background image

8

GB

D

F

E

I

NL

P

GR

RU

TR

CZ

SV

HG

PO

At a distance 1 m or more away from your TV and radio (to prevent picture from
being distorted or noise from being generated).

In a place as far away as possible from fluorescent and incandescent lights (so
the infrared remote control can operate the air conditioner normally).

Do not install unit at a site where fire detector is located at the supply air side.
(Fire detector may operate erroneously due to the heated air supplied during
heating operation.)

When special chemical product may scatter around such as site chemical plants
and hospitals, full investigation is required before installing unit. (The plastic
components may be damaged depending on the chemical product applied.)

If the unit is run for long hours when the air above the ceiling is at high tem-
perature/high humidity (due point above 26 

°

C), due condensation may be

produced in the indoor unit. When operating the units in this condition, add
insulation material (10-20 mm) to the entire surface of the indoor unit to avoid
due condensation.

Do not install the unit where ambient temperature exceeds 35

°

C [95

°

F] DB.

3.1. Install the indoor unit on a ceiling strong

enough to sustain its weight

 Warning:

The unit must be securely installed on a structure that can sustain its weight.
If the unit is mounted on an unstable structure, it may fall down causing
injuries.

3.2. Securing installation and service space

Select the optimum direction of supply airflow according to the configuration of
the room and the installation position.

As the piping and wiring are connected at the bottom and side surfaces, and
the maintenance is made at the same surfaces, allow a proper space properly.
For the efficient suspension work and safety, provide a space as much as
possible.

[Fig. 3.2.1] (P.2)

A

Access door

B

Electrical parts box

C

Air inlet

D

Air outlet

E

Ceiling surface

3.3. Combining indoor units with outdoor

units

For combining indoor units with outdoor units, refer to the outdoor unit installation
manual.

6. Refrigerant pipe and drain pipe specifications

To avoid dew drops, provide sufficient antisweating and insulating work to the re-
frigerant and drain pipes.
When using commercially available refrigerant pipes, be sure to wind commer-
cially available insulating material (with a heat-resisting temperature of more than
100

°

C and thickness given below) onto both liquid and gas pipes.

Insulate all indoor pipes with form polyethylene insulation with a minimum density
of 0.03 and a thickness as specified in the table below.

1

Select the thickness of insulating material by pipe size.

Pipe size

Insulating material’s thickness

6.4 mm to 25.4 mm

More than 10 mm

28.6 mm to 38.1 mm

More than 15 mm

2

If the unit is used on the highest story of a building and under conditions of
high temperature and humidity, it is necessary to use pipe size and insulating
material’s thickness more than those given in the table above.

3

If there are customer’s specifications, simply follow them.

4. Fixing hanging bolts

4.1

Fixing hanging bolts

[Fig. 4.1.1] (P.2)

A

Center of gravity

(Give site of suspension strong structure.)

Hanging structure

Ceiling: The ceiling structure varies from building to one another. For detailed
information, consult your construction company.

If necessary, reinforce the hanging bolts with anti-quake supporting members
as countermeasures against earthquakes.
* Use M10 for hanging bolts and anti-quake supporting members (field supply).

5. Installing the unit

5.1. Hanging the unit body

s

s

s

s

s

Bring the indoor unit to an installation site as it is packed.

s

s

s

s

s

To hang the indoor unit, use a lifting machine to lift and pass through the
hanging bolts.

[Fig. 5.1.1] (P.2)

A

Unit body

B

Lifting machine

[Fig. 5.1.2] (P.2)

C

Nuts (field supply)

D

Washers (accessory)

E

M10 hanging bolt (field supply)

5.2. Transporting the heat exchanger unit

and the fan unit separately

s

s

s

s

s

Refer to the “Manipulation Details” label on the unit for how to separate
the heat exchanger unit and the fan unit.

 Caution:

Heat exchanger unit and the fan unit cannot be installed in separate loca-
tions. Doing so will cause water leakage.

5.3. Confirming the unit’s position and fix-

ing hanging bolts

s

s

s

s

s

Use the gage supplied with the panel to confirm that the unit body and
hanging bolts are positioned in place. If they are not positioned in place,
it may result in dew drops due to wind leak. Be sure to check the positional
relationship.

s

s

s

s

s

Use a level to check that the surface indicated by 

A

A

A

A

A

 is at level. Ensure

that the hanging bolt nuts are tightened to fix the hanging bolts.

s

s

s

s

s

To ensure that drain is discharged, be sure to hang the unit at level using
a level.

[Fig. 5.3.1] (P.2)

A

Indoor unit’s bottom surface

 Caution:

Install the unit in horizontal position. If the side with drain port is installed
higher, water leakage may be caused.

Model name

PEA-RP170WHA

PEA-RP200WHA

W

1034

1034

L

1324

1324

X

494

494

Y

701

701

Z

235

235

Product Weight (kg)

108

108

Center of gravity and Product Weight

WT05749X01_GB.p65

09/11/6, 12:27

8

Summary of Contents for Mr.Slim PEA-RP200WHA

Page 1: ...Air Conditioners INDOOR UNIT PEA RP170 200 WHA GB INSTALLATION MANUAL For safe and correct use please read this installation manual thoroughly before installing the air conditioner unit ...

Page 2: ... Refrigerant piping liquid C Refrigerant piping gas D Control box E Drain pipe F Air outlet 200 300 150 200 50 50 1350 730 450 470 more than 20 30 10 more than 20 more than 100 60 23 1324 23 37 1250 1100 1100 800 1034 B C D A A E Keep the service space for the maintenance from the bottom when the heat exchanger is cleaned 701 494 235 1034 1324 A A B A 165 52 100 244 30 424 A B E C D F A Access doo...

Page 3: ...en the insulation and the main body I Thermal insulation tubing small supplied 1 J Ties large supplied 4 K Ensure that there is no gap here Place join upwards L Thermal insulation tubing medium supplied 2 M Thermal insulation N Pull O Flared pipe end P Wrap with damp cloth Q Return to original position R Ensure that there is no gap here Fig 7 2 1 A B 1 C C C D 2 E A Downward slope 1 100 or more B ...

Page 4: ... Air outlet I Keep duct work length 850 mm or more A Non polarized B TB15 C Remote Controller D TB4 Fig 9 2 2 B G E F H A I C C D D A B C 9 3 A Terminal bed box B Knockout hole C Remove A Screw holding cover 2pcs B Cover Fig 9 3 1 Fig 9 3 2 A B B C A A Terminal block for indoor transmission cable B Terminal block for outdoor transmission cable C Remote controller A C TB4 TB15 B S1 S2 S3 S1 S2 S3 2...

Page 5: ...F button B Test run display C Indoor temperature liquid line temperature display D ON OFF lamp E Power display A CHECK button B Refrigerant address C TEMP button D IC Indoor unit OC Outdoor unit E Check code F Error code display Test run remaining time display G Set temperature button H Mode selection button I Fan speed button M TEST button A Filter button Enter button B TEST button C Set Time but...

Page 6: ...on the unit If a different refrigerant or air is mixed with the original refrigerant the refrig erant cycle may malfunction and the unit may be damaged If the air conditioner is installed in a small room measures must be taken to prevent the refrigerant concentration from exceeding the safety limit even if the refrigerant should leak Consult the dealer regarding the appropriate measures to prevent...

Page 7: ...fied capacity A fuse or circuit breaker of a larger capacity or a steel or copper wire may result in a general unit failure or fire Do not wash the air conditioner units Washing them may cause an electric shock Be careful that the installation base is not damaged by long use If the damage is left uncorrected the unit may fall and cause personal injury or property damage Install the drain piping ac...

Page 8: ...indoor pipes with form polyethylene insulation with a minimum density of 0 03 and a thickness as specified in the table below 1 Select the thickness of insulating material by pipe size Pipe size Insulating material s thickness 6 4 mm to 25 4 mm More than 10 mm 28 6 mm to 38 1 mm More than 15 mm 2 If the unit is used on the highest story of a building and under conditions of high temperature and hu...

Page 9: ...Insertion margin F Drain hose accessory G Drain pipe O D ø32 PVC TUBE field supply H Insulating material field supply I Max 145 5 mm 7 Connecting refrigerant pipes and drain pipes 7 1 Refrigerant piping work This piping work must be done in accordance with the installation manuals for both outdoor unit For constraints on pipe length and allowable difference of elevation refer to the outdoor unit m...

Page 10: ...ion and supplied installation manuals Special circuits should also be used If the power cir cuit lacks capacity or has an installation failure it may cause a risk of elec tric shock or fire 1 Be sure to install an earth leakage breaker to the power 2 Install the unit to prevent that any of the control circuit cables remote control ler transmission cables is brought in direct contact with the power...

Page 11: ...for at least 2 seconds FUNCTION will start to flash 2 Use the C button to set the refrigerant address 3 to 00 3 Press D and will start to flash in the unit number 4 display 4 Use the C button to set the unit number 4 to 01 04 or AL 5 Press the E MODE button to designate the refrigerant address unit number will flash in the mode number 1 display momentarily 6 Press the F buttons to set the mode num...

Page 12: ...election button and switch to the cooling or heating mode Make sure that cold or warm wind is blown out 5 Press the Fan speed button Make sure that the wind speed is switched 6 Check operation of the outdoor unit fan 7 Release test run by pressing the ON OFF button Stop 8 Register a telephone number The telephone number of the repair shop sales office etc to contact if an error occurs can be regis...

Page 13: ......

Page 14: ......

Page 15: ......

Page 16: ...Voltage Directive 2006 95 EC Electromagnetic Compatibility Directive 2004 108 EC This product is designed and intended for use in the residential commer cial and light industrial environment HEAD OFFICE TOKYO BLDG 2 7 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN Authorized representative in EU MITSUBISHI ELECTRIC EUROPE B V HARMAN HOUSE 1 GEORGE STREET UXBRIDGE MIDDLESEX UB8 1QQ U K ...

Reviews: