background image

Job Name: 

Location: 

Date:

Purchaser: 

Engineer:

Submitted to: 

For       Reference       Approval       Construction

System Designation: 

Schedule No.: 

  

Cooling*

Rated Capacity. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17,200 Btu/h

Total Input. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .90 W

Current . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0.74 A

Heating*

Rated Capacity. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20,100 Btu/h

Total Input. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .70 W

Current . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0.63 A

Rating  Conditions  (Cooling)  -  Indoor:  80ºF  (27ºC)  DB  /  67ºF  (19ºC)  WB.

Outdoor: 95ºF (35ºC) DB / 75ºF (24ºC) WB.

(Heating) - Indoor: 70ºF (21ºC) DB / 60ºF (16ºC) WB. Outdoor: 47ºF (8ºC) DB / 

43ºF (6ºC) WB. 

(For data on specific indoor units [all ducted, all non-ducted, and both ducted 

and non-ducted] combinations, see the MXZ Technical and Service Manual.)

Electrical Requirements

Power Supply . . . . . . . . . . . . . . . . . . . . 208 / 230V, 1-Phase, 60 Hz

MCA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 A

Voltage

Indoor - Outdoor S1-S2  . . . . . . . . . . . . . . . . . . . . . . AC 208 / 230V

Indoor - Outdoor S2-S3  . . . . . . . . . . . . . . . . . . . . . . . . . . . .DC 24V

Indoor Unit: SEZ-KD18NA

Fan

Type x Quantity. . . . . . . . . . . . . . . . . . . . . . . . . . . . Sirocco Fan x 4

Motor  . . . . . . . . . . . . . . . . . . . . . Direct-driven DC Brushless Motor

Motor Output. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .96  W

Airflow (Lo - Med - Hi). . . . . . . . . . . . . . . . . . . 423 - 529 - 635 CFM

Air Filter  . . . . . . . . . . . . . . . . . . . . . . . . Polypropylene  Honeycomb

External Static Pressure. . . . . . . . . . . 0.02 - 0.06 - 0.14 - 0.20

"

WG

Sound Pressure Level (Lo - Med - Hi) . . . . . . . . .30 - 34 - 38 dB(A)

DIMENSIONS

UNIT INCHES / MM

46-7/8 / 1,190

D

27-9/16 / 700

H

7-7/8 / 200

Weight. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  60 lbs. / 27 kg 

Field Drainpipe Size O.D.. . . . . . . . . . . . . . . . . . . . . 1-1/4" / 32 mm

Wall-mounted Remote Controller . . . . . . . . . . . . . . . . . PAR-21MAA 

(See Data Submittal Sheet)

Refrigerant Type. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . R410A

Refrigerant Pipe Size O.D.

   Gas Side . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1/2" / 12.7 mm

   Liquid Side. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1/4" / 6.35 mm

Connection Method  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Flared

SUbMITTal DaTa: SEZ-KD18Na

         

18,000 bTU/H HORIZONTal-DUCTED INDOOR UNIT FOR MXZ MUlTI-ZONE HEaT-pUMp SYSTEMS

Remote Controller: PAR-21MAA

OpTIONal aCCESSORIES

• M-NET Control Adapter (MAC-399IF)

• External Heat Adapter (PAC-YU25HT)

• CN24 Relay Kit (CN24RELAY-KIT-CM)

• Three-pole Disconnect Switch (TAZ-MS303)

GENERal FEaTURES

• Ceiling-concealed ducted indoor unit for residential applications

• Ultra thin body: 7-7/8

"

 high

• Built-in drain mechanism for condensate removal; lifts to 21-11/16

"

• Air filter is included with indoor unit

• Quiet operation ― as low as 23 dBA

• PAR-21MAA wired remote controller is included

• Indoor unit powered from outdoor unit using A-Control

• Automatic fan speed control

• Auto restart following a power outage

• Limited warranty: one year on parts and defects

MXZ MUlTI-ZONE HEaT-pUMp OUTDOOR UNITS

MXZ MUlTI-ZONE SYSTEMS CaN INClUDE:

• All Horizontal-ducted Indoor Units:  

  

SEZ-KD09, 12, 15, 18Na

• Select Wall-mounted Indoor Units:  

  

MSZ-a09, 12, 15, 17, 24Na

  

  and  

  

MSZ-FD09, 12Na

• A combination of both Horizontal-ducted 

  and Wall-mounted Indoor Units

Refer to the separate submittal forms for the 

MSZ-A and MSZ-FD Indoor Units and MXZ 

Outdoor Units.

Horizontal-ducted Indoor Unit: SEZ-KD-NA

Remote Controller  

PAR-21MAA -  

Packaged with SEZ

Wall-mounted Indoor Unit: MSZ-A09, 12, 15, 17, 24NA

Wireless Remote Controller -  

Packaged with MSZ-A and MSZ-FD 

(Optional Wired Remote Controller 

PAR-21MAA)

Outdoor Unit: MXZ-3A30NA

Wall-mounted Indoor Unit: MSZ-FD-NA

MXZ COMpaTIblE INDOOR UNITS aND REMOTE CONTROllERS

Reviews: