background image

1

1.  Safety precautions

Note:

The phrase “Wired remote controller” in this installation manual refers to the PAR-40MAA. If you need any information for other remote controller, please 

refer to the installation manual that is included with the optional remote controller.

►  Before installing the unit, make sure you read all the “Safety Precautions”. 

►  The “Safety Precautions” provide very important points regarding safety. Make sure you follow them. 

►  Please report to your supply authority or obtain their consent before connecting this equipment to the power supply system.

Symbols used in the text

 Warning:

Describes precautions that should be observed to prevent danger of injury or 

death to the user.

 

Caution:

Describes precautions that should be observed to prevent damage to the 

unit.

Symbols used in the illustrations 

 : Indicates a part which must be grounded.

 : Be sure not to do.

After installation work has been completed, explain the “Safety Precautions,” use, 
and maintenance of the unit to the customer according to the information in the 
Operation Manual and perform the test run to ensure normal operation. Both the 
Installation Manual and Operation Manual must be given to the user for keeping. 
These manuals must be passed on to subsequent users.

MEANINGS OF SYMBOLS DISPLAYED ON INDOOR UNIT AND/OR OUTDOOR UNIT

WARNING

(Risk of fire)

This mark is for R32 refrigerant only. Refrigerant type is written on nameplate of outdoor unit.

In case that refrigerant type is R32, this unit uses a flammable refrigerant.

If refrigerant leaks and comes in contact with fire or heating part, it will create harmful gas and there is risk of fire.

Read the OPERATION MANUAL carefully before operation.

Service personnel are required to carefully read the OPERATION MANUAL and INSTALLATION MANUAL before operation.

Further information is available in the OPERATION MANUAL, INSTALLATION MANUAL, and the like.

 

Warning:

•  Carefully read the labels affixed to the main unit. 

•  Ask a dealer or an authorized technician to install, relocate and repair the 

unit.

•  The user should never attempt to repair the unit or transfer it to another 

location.

•  For installation and relocation work, follow the instructions in the Installation 

Manual and use tools and pipe components specifically made for use with 

refrigerant specified in the outdoor unit installation manual.

•  The unit must be installed according to the instructions in order to 

minimize the risk of damage from earthquakes, typhoons, or strong winds. 

An incorrectly installed unit may fall down and cause damage or injuries.

•  Do not alter the unit. It may cause fire, electric shock, injury or water 

leakage.

•  The unit must be securely installed on a structure that can sustain its 

weight. 

•  The appliance shall be stored in a well-ventilated area where the room size 

corresponds to the room area as specified for operation.

•  If the air conditioner is installed in a small room or closed room, measures 

must be taken to prevent the refrigerant concentration in the room from 

exceeding the safety limit in the event of refrigerant leakage. Should the 

refrigerant leak and cause the concentration limit to be exceeded, hazards 

due to lack of oxygen in the room may result.

•  Keep gas-burning appliances, electric heaters, and other fire sources 

(ignition sources) away from the location where installation, repair, and 

other air conditioner work will be performed.

  If refrigerant comes into contact with a flame, poisonous gases will be 

released.

•  Ventilate the room if refrigerant leaks during operation. If refrigerant comes 

into contact with a flame, poisonous gases will be released.

•  All electric work must be performed by a qualified technician according to 

local regulations and the instructions given in this manual. 

•  Do not use intermediate connection of the electric wires.

•  Use only specified cables for wiring. The wiring connections must be made 

securely with no tension applied on the terminal connections. Also, never 

splice the cables for wiring (unless otherwise indicated in this document).

  Failure to observe these instructions may result in overheating or a fire.

•  When installing or relocating, or servicing the air conditioner, use only the 

specified refrigerant written on outdoor unit to charge the refrigerant lines. 

Do not mix it with any other refrigerant and do not allow air to remain in the 

lines.

   If air is mixed with the refrigerant, then it can be the cause of abnormal high 

pressure in the refrigerant line, and may result in an explosion and other 

hazards.

   The use of any refrigerant other than that specified for the system will 

cause mechanical failure or system malfunction or unit breakdown. In the 

worst case, this could lead to a serious impediment to securing product 

safety.

•  The appliance shall be installed in accordance with national wiring 

regulations.

•  This appliance is not intended for use by persons (including children) with 

reduced physical, sensory or mental capabilities, or lack of experience 

and knowledge, unless they have been given supervision or instruction 

concerning use of the appliance by a person responsible for their safety.

•  Children should be supervised to ensure that they do not play with the 

appliance.

•  The terminal block cover panel of the unit must be firmly attached.

•  If the supply cord is damaged, it must be replaced by the manufacturer, its 

service agent or similarly qualified persons in order to avoid a hazard.

•  Use only authorized accessories and ask a dealer or an authorized 

technician to install them.

  If accessories are incorrectly installed, water leakage, electric shock, or fire 

may result.

