16
• If the unit cannot be operated properly after the test run has been performed, refer to the following table to remove the cause.
Symptom
Cause
Wired remote controller
LED 1, 2 (PCB in outdoor unit)
On the wireless remote controller with condition above, following phenomena take place.
• No signals from the remote controller are accepted.
• Operation lamp is blinking.
• The buzzer makes a short piping sound.
PLEASE WAIT
PLEASE WAIT
→
Error code
Display messages do not
appear even when operation
switch is turned ON (operation
lamp does not light up).
For about 2
minutes after
power-on
After about 2
minutes has
expired after
power-on
After LED 1, 2 are lighted, LED 2 is
turned off, then only LED 1 is
Only LED 1 is lighted.
→
LED 1, 2 blink.
Only LED 1 is lighted.
→
LED 1 blinks twice,
LED 2 blinks once.
• For about 2 minutes after power-on,op-
eration of the remote controller is not possible
due to system start-up. (Correct operation)
• Connector for the outdoor unit’s protection
device is not connected.
• Reverse or open phase wiring for the outdoor
unit’s power terminal block (L1, L2, L3)
• Incorrect wiring between indoor and outdoor
units (incorrect polarity of S1, S2, S3)
• Remote controller wire short
Note:
Operation is not possible for about 30 seconds after cancellation of function selection. (Correct operation)
For description of each LED (LED1, 2, 3) provided on the indoor controller, refer to the following table.
LED1 (power for microcomputer)
Indicates whether control power is supplied. Make sure that this LED is
always lit.
LED2 (power for remote controller)
Indicates whether power is supplied to the remote controller.
This LED lights only in the case of the indoor unit which is connected to the
outdoor unit refrigerant address “0”.
LED3 (communication between indoor and
outdoor units)
Indicates state of communication between the indoor and outdoor units.
Make sure that this LED is always blinking.
lighted. (Correct operation)