6. Electrical work
7. Test run
7.1. Before test run
After completing installation and the wiring and piping of the indoor and outdoor
units, check for refrigerant leakage, looseness in the power supply or control
wiring, wrong polarity, and no disconnection of one phase in the supply.
Use a 500-volt megohmmeter to check that the resistance between the power
supply terminals and ground is at least 1.0 MΩ.
Do not carry out this test on the control wiring (low voltage circuit) terminals.
Warning:
Do not use the air conditioner if the insulation resistance is less than 1.0 MΩ.
7.2. Test run
The following 3 methods are available.
7.2.1. Using wired remote controller (Fig. 7-1)
1
Turn on the power at least 12 hours before the test run.
2
Press the [TEST] button twice. “TEST RUN” liquid crystal display
3
Press the [Mode selection] button and switch to the cooling mode.
Make sure that cold wind is blown out.
4
Press the [Fan speed] button. Make sure that the wind speed is switched.
5
Press the [Air direction button] or [Louver button].
Check operation of the vane or louver.
6
Check operation of the outdoor unit fan.
7
Release test run by pressing the [ON/OFF] button. Stop
8
Register a telephone number.
The telephone number of the repair shop, sales office, etc., to contact if an error
occurs can be registered in the remote controller. The telephone number will be
displayed when an error occurs. For registration procedures, refer to the operation
manual for the indoor unit.
Fig. 7-1
°C
°C
SIMPLE
PAR-21MAA
ON/OFF
FILTER
CHECK
OPERATION
CLEAR
TEST
TEMP.
MENU
BACK
DAY
MONITOR/SET
CLOCK
ON/OFF
TEST RUN
COOL
A
F
C
E
D B
M
I
O
N
H G
A
ON/OFF button
B
Test run display
C
Indoor temperature liquid
line temperature display
D
ON/OFF lamp
E
Power display
F
Error code display
Test run remaining time
display
G
Set temperature button
H
Mode selection button
I
Air direction button
M
TEST button
N
Fan speed button
O
Louver button
Mode
Power failure automatic recovery
Indoor temperature detecting
LOSSNAY connectivity
Power voltage
Settings
Not available
Available *1
Indoor unit operating average
Set by indoor unit’s remote controller
Remote controller’s internal sensor
Not Supported
Supported (indoor unit is not equipped with outdoor-air intake)
Supported (indoor unit is equipped with outdoor-air intake)
240 V
220 V, 230 V
Mode no.
Setting no. Initial setting Setting
01 1
2
1
02
2
3
1
03
2
3
04 1
2
Mode
Filter sign
Fan speed
UP/down vane setting
Settings
100h *2
2500h *2
No filter sign indicator
Silent
Standard
High ceiling
No. Vanes
Eguipped with vanes (vanes angle setup
1
)
Eguipped with vanes (vanes angle setup
2
)
Mode no. Setting no. Initial setting Setting
1
07
2
3
1
08
2
3
1
11
2
3
*1 When the power supply returns, the air conditioner will start 3 minutes later.
*2 The functions above are available only when the wired remote controller is used.