•  After installation has been completed, check for refrigerant leaks. If 

refrigerant leaks into the room and comes into contact with the flame of a 

heater or portable cooking range, poisonous gases will be released.

•  Do not use means to accelerate the defrosting process or to clean, other 

than those recommended by the manufacturer.

•  The appliance shall be stored in a room without continuously operating 

ignition sources (for example: open flames, an operating gas appliance or 

an operating electric heater).

•  Do not pierce or burn.

•  Be aware that refrigerants may not contain an odour.

•  Pipe-work shall be protected from physical damage.

•  The installation of pipe-work shall be kept to a minimum.

•  Compliance with national gas regulations shall be observed.

•  Keep any required ventilation openings clear of obstruction.

•  Do not use low temperature solder alloy in case of brazing the refrigerant 

pipes.

•  When performing brazing work, be sure to ventilate the room sufficiently.

  Make sure that there are no hazardous or flammable materials nearby.

  When performing the work in a closed room, small room, or similar 

location, make sure that there are no refrigerant leaks before performing 

the work.

  If refrigerant leaks and accumulates, it may ignite or poisonous gases may 

be released.

1.  Safety precautions .............................................................................................1
2.  Installation location ............................................................................................2
3.  Installing the indoor unit ....................................................................................3
4.  Installing the refrigerant piping ..........................................................................6

5.  Drainage piping work .........................................................................................7
6.  Electrical work ...................................................................................................8
7.  Test run ............................................................................................................14
8.  Easy maintenance function .............................................................................18

For safe and correct use, read this manual and the outdoor unit installation manual thoroughly before installing the air-conditioner unit.

en

Contents

RH79A071W01_01en.indd   1

2020/09/24   9:05:06

Summary of Contents for Mr. SLIM PKA-M-LAL Series

Page 1: ...Air Conditioners PKA M LAL Series FOR INSTALLER English INSTALLATION MANUAL RH79A071W01_Cover indd 1 2020 09 24 9 08 55 ...

Page 2: ...igerant comes into contact with a flame poisonous gases will be released All electric work must be performed by a qualified technician according to local regulations and the instructions given in this manual Do not use intermediate connection of the electric wires Use only specified cables for wiring The wiring connections must be made securely with no tension applied on the terminal connections A...

Page 3: ...s or dripping water When the room humidity exceeds 80 or when the drainpipe is clogged water may drip from the indoor unit Do not install the indoor unit where such dripping can cause damage When installing the unit in a hospital or communications office be prepared for noise and electronic interference Inverters home appliances high frequency medical equipment and radio communications equipment c...

Page 4: ... the wall mounting fixture 3 2 1 Setting the wall mounting fixture and piping positions Using the wall mounting fixture determine the unit s installation position and the locations of the piping holes to be drilled Warning Before drilling a hole in the wall you must consult the building contractor Fig 3 2 A Mount board 1 B Indoor unit C Bottom left rear pipe hole ø75 D Bottom right rear pipe hole ...

Page 5: ... Reference marking for flare connection C Through hole D On site piping 3 4 Preparing the indoor unit Check beforehand because the preparatory work will differ depending on the exiting direction of the piping When bending the piping bend gradually while maintaining the base of the piping exiting portion Abrupt bending will cause misshaping of the piping Cut off outlet of the pipe depending on the ...

Page 6: ...or unit is installed level A Mount board 1 B Indoor unit C Hook D Square hole Left and left rear piping Fig 3 11 3 While inserting the drain hose into the wall penetration hole penetration sleeve hang the top of the indoor unit to the mount board 1 Cut part of the shipping box and wrap into a cylindrical form as illustrated in the diagram Hook this to the rear surface rib as a spacer and raise the...

Page 7: ...y ø6 35 thickness 0 8 mm ø9 52 thickness 0 8 mm ø12 7 thickness 0 8 mm ø15 88 thickness 1 0 mm Do not use pipes thinner than those specified above 4 2 Connecting pipes Fig 4 1 When commercially available copper pipes are used wrap liquid and gas pipes with commercially available insulation materials heat resistant to 100 C or more thickness of 12 mm or more The indoor parts of the drain pipe shoul...

Page 8: ...C TUBE Make sure that there is no water leakage from the connections Do not put the drain piping directly in a drainage ditch where sulphuric gas may be generated When piping has been completed check that water flows from the end of the drain pipe Caution The drain pipe should be installed according to this Installation Manual to ensure correct drainage Thermal insulation of the drain pipes is nec...

Page 9: ...g strand wires because beards may cause the wiring to short out 3 Install the parts that were removed back to their original condition 4 Fasten each of the wires with the clamp under the electrical parts box A Electrical box cover B Fixing screw C Clamp D Ground wire connection portion E MA remote control terminal block 1 2 do not have polarity F Terminal block for indoor and outdoor units connect...

Page 10: ...ting Indoor unit L N 3 Indoor unit Outdoor unit S1 S2 3 230 V AC Indoor unit Outdoor unit S2 S3 3 4 24 V DC 28 V DC Wired remote controller option Indoor unit 3 12 V DC 1 For 35 140 outdoor unit application Max 45 m If 2 5 mm2 used Max 50 m If 2 5 mm2 used and S3 separated Max 80 m For 200 250 outdoor unit application Max 18 m If 2 5 mm2 used Max 30 m If 4 mm2 used and S3 separated Max 50 m If 6 m...

Page 11: ...r supply terminal kit is used change the indoor unit electrical box wiring refering to the figure in the right and the DIP switch settings of the outdoor unit control board Refer to the installation manual for the Power supply terminal kit Affix label B that is included with the manuals near each wiring diagram for the indoor and outdoor units Note Some units cannot be used in a simultaneous twin ...

Page 12: ...splay 12 hour format 24 hour format B AUTO mode Single set point Dual set point C Pair No 0 3 D Backlight On Off E 4 1 Switching to the initial setting mode 1 Press the button 1 to stop the air conditioner 2 Press the button 2 The Function setting screen will be displayed and the function No A will blink Fig 6 6 Press the button 4 to change the function No 3 Check that function No 1 is displayed a...

Page 13: ...rsor Cursor Ref address Mode 1 Mode 2 Mode 3 Mode 4 Grp F1 F2 F3 F4 Function setting Cursor Cursor Request Ref address Mode 1 Mode 2 Mode 3 Mode 4 Grp Fig 6 11 Fig 6 12 F1 F2 F3 F4 Function setting Ref address Sending data Grp Fig 6 13 Fig 6 14 Fig 6 16 Fig 6 15 Fig 6 17 6 3 2 By wireless remote controller 1 Going to the function select mode Press the button between of 5 seconds Start this operati...

Page 14: ...ported indoor unit is equipped with outdoor air intake 3 Power voltage 240 V 04 1 220 V 230 V 2 Select unit numbers 1 to 4 or All Mode Settings Mode no Setting no Initial setting setting Filter sign 100 Hr 07 1 2500 Hr 2 No filter sign indicator 3 Fan speed Silent 08 1 Standard 2 High ceiling 3 Fan speed during the cooling thermostat is OFF Setting fan speed 27 1 Stop 2 Extra low 3 1 When the powe...

Page 15: ... is turned on Please Wait is displayed for 3 minutes during system startup Normal After power is turned on Please Wait is displayed for 3 minutes then error code is dis played After startup is displayed green once and red once blink alternately F1 Incorrect connection of outdoor terminal block L N and S1 S2 S3 After startup is displayed green once and red twice blink alternately F3 F5 F9 Outdoor u...

Page 16: ...ller power supply Indicates whether power is supplied to the wired remote controller The LED is lit only for the indoor unit that is con nected to the outdoor unit that has an address of 0 LED 3 indoor outdoor unit communication Indicates whether the indoor and outdoor units are communicating Make sure that this LED is always blinking Test run Fig 7 5 1 Press the button 1 to stop the air condition...

Page 17: ...ignal received Beeper sounds Refer to the following tables for details on the check codes Wireless remote controller Output pattern A 7 3 Self check Refer to the installation manual that comes with each remote controller for details Output pattern A Errors detected by indoor unit Wireless remote controller Wired remote controller Symptom Remark Beeper sounds OPERATION INDICATOR lamp blinks Number ...

Page 18: ...ceived the specified refrigerant address is incorrect On wireless remote controller The continuous buzzer sounds from receiving section of indoor unit Blink of operation lamp On wired remote controller Check code displayed in the LCD If the unit cannot be operated properly after test run refer to the following table to find the cause Symptom Cause Wired remote controller LED 1 2 PCB in outdoor uni...

Page 19: ...l Ref address Cool Ref address Cool Sub cool OU TH4 temp OU TH6 temp OU TH7 temp IU air temp IU HEX temp IU filter time 1 2 3 Select Service from the Main menu and press the SELECT button Select Check with the F1 or F2 button and press the SELECT button Select Smooth maintenance with the F1 or F2 button and press the SELECT button Select each item Select the item to be changed with the F1 or F2 bu...

Page 20: ...99 514 Carnaxide Lisbon Portugal Spanish Branch Carretera de Rubi 76 80 Apdo 420 08173 Sant Cugat del Valles Barcelona Spain Scandinavian Branch Hammarbacken 14 P O Box 750 SE 19127 Sollentuna Sweden UK Branch Travellers Lane Hatfield Herts AL10 8XB England U K Polish Branch Krakowska 50 PL 32 083 Balice Poland MITSUBISHI ELECTRIC TURKEY ELEKTRİK ÜRÜNLERI A Ş Şerifali Mah Kale Sok No 41 34775 Ümra...

Reviews: