32
33
OCH659A
E6
E7
Check code Abnormal point and detection method
Cause
Countermeasure
Fb
(FB)*
E1
or
E2
Contact failure, short circuit or,
miswiring (reverse wiring) of
indoor/outdoor unit connecting
wire
Defective transmitting receiving
circuit of indoor controller board
Defective transmitting receiving
circuit of indoor controller board
Noise has entered into indoor/
outdoor unit connecting wire.
Check LED display on the outdoor control
circuit board. (Connect A-control service
tool, PAC-SK52ST.) Refer to outdoor unit ser-
vice manual.
Check disconnection or looseness of indoor/
outdoor unit connecting wire of indoor unit or
outdoor unit.
Check all the units in case of twin triple
indoor unit system.
– Turn the power off, and on again to
check. If abnormality occurs again,
replace indoor controller board or outdoor
controller circuit board.
Note:
Other indoor controller board may have defect
in the case of twin triple indoor unit system.
Indoor/outdoor unit communication
error (Transmitting error)
Abnormal if “1” receiving is detected 30
times continuously though indoor controller
board has transmitted “0”.
Defective transmitting receiving
circuit of indoor controller board
Noise has entered into power
supply.
Noise has entered into outdoor
control wire.
– Turn the power off, and on again to
check. If abnormality occurs again,
replace indoor controller board.
Indoor/outdoor unit communication
error (Signal receiving error)
Abnormal if indoor controller board
cannot receive any signal normally for
6 minutes after turning the power on.
Abnormal if indoor controller board
cannot receive any signal normally for
3 minutes.
Consider the unit abnormal under
the following condition: When 2 or
more indoor units are connected to an
outdoor unit, indoor controller board
cannot receive a signal for 3 minutes
from outdoor controller circuit board, a
signal which allows outdoor controller
circuit board to transmit signals.
Indoor controller board
Abnormal if data cannot be read normally
from the nonvolatile memory of the indoor
controller board.
Defective indoor controller
board
Replace indoor controller board.
* The check code in the parenthesis indicates
PAR-33MAA model.
Remote controller control board
Abnormal if data cannot be read nor-
mally from the nonvolatile memory of the
remote controller control board.
(Check code: E1)
Abnormal if the clock function of remote
controller cannot be operated normally.
(Check code: E2)
Defective remote controller
Replace remote controller.
PA
Forced compressor stop
(due to water leakage abnormality)
The unit has a water leakage abnormality
when the following conditions, a) and b),
are satisfied while the above-mentioned
detection is performed.
a) The intake temperature subtracted
with liquid pipe temperature detects
to be less than −10˚C for a total of
30 minutes. (When the drain sensor
is detected to be NOT soaked in the
water, the detection record of a) and b)
will be cleared.)
b) Drain float switch detects to be in the
water for more than 15 minutes.
Note:
Once the water leakage abnormality is
detected, abnormality state will not be
released until the main power is reset.
Drain pump trouble
Defective drainage
· Drain pump clogging
· Drain pipe clogging
Open circuit of float switch
Contact failure of float switch
connector
Dew condensation on float
switch
· Drain water trickles down lead
wire.
· Drain water ripples due to filter
clogging.
Extension piping connection
difference at twin, triple or
quadruple system
Miswiring of indoor/outdoor
connecting at twin, triple or
quadruple system
Room temperature thermistor/
liquid pipe temperature
thermistor detection is defective.
Check the drain pump.
Check whether water can be drained.
Check the resistance of the float switch.
Check the connector contact failure.
Check the float switch leadwire mounted.
Check the filter clogging.
Check the piping connection.
Check the indoor/outdoor connecting wires.
Check the room temperature display of
remote controller.
Check the indoor liquid pipe temperature dis-
play of outdoor controller board.