39
(5) Drain pump control
(Option : Only PKH-2.5FKA-E / PKH-3FKA-E / PKH-4FKSA-E)
The drain pump works in COOL or DRY operation. When operation stops or changes to HEAT mode, the drain pump con-
tinues to operate for 3 more minutes. The drain pump does not work in check mode.
<Drain sensor>
When both the drain pump and unit are operating, the drain sensor detects the temperature. This temperature tells whether
the drain water level is above or under the drain sensor. If the drain water level rises above the drain sensor due to a drain
pump malfunction, the unit will stop operating in order to prevent drain from overflowing. The check code “P5” on the
remote controller will display this occurrence. When both of the following conditions are satisfied, the drain sensor is deter-
mined to be under water.
●
Though the drain sensor has been heated by the drain sensor heater for more than 40 seconds, its temperature rise is
less than 20 degrees.
●
The drain sensor temperature is below 63°C.
2-2 DRY operation
<DRY operation time chart>
w
1 Even if the room temperature rise above the set temperature during this period, the compressor will not start until this period
has ended.
Minimum 3 minutes
w
1
ON
Thermostat
Indoor fan
Auto vane
Compressor
ON
(PKH-2.5/3/4)
w
Refer to page 40 for P K H - 1 . 6 / 2
Initially 10 degrees discharge
(Changeable by remote controller setting)
LOW speed
LOW speed
ON
ON
OFF
OFF
CLOSE
CLOSE
OFF
OFF
Operation starts by
P O W E R b u t t o n
ON.
Operation stops by
P O W E R b u t t o n
OFF.
Room temperature
becomes equal to
set temperature.
Room temperature
rises above set
temperature.
<How to operate>
1
Press POWER ON/OFF button.
2
Press the
a
button to display “
e
”.
3
Press the
i
TEMP. button to set the desired temperature.
NOTE: The set temperature changes 1°C when the
or
button is press one time DRY 19 to 30°C.
FILTER
CHECK MODE
TEST RUN
241