![Mitsubishi Electric Mr.Slim PUHZ-RP100YKA Service Manual Download Page 13](http://html.mh-extra.com/html/mitsubishi-electric/mr-slim-puhz-rp100yka/mr-slim-puhz-rp100yka_service-manual_1810290013.webp)
13
To
ta
l
Electrical circuit
Refrigerant circuit
Indoor side
Outdoor
side
Representative matching
SHF
BF
W
kW
Mode
Capacity
Input
PLA-RP71BA2
PLA-RP71BA2
Cooling
7,100
1.90
Heating
8,000
1.90
8.20
2.73
0.95
69
45
12
5
27
19
14.5
35
24
0.73
0.21
8.25
2.65
0.71
72
43
3
5
20
15
38.8
7
6
—
—
1 , 50
230
PUHZ-RP71VHA4
1 , 50
230
Phase , Hz
Voltage
Current
Outdoor unit
Phase , Hz
Voltage
Current
Discharge pressure
Suction pressure
Discharge temperature
Condensing temperature
Suction temperature
Ref. pipe length
Intake air temperature
Discharge air temperature
Intake air temperature
V
A
V
A
MPa
MPa
°C
°C
°C
m
°C
°C
°C
°C
°C
Indoor unit
D.B.
W.B.
D.B.
D.B.
W.B.
PLA-RP35BA
PLA-RP50BA
PLA-RP60BA
PLA-RP35BA
PLA-RP50BA
PLA-RP60BA
Cooling
3,600
1.07
Heating
4,100
1.12
Cooling
5,000
1.55
Heating
6,000
1.62
Cooling
6,000
1.60
Heating
7,000
1.82
4.66
2.70
1.01
70
46
15
5
27
19
15.8
35
24
0.84
0.28
4.93
2.69
0.74
71
41
2
5
20
15
34.6
7
6
—
—
6.72
2.91
0.99
73
49
11
5
27
19
15.3
35
24
0.81
0.24
7.08
2.76
0.67
77
44
-1
5
20
15
37.8
7
6
—
—
6.95
2.64
0.96
67
44
11
5
27
19
14.2
35
24
0.76
0.21
7.98
2.90
0.74
80
46
3
5
20
15
39.2
7
6
—
—
1 , 50
230
PUHZ-RP35VHA4
1 , 50
230
1 , 50
230
PUHZ-RP50VHA4
1 , 50
230
1 , 50
230
PUHZ-RP60VHA4
1 , 50
230
0.22
0.14
0.36
0.29
0.36
0.29
0.51
0.43
6-5. STANDARD OPERATION DATA
The unit of pressure has been changed to MPa based on international SI system.
The conversion factor is : 1(MPa)=10.2(kgf/cm²)