background image

7

4.7. Precautions when reusing existing R22 refrigerant pipes

• Refer to the flowchart below to determine if the existing pipes can be used and if it is necessary to use a filter dryer.
• See below for oil condition.

Clear to slight yellow color 

 Normal

Black or brown 

 Pipe cleaning is necessary.

• If the diameter of the existing pipes is different from the specified diameter, refer to technological data materials to confirm if the pipes can be used.
• If pipes with a diameter of ø19.05 mm are used for RP4-6, DIP switch SW8-1 on the control board must be switched to ON.

Measure the existing pipe thickness and check
for damage.

The existing pipe thickness meets specifi-
cations and the pipes are not damaged.

The existing pipe thickness does not meet
specifications or the pipes are damaged.

Check if the existing air conditioner can operate.

The existing air conditioner can operate.

The existing air conditioner cannot operate.

After operating the cooling system for about
30 minutes, do a pump down work.

Use a refrigerant collecting device to collect the refrigerant.

Check the oil condition when collecting the refrigerant.

Oil is clean.

Oil is dirty.

When the compressor bearings are
glazed, rotation scratches are present,
or the compressor breaks down, iron
particles or oil deterioration will blacken
the oil.

Disconnect the existing air conditioner from
the pipes.

Disconnect the existing air conditioner from the pipes and
clean the pipes using a cleaning device.

Attach a filter dryer. (Sold separately)

The existing pipes can be reused.
Attach the new air conditioner.

The existing pipes cannot be reused.
Use new pipes.

4. Installing the refrigerant piping

4.8. For twin/triple combination

Refrigerant piping limitation of length, height difference are shown in the figure. (Fig.
4-7)

A

Indoor unit

B

Outdoor unit

C

Multi distribution pipe (option)

D

Height difference (Indoor unit-Outdoor unit) Max. 30 m

E

Height difference (Indoor unit-Indoor unit) Max. 1 m

A

A

A

C

E

D

D

B

C

A

B

 B–C 

 B–D 

 8 m

 C–D 

RP3 : A+B+C 

 50

RP4-6 : A+B+C(+D) 

 75 m

Fig. 4-7

5. Drainage piping work

Outdoor unit drainage pipe connection

When drain piping is necessary, use the drain pan (optional parts).

Summary of Contents for Mr.Slim PUNZ-RP-HA-A

Page 1: ...Air Conditioners PUHZ RP HA A English INSTALLATION MANUAL For safe and correct use please read this installation manual thoroughly before installing the air conditioner unit FOR INSTALLER ...

Page 2: ...ant pipes If the pipes are not connected correctly the unit will not be properly grounded and electric shock may result Use only specified cables for wiring The connections must be made securely without tension on the terminals If the cables are connected or installed in correctly overheating or fire may result The terminal block cover panel of the outdoor unit must be firmly attached If the cover...

Page 3: ...e rioration or compressor breakdown may result Use ester oil ether oil alkylbenzene oil small amount as the refrigeration oil applied to the flared sections If mineral oil is mixed in the refrigeration oil oil deterioration may result Do not use refrigerant other than R410A refrigerant If another refrigerant is used the chlorine will cause the oil to deteriorate Use the following tools specificall...

Page 4: ...nal air outlet guides for upward airflow 3 Obstacles at front only Fig 2 14 When using an optional air outlet guide the clearance for RP4 6 models is 1000 mm or more 4 Obstacles at front and rear only Fig 2 15 When using an optional air outlet guide the clearance for RP4 6 models is 1000 mm or more 5 Single parallel unit arrangement Fig 2 16 When using an optional air outlet guide installed for up...

Page 5: ...Model RP3 6 Liquid ODø9 52 3 8 Gas ODø15 88 5 8 Drainage piping PVC ODø32 1 1 4 Table 1 Fig 4 2 Fig 4 1 A A B Fig 4 2 4 1 Precautions for devices that use R410A refrigerant Refer to page 3 for precautions not included below on using air conditioners with R410A refrigerant Use ester oil ether oil alkylbenzene oil small amount as the refrigeration oil applied to the flared sections Use C1220 copper ...

Page 6: ... method 1 Gas side Fig 4 5 1 Remove the cap pull the handle toward you and rotate 1 4 turn in a counterclock wise direction to open 2 Make sure that the stop valve is open completely push in the handle and rotate the cap back to its original position 2 Liquid side Fig 4 6 1 Remove the cap and turn the valve rod counterclockwise as far as it will go with the use of a 4 mm hexagonal wrench Stop turn...

Page 7: ...inutes do a pump down work Use a refrigerant collecting device to collect the refrigerant Check the oil condition when collecting the refrigerant Oil is clean Oil is dirty When the compressor bearings are glazed rotation scratches are present or the compressor breaks down iron particles or oil deterioration will blacken the oil Disconnect the existing air conditioner from the pipes Disconnect the ...

Page 8: ... 1 0MΩ Ω Ω Ω Ω s Do not carry out this test on the control wiring low voltage circuit termi nals Warning Do not use the air conditioner if the insulation resistance is less than 1 0MΩ Ω Ω Ω Ω Insulation resistance After installation or after the power source to the unit has been cut for an extended period the insulation resistance will drop below 1 MΩ due to refrigerant accumulat ing in the compre...

Page 9: ... down Perform the following procedures to collect the refrigerant when moving the indoor unit or the outdoor unit 1 Before collecting the refrigerant first make sure that the all of the SW5 DIP switches for function changes on the control board of the outdoor unit are set to OFF If all of the SW5 switches are not set to OFF record the settings and then set all of the switches to OFF Start collecti...

Page 10: ......

Page 11: ...0 1500 300 500 Max 500 200 300 1000 1500 300 500 1000 1500 Max 300 1000 1500 1000 1500 300 500 500 1000 400 600 1000 2000 100 150 1000 1500 500 800 150 1000 1500 400 600 2000 3000 300 500 Fig 2 6 Fig 2 7 Fig 2 8 Fig 2 9 Fig 2 10 Fig 2 11 Fig 2 12 Fig 2 13 Fig 2 14 Fig 2 15 Fig 2 16 Fig 2 17 Fig 2 18 ...

Page 12: ... sure to put the contact address telephone number on this manual before handing it to the customer HEAD OFFICE MITSUBISHI DENKI BLDG 2 2 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN Printed in Japan BG79U130H01 ...

Reviews: