remote controller holder to the desired location using two tapping 

screws.

 Place the lower end of the controller into the holder.

Remote controller

Wall

Display panel

Receiver

• 

The signal can travel up to approximately 7 meters (in a straight line) within 45 

degrees to both right and left of the center line of the receiver.

3) Setting the Model No.

  Insert batteries.

  Press the SET button with something sharp at the end. 

MODEL SELECT

 blinks and Model No. is lighted.

 Press the temp 

   button to set the Model No.

  Press the SET button with something sharp at the end. 

MODEL SELECT

 and Model No. are lighted for three seconds, then turned off.

Indoor

Outdoor

Model No.

SEZ

heat pump models

026

cooling only models

058

8.3.2. Signal Receiving Unit

1) Sample system connection 

[Fig. 8-5] (P.6)

Only the wiring from the signal receiving unit and between the remote controllers is 

shown in Fig. 8-5. The wiring differs depending on the unit to be connected or the 

system to be used. 

For details on restrictions, refer to the installation manual or the service handbook 

that came with the unit.

1. Connecting to Mr. SLIM air conditioner

(1) Standard 1:1

  Connecting the signal receiving unit 

Connect the signal receiving unit to the CN90 (Connect to the wireless remote 

controller board) on the indoor unit using the supplied remote controller wire. 

Connect the signal receiving units to all the indoor units.

2) Setting the pair number switch

[Fig. 8-6] (P.6)

1. Setting method

Assign the same pair number to the wireless remote controller as that of the 

indoor unit. If not doing so, the remote controller cannot be operated. Refer to 

the installation manual that came with the wireless remote controller for how to 

set pair numbers of wireless remote controllers.

Position of daisy wire on the controller circuit board on the indoor unit.

Summary of Contents for Mr. Slim SEZ-M25DAL

Page 1: ...nditioners INDOOR UNIT SEZ M25 M35 M50 M60 M71DAL INSTALLATION MANUAL For safe and correct use please read this installation manual thoroughly before installing the air conditioner unit FOR INSTALLER English ORIGINAL ...

Page 2: ...ess door 1 450 mm x 450 mm Ⓕ Maintenance access space Ⓖ Supply air mm Model P Q R S SEZ M25 700 50 150 800 1300 SEZ M35 50 900 150 250 1000 1500 SEZ M60 71 1100 250 350 1200 1700 777 S 50 50 P 700 Min 300 mm Viewed from the direction of the arrow B Ⓖ Ⓗ Ⓚ Ⓕ Ⓐ Ⓘ Fig 3 1 5 Ⓖ Ⓗ Ⓘ Ⓕ 700 450 475 450 Q 50 150 450 450 100 200 Min 300 mm Viewed from the direction of the arrow A P Ⓔ Ⓐ Ⓓ Fig 3 1 2 Unit mm Mi...

Page 3: ...3 4 Fig 4 1 5 Y X L W Ⓐ Z Ⓐ Center of gravity 5 1 Ⓒ Ⓓ Ⓒ Ⓔ Ⓓ Ⓒ Nuts field supply Ⓓ Washers accessory Ⓔ M10 hanging bolt field supply Fig 5 2 Ⓑ Ⓐ Ⓐ Unit body Ⓑ Lifting machine Fig 5 1 ...

Page 4: ... 3 6 5 Ⓓ Ⓔ Ⓗ Ⓖ Ⓘ Ⓕ Ⓑ Ⓒ 5 25 Ⓐ Ⓐ Indoor unit Ⓑ Pipe cover short accessory Ⓒ Tie band accessory Ⓓ Band fixing part Ⓔ Insertion margin Ⓕ Drain hose accessory Ⓖ Drain pipe O D ø32 PVC TUBE field supply Ⓗ Insulating material field supply Ⓘ Max 145 5 mm Fig 6 11 Ⓐ Pipe cover small accessory Ⓑ Caution Pull out the thermal insulation on the refrigerant piping at the site insert the flare nut to flare the ...

Page 5: ... ordinary bushing Ⓘ Signal receiving unit wiring Ⓙ Terminal bed for power source and indoor transmission Ⓚ Indoor outdoor unit connecting wire Ⓛ Connecting the signal receiving unit Connect the signal receiving unit to the CN90 Connect to the wireless remote controller board on the indoor unit using the supplied remote controller wire Connect the signal receiving units to all the indoor units Ⓐ Te...

Page 6: ...ord Outdoor terminal block Always install an earth wire 1 core 1 5 mm2 longer than other cables Signal receiving unit cable accessory wire length 5 m Signal receiving unit Power supply cord Ⓕ Indoor controller board 8 8 2 J41 J42 JP1 JP2 JP3 CN90 CN4F CN44 CN20 Red CNMF SW1 SW2 CN32 CN41 CN51 ON OFF SWE CN2L CN22 Blue CNP Blue CN3C Blue CN01 Black CN90 Connector for remote controller wire connecti...

Page 7: ...r wire Fig 8 13 Ⓐ Insert the minus screwdriver toward the arrow pointed and wrench it to remove the cover A flat screwdriver whose width of blade is between 4 and 7 mm 5 32 9 32 inch must be used Fig 8 14 Ⓐ Indoor unit Hang the cover to the upper hooks 2 places Mount the cover to the lower case Ⓐ Cross section of upper hooks Fig 8 10 Fig 8 15 Ⓗ Ⓙ Ⓘ When using the switch box When installing directl...

Page 8: ...nstalling the lower case directly on the wall or the ceiling use wood screws Insert the minus screwdriver toward the arrow pointed and wrench it to remove the cover A flat screwdriver whose width of blade is between 4 and 7 mm 5 32 9 32 inch must be used Fig 8 19 Ⓐ Hang the cover to the upper hooks 2 places Mount the cover to the lower case Ⓐ Cross section of upper hooks Ⓐ Hour button Ⓑ Minute but...

Page 9: ...lve Ⓕ Outdoor unit Ⓖ Refrigerant gas cylinder operating valve Ⓗ Refrigerant gas cylinder for R32 R410A with siphon Ⓘ Refrigerant liquid Ⓙ Electronic scale for refrigerant charging Ⓚ Charge hose for R32 R410A Ⓛ Gauge manifold valve for R32 R410A Ⓜ Service port 10 1 ON OFF TEMP FAN VANE TEST RUN AUTO STOP AUTO START h min LOUVER MODE CHECK RESET SET CLOCK TESTRUN Ⓑ Ⓐ Ⓒ Ⓓ ...

Page 10: ...efective insulation exceeding the permissible current etc Check that the refrigerant gas does not leak after installation has completed Perform the installation securely referring to the installation manual Incomplete installation could cause a personal injury due to fire electric shock the unit falling or leakage of water Perform electrical work according to the installation manual and be sure to...

Page 11: ...all room or similar location make sure that there are no refrigerant leaks before performing the work If refrigerant leaks and accumulates it may ignite or poisonous gases may be released For installation and relocation work follow the instructions in the installation manual and use tools and pipe components specifically made for using with refrigerant specified in the outdoor unit installation ma...

Page 12: ...re high humidity due point above 26 C due condensation may be produced in the indoor unit When operating the units in this condition add insulation material 10 20 mm to the entire surface of the indoor unit to avoid due condensation 3 1 Install the indoor unit on a ceiling strong enough to sustain its weight Secure enough access space to allow for the maintenance inspection and replacement of the ...

Page 13: ...ing boards Center of gravity and Product Weight Model name W L X Y Z Product Weight kg SEZ M25 625 752 263 351 106 17 5 SEZ M35 625 952 286 448 104 21 SEZ M50 625 952 280 437 104 22 SEZ M60 625 1152 285 527 104 25 5 SEZ M71 625 1152 285 527 104 25 5 5 Installing the unit 5 1 Hanging the unit body Bring the indoor unit to an installation site as it is packed To hang the indoor unit use a lifting ma...

Page 14: ... flare nut included with this indoor unit 6 2 4 Flaring work Fig 6 6 P 4 ⓐ Flaring tool ⓑ Die ⓒ Copper tube ⓓ Flare nut ⓔ Yoke Carry out flaring work using flaring tool as shown below Pipe diameter mm Dimension A mm B 0 0 4 mm When the tool for R32 R410A is used Clutch type 6 35 0 0 5 9 1 9 52 0 0 5 13 2 12 7 0 0 5 16 6 15 88 0 0 5 19 7 Firmly hold copper tube in a die in the dimension shown in th...

Page 15: ...Downward slope 1 100 or more Ⓑ Connection dia R1 external thread Ⓒ Indoor unit Ⓓ Collective piping Ⓔ Maximize this length to approx 10 cm Ensure that the drain piping is downward pitch of more than 1 100 to the outdoor discharge side Do not provide any trap or irregularity on the way Ensure that any cross wise drain piping is less than 20 m excluding the difference of elevation If the drain piping...

Page 16: ...t connecting wire 3 core 1 5 mm2 or more Ⓓ Outdoor terminal block Ⓔ Power supply cord Ⓕ Indoor controller board Connecting cable Cable 3 core 1 5 mm2 in conformity with Design 245 IEC 57 Indoor terminal block Outdoor terminal block Always install an earth wire 1 core 1 5 mm2 longer than other cables Signal receiving unit cable accessory wire length 5 m Signal receiving unit Power supply cord Perfo...

Page 17: ... position depending on the indoor unit model Connect the remote controller wire securely to the order wire To pass the remote controller wire through the conduit follow the procedure as shown in Fig 8 12 Fig 8 12 P 7 Ⓐ Fix tightly with tape Ⓒ Order wire Ⓑ Remote controller wire Note The point where the remote controller wire is connected differs depending on the indoor unit model Take into account...

Page 18: ...ntroller s internal sensor 3 LOSSNAY connectivity Not Supported 03 1 〇 Supported indoor unit is not equipped with outdoor air intake 2 Supported indoor unit is equipped with outdoor air intake 3 Function table 2 Select unit numbers 01 to 04 or all units AL wired remote controller 07 wireless remote controller Mode Settings Mode no Setting no Initial setting Check Filter sign 100 Hr 07 1 2500 Hr 2 ...

Page 19: ...rol system error memory error etc 14 PL Refrigerant circuit abnormal No sound No corresponding Output pattern B Errors detected by unit other than indoor unit outdoor unit etc Wireless remote controller Symptom Remark Beeper sounds OPERATION INDICATOR lamp flashes Number of times 1 Indoor outdoor unit communication error Transmitting error Outdoor unit For details check the LED display of the outd...

Page 20: ... between the indoor and outdoor units Make sure that this LED is always blinking 9 3 AUTO RESTART FUNCTION Indoor controller board This model is equipped with the AUTO RESTART FUNCTION When the indoor unit is controlled with the remote controller the operation mode set temperature and the fan speed are memorized by the indoor controller board The auto restart function sets to work the moment the p...

Page 21: ......

Page 22: ...owing EU regulations Low Voltage Directive 2014 35 EU Electromagnetic Compatibility Directive 2014 30 EU Energy related Products Directive 2009 125 EC Machinery Directive 2006 42 EC This product is designed and intended for use in the residential commercial and light industrial environment HEAD OFFICE TOKYO BLDG 2 7 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN ...

Reviews: