67
SW2 setting
Display detail
Explanation for display
Unit
1
ON
2 3 4 5 6
Pulse
LEV-A opening pulse on error occurring
0~480
0~480
(When it is 100 pulse or more, hundreds digit, tens
digit and ones digit are displayed by turns.)
(Example) When 130 pulse;
0.5 secs. 0.5secs. 2 secs.
:
Indoor room temperature (TH1) on error
occurring
8~39
8~39
:
Indoor pipe temperature/Liquid (TH2) on
error occurring
-39~88
-39~88
(When the temperature is 0°C or less, “–” and
temperature are displayed by turns.)
(Example) When –15°C;
0.5 secs. 0.5secs. 2 secs.
Indoor pipe temperature/Cond./Eva.
(TH5) on error occurring
-39~88
-39~88
(When the temperature is 0°C or less, “–” and
temperature are displayed by turns.)
(Example) When –15°C;
0.5 secs. 0.5secs. 2 secs.
Outdoor pipe temperature/2 phase (TH6)
on error occurring
-39~88
-39~88
(When the temperature is 0°C or less, “–” and
temperature are displayed by turns.)
(Example) When –15°C;
0.5 secs. 0.5secs. 2 secs.
Outdoor outside temperature (TH7) on
error occurring
-39~88
-39~88
(When the temperature is 0°C or less, “–” and
temperature are displayed by turns.)
(Example) When –15°C;
0.5 secs. 0.5secs. 2 secs.
Outdoor heatsink temperature (TH8) on
error occurring
-40~200
-40~200
(When the temperature is 0°C or less, “–” and
temperature are displayed by turns.)
(When the temperature is 100°C or more, hundreds
digit, tens digit and ones digit are displayed by
turns.)
30
1
1
ON
2 3 4 5 6
1
ON
2 3 4 5 6
1
ON
2 3 4 5 6
1
ON
2 3 4 5 6
1
ON
2 3 4 5 6
1
ON
2 3 4 5 6
15
15
15
15
:
:
:
:
The black square (
■
) indicates a switch position.
OCH424